Rockwell Automation Publication 1606-RM122A-EN-P - September 2021 13
DC Power Supply - 24V, 2.5 A, 60 W, Single-phase Input Reference Manual
Lifetime Expectancy The lifetime expectancies that are shown in the table indicate the minimum
operating hours (service life). The lifetime expectancy of the built-in
electrolytic capacitors determines the lifetime expectancy of the power supply.
Lifetime expectancy is specified in operational hours and is calculated
according to the manufacturer specification of the capacitor.
The manufacturer of the electrolytic capacitors only states a maximum life of
up to 15 years (131,400 h). Any number that exceeds this value is a calculated
theoretical lifetime, which can be used to compare devices.
Mean Time between Failure Mean time between failure (MTBF) is calculated according to statistical device
failures, and indicates reliability of a device. It is the statistical representation
of the likelihood of a unit to fail and does not necessarily represent the life of a
product. An MTBF value of, for example, 1,000,000 h means that statistically
one unit fails every 100 hours if 10,000 units are installed in the field. However,
it cannot be determined if the failed unit has been running for 50,000 h or only
for 100 h. For these types of units, the Mean Time To Failure (MTTF) value is
the same as the MTBF value.
Electromagnetic
Compatibility
The electromagnetic compatibility (EMC) behavior of the device is designed
for applications in industrial, residential, commercial, and light industrial
environments. The device complies with EN 61000-6-1, EN 61000-6-2,
EN 61000-6-3, EN 61000-6-4, EN 61000-3-2, and EN 61000-3-3.
The device complies with FCC Part 15 rules. Operation is subjected to following
two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may
cause undesired operation.
Attributes Values (in kilo hours) Notes
AC 100V AC 120V AC 230V
Lifetime expectancy
146 khr 162 khr 161 khr At 24V, 1.5 A and 40 °C (104 °F)
320 khr 329 khr 277 khr At 24V, 0.75 A and 40 °C (104 °F)
414 khr 459 khr 456 khr At 24V, 1.5 A and 25 °C (77 °F)
905 khr 931khr 782 khr At 24V, 0.75 A and 25 °C (77 °F)
Attributes Values (in kilo hours) Notes
AC 100V AC 120V AC 230V
MTBF SN 29500, IEC 61709 1973 khr 2088 khr 2081 khr At 24V, 1.5 A and 40 °C (104 °F)
3349 khr 3500 khr 3498 khr At 24V, 1.5 A and 25 °C (77 °F)
MTBF MIL HDBK 217F
812 khr 826 khr 748 khr At 24V, 1.5 A, 40 °C (104 °F); Ground Benign GB40(1)
(1) Ground Benign (GB): A non-mobile, temperature, and humidity-controlled environment that is readily accessible to
maintenance. Includes laboratory instruments and test equipment, medical electronic equipment, business and scientific
computer complexes, and missiles and support silos in ground silos.
1122 khr 1144 khr 1044 khr At 24V, 1.5 A, 25 °C (77 °F); Ground Benign GB25(1)
194 khr 200 khr 191 khr At 24V, 1.5 A, 40 °C (104 °F); Ground Fixed GF40(2)
(2) Ground Fixed (GF): Moderately controlled environments such as installations in permanent racks with adequate cooling air
and possible installation in unheated buildings. Includes permanent installation of air traffic control radar and
communication facilities.
253 khr 261 khr 251 khr At 24V, 1.5 A, 25 °C (77 °F); Ground Fixed GF25(2)