manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ADTRAN
  6. •
  7. Power Supply
  8. •
  9. ADTRAN TOTAL ACCESS 4303 PLUS User manual

ADTRAN TOTAL ACCESS 4303 PLUS User manual

Other ADTRAN Power Supply manuals

ADTRAN NetVanta 1110 User manual

ADTRAN

ADTRAN NetVanta 1110 User manual

ADTRAN NetVanta 1131 RPS/EPS User manual

ADTRAN

ADTRAN NetVanta 1131 RPS/EPS User manual

ADTRAN NetVanta 1000 Series Instruction Manual

ADTRAN

ADTRAN NetVanta 1000 Series Instruction Manual

ADTRAN NT1 T400 User manual

ADTRAN

ADTRAN NT1 T400 User manual

ADTRAN Power Supply/Battery Charger User manual

ADTRAN

ADTRAN Power Supply/Battery Charger User manual

ADTRAN ATLAS 890 User manual

ADTRAN

ADTRAN ATLAS 890 User manual

ADTRAN 61175044L2-22B User manual

ADTRAN

ADTRAN 61175044L2-22B User manual

ADTRAN D4PBCU0 Maintenance and service guide

ADTRAN

ADTRAN D4PBCU0 Maintenance and service guide

ADTRAN Total Access 850 Instruction Manual

ADTRAN

ADTRAN Total Access 850 Instruction Manual

ADTRAN NetVanta 1760-12F User manual

ADTRAN

ADTRAN NetVanta 1760-12F User manual

ADTRAN 4303 DC Manual

ADTRAN

ADTRAN 4303 DC Manual

ADTRAN TOTAL ACCESS MX2800 User manual

ADTRAN

ADTRAN TOTAL ACCESS MX2800 User manual

ADTRAN NetVanta 1131 RPS/EPS User manual

ADTRAN

ADTRAN NetVanta 1131 RPS/EPS User manual

ADTRAN HDSL 851 Instruction Manual

ADTRAN

ADTRAN HDSL 851 Instruction Manual

ADTRAN Total Access 850 Instruction Manual

ADTRAN

ADTRAN Total Access 850 Instruction Manual

ADTRAN 3192 User manual

ADTRAN

ADTRAN 3192 User manual

ADTRAN Total Access 1500 Instruction Manual

ADTRAN

ADTRAN Total Access 1500 Instruction Manual

ADTRAN NT1 ACE4 User manual

ADTRAN

ADTRAN NT1 ACE4 User manual

Popular Power Supply manuals by other brands

Videx 520MR Installation instruction

Videx

Videx 520MR Installation instruction

Poppstar 1008821 Instructions for use

Poppstar

Poppstar 1008821 Instructions for use

TDK-Lambda LZS-A1000-3 Installation, operation and maintenance manual

TDK-Lambda

TDK-Lambda LZS-A1000-3 Installation, operation and maintenance manual

TDK-Lambda 500A instruction manual

TDK-Lambda

TDK-Lambda 500A instruction manual

Calira EVS 17/07-DS/IU operating instructions

Calira

Calira EVS 17/07-DS/IU operating instructions

Monacor PS-12CCD instruction manual

Monacor

Monacor PS-12CCD instruction manual

VOLTIMA MagicBox 15 Installation and operating instructions

VOLTIMA

VOLTIMA MagicBox 15 Installation and operating instructions

Miller Auto Deltaweld 452 owner's manual

Miller

Miller Auto Deltaweld 452 owner's manual

BCP PUOUBK How to install

BCP

BCP PUOUBK How to install

HC 2210 manual

HC

HC 2210 manual

Agilent Technologies 6032A Service manual

Agilent Technologies

Agilent Technologies 6032A Service manual

Radial Engineering SB-48UB user guide

Radial Engineering

Radial Engineering SB-48UB user guide

Puls CT5.241 installation manual

Puls

Puls CT5.241 installation manual

OCZ ZX1250W Technical specifications

OCZ

OCZ ZX1250W Technical specifications

iseg ECH 238 manual

iseg

iseg ECH 238 manual

Agilent Technologies 6631B Service manual

Agilent Technologies

Agilent Technologies 6631B Service manual

Power XXL A Series instruction manual

Power

Power XXL A Series instruction manual

HP 6200B Operating and service manual

HP

HP 6200B Operating and service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

ALARM RELAYS
There are eight alarm relays that provide normally open or normally closed
contacts for each of the following alarms:
■Visual Critical
■Visual Major
■Visual Minor
■Audible Critical
■Audible Major
■Audible Minor
■Auxiliary 1
■Auxiliary 2
POWER SUPPLY 48 PIN CONNECTOR PINOUT
TOTAL ACCESS 4303 PLUS DC POWER SUPPLY
DC SUPPLY
CLEI: SLPOCDBC_ _
DC SUPPLY
PLUS
1202335L1
POWER
TEMP
61202335L1-22A
0401
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
FRONT PANEL LEDs
POWER ●●Off Both –48 VDC fuses blown, power not supplied to the shelf,
or incorrect polarity on the voltage supplied to the shelf
●Green Power supplied is the correct voltage and polarity; backplane
and hot insertion voltages correct
●Amber –48 VDC input and hot insertion voltage present; no back-
plane voltage
●Red –48 VDC input present; no backplane voltage and no hot
insertion voltage
TEMP ●●Off Normal
●Red Over-temperature condition
DESCRIPTION
The Total Access®4303 Plus DC Power Supply is a removable assembly that provides
the voltages necessary for proper system operation. The unit features LEDs for over-
temperature and DC output, an input fuse, and the ability to be hot-swapped when
used with another DC supply in the same chassis. The supply interfaces to the Total
Access backplane through a 48-pin connector. The unit accepts one or two –48 VDC
inputs from the backplane and supplies –48 VDC fused output for use with external
input logic, +5 VDC as hot insertion bias voltage for modules, and +2.1 VDC for back-
plane termination. In addition, the Total Access 4303 Plus DC Supply provides alarm
relay ouputs when installed in slot PS-A.
The following features are supported on the Total Access 4303 Plus DC Power Supply:
■Thermal limit indicator with open collector output
■DC status indicator on the 2.1 and 5 volt outputs with open collector output
■Short circuit protection
■Compatible with existing Total Access DC Power Supplies (P/N 1200335L1)
SPECIFICATIONS
Specifications
Input Voltage –42 VDC to –56 VDC
Operating Temperature –40°C to +65°C
Storage Temperature –40°C to +85°C
Relative Humidity Up to 95% noncondensing
Over Temperature Indication 90°C ±5%
–48 VDC Short Circuit Protection Fused 1-amp slow blow
Backplane Voltage Short Circuit Protection Self-mending
Compliance FCC Part 15, UL 60950, NEBS Level III,
GR-1089-CORE
Pin # Row A Signal Row B Signal Row C Signal
1 AUD_CRIT_NO AUD_CRIT_COM AUD_CRIT_NC
2 AUD_MAJ_NO AUD_MAJ_COM AUD_MAJ_NC
3 AUD_MIN_NO AUD_MIN_COM AUD_MIN_NC
4 VIS_CRIT_NO VIS_CRIT_COM VIS_CRIT_NC
5 VIS_MAJ_NO VIS_MAJ_COM VIS_MAJ_NC
6 VIS_MIN_NO VIS_MIN_COM VIS_MIN_NC
7 AUX1_RLY_NO AUX1_RLY_COM AUX1_RLY_NC
8 AUX2_RLY_NO AUX2_RLY_COM AUX2_RLY_NC
9 –48V_A PS_OK PS_TEMP
10 –48V_B 2.1V PS_PRESENT
11 2.1V 2.1V 2.1V
12 –48V_AB_RTN 2.1V VCC
13 GND GND GND
14 GND GND PSRLY_CLK
15 GND PSRLY_LOAD PSRLY_DATAIN
16 FR_GND –48V PSRLY_DATAOUT
JOBAID
#61202335L1-22A#
TURNUP STEPS
To install the Total Access 4303 Plus DC Power Supply, perform the following steps:
After unpacking the Total Access 4303 Plus DC Power Supply, inspect it for damage. If damage is
found, file a claim with the carrier and then contact ADTRAN®Customer Service.
Pull the ejector tab on the bottom of the Total Access 4303 Plus DC Power Supply into the down
position.
Hold the Total Access 4303 Plus DC Power Supply by the front panel while supporting the bottom
edge of the module and align the module edge with the guide groove for slot PS-A or PS-B in the
chassis. If using only one Total Access Plus DC Power Supply module, insert the module in slot
PS-A in order to use the alarm relay outputs.
Gently but firmly push the module into the selected slot. Simultaneous thumb pressure at the top
(above the POWER LED) and at the bottom (below the electrostatic caution symbol) of the module
will ensure a good seat of the module pins into the backplane connector.
Apply power to the shelf and verify that the POWER LED is green. If the POWER LED does not
illuminate, disconnect power, and verify polarity.
Push the ejector tab up and closed against the module front panel.
To verify one or both –48 VDC supply voltages, use the SCU terminal and navigate to the
following path:
System Status/System Alarms/–48V Bus
COMPLIANCE
This product is NRTL listed to the applicable UL standards. The Total Access 4303 Plus DC Power
Supply is intended for installation in a type “B” or “E” enclosure in a Restricted Access Only area. The
Total Access 4303 shelf Frame Ground terminal must be connected to an earth ground to ensure that
the front panel of the Total Access 4303 Plus DC Power Supply is properly grounded via the backplane
connector.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the user’s authority to
operate this equipment.
WARRANTY
ADTRAN will replace or repair this product within the warranty period if it does not meet its published
specifications or fails while in service. Warranty information can be found at www.adtran.com/warran-
ty. U.S. and Canada customer Faxback: 877-457-5007, Document 414.
TOTAL ACCESS 4303 PLUS DC POWER SUPPLY
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com
61202335L1-22A
Code Input Output
Power Code (PC) F C
Telecommunication Code (TC) – X
Installation Code (IC) A –
1
2
3
4