manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Argus Security
  6. •
  7. Security Sensor
  8. •
  9. Argus Security A2000L User manual

Argus Security A2000L User manual

A2000L
ANALOGUE PHOTO & CATEGORY A1R HEAT DE-
TECTOR - ALTAIR LITE SERIES
LOOP IN (+)
LOOP IN (-)
LOOP OUT (+)
LOOP OUT (-)
SHIELD
Figure 2
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
928f/02
[email protected] L20-A200L-0001 (vA.5)
GENERAL DESCRIPTION
This type of detector (figure 1) continuously samples the air and the temperature variation in the
protected area to provide the earliest warning of fire, offering, at the same time, a high level of
false alarm rejection.
The particular design of the smoke entry ports limits potential contamination, extends maintenance
periods and does not compromise smoke response sensitivity.
These detectors are designed for an open area protection and must only be connected to control
panels that use the Altair analogue-intelligent addressable communication protocol for monitoring
and control, providing high rates of information exchange and fast and secure responses.
Note: Before installing this device please thoroughly read this leaflet and refer to the applicable
European Standards and National Codes of Practice (e.g. BS5839-1:2002 for UK) for guidance on location, spacing and acceptable
use. Also seek guidance from the compatible control panel instructions to ensure appropriate design criteria and configuration specifi-
cations are followed.
INSTALLATION
For the installation to the ceiling, the detector must be mounted only on the compatible adaptor bases listed in the “TECHNICAL
SPECIFICATIONS” table. Refer to the specific base’s literature for further details.
WIRING
After having installed the base to the ceiling, wiring has to be carried out in order to connect the base to the analogue loop and, so, to
the installation.
Analogue loop wires must be correctly connected to the base’s terminals: check the performed wiring by referring to the figure 2
diagram.
Figure 1
REMOTE OUTPUT CAPABILITY
Remote output capability is available as a standard feature, so a
remote indication lamp or a compatible slave platform sounder
(check power requirements and loop drive limits) may be wired to
the base terminals (Figure 3).
If other equipment is connected to the remote output, its
supply current must be eventually limited by using an ade-
quate resistor. Consult the TECHNICAL SPECIFICATIONS
table and assess the external device current absorption’s
value.
DEVICE PROGRAMMING - ADDRESS SETTING
Detectors can be addressed using a special hand-held program-
ming unit. Addresses may be selected from a range from 1 to
240, although, of course, each device on the loop must have a
unique address.
Automatic addressing by the control panel cannot be performed
with this type of device.
DEVICE PROGRAMMING - SENSITIVITY SETTING
A choice of four smoke sensitivity levels is available; if such
feature is provided, this level can be set through the control panel.
Level 1 is most sensitive and level 4 is the least sensitive.
No thermal sensitivity level can be selected on this detector
model.
DETECTOR PLACEMENT
1) Position the detector centrally on its adaptor base ensuring it is
level.
2) Rotate clockwise applying gentle pressure. The detector will drop into its keyed
location.
3) Continue to rotate clockwise a few degrees until the detector has fully engaged in
the adaptor base (figure 4).
4) When the detector is firmly engaged, check the alignment of the raised reference
marks on the detector and on the base (figure 5).
IMPORTANT NOTES ON DETECTORS PLACEMENT
Disconnect loop power before installing the detector.
Dust covers help to protect the devices during shipping and when first installed.
They are not intended to provide complete protection against contamination, there-
fore, detectors should be removed before construction, major re-decoration or other
dust producing work is started. Dust covers must be removed before the system can
be made operational.
Figure 5
Figure 4
REMOTE
ALARM (+)
REMOTE
ALARM (-)
Figure 3
HEAT TEST
Use a hair dryer of 1000-1500 W or an heat tool from an approved manufacturer. Direct the heat towards the detector from its side.
Hold the heat source at about 15 cm away from the detector in order to prevent damage to its cover during testing.
The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LEDs should be activated by
the control panel itself.
MAINTENANCE
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted alarm or fault condi-
tions. Remove the detector from its mounting base to allow inspection in good light at ground level. Inspect the smoke entry ports
around the detector and the thermistor area and use a small, soft bristle brush to dislodge any evident contaminants such as insects,
spider webs, hairs, etc. Use a small vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small
particles from the smoke entry screen area and the thermistor area. Wipe the exterior housing of the detector with a clean, damp, lint
free cloth to remove any surface film that can later attract airborne contaminants. Use the hand-held programming unit to read the
pollution percentage of the chamber; please, refer to the programming unit instruction manual. After all detectors have been inspect-
ed, repositioned on their mounting bases and power has been re-applied, check correct operation by testing the device.
TECHNICAL SPECIFICATIONS **
* Product operates down to 15 V, but without LED indication.
** Further technical data: see document TDS-A200L held by the manufacturer.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly
resistant to environmental deterioration. However, after 10 years of continuous operation, it is
advisable to replace the devices in order to minimize the risk of reduced performance caused
by external factors. Ensure that this device is only used with compatible control panels. Detec-
tion systems must be checked, serviced and maintained on a regular basis to confirm correct
operation.
Smoke detectors may respond differently to various kinds of smoke particles, thus application
advice should be sought for special risks. Detectors cannot respond correctly if barriers exist
between them and the fire location and may be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engi-
neering standards. Appropriate risk assessment should be carried out initially to determine
correct design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materi-
als or manufacturing defects, effective from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect
handling or usage. Product must be returned via your authorized supplier for repair or replace-
ment together with full information on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon request.
ANTI -TAMPER DETECTOR LOCK
The detector can be locked to its base as a deterrent to intentional removal performed by non authorized personnel.
Using a cutter, remove the anti-tamper plastic detail, as illustrated in figure 6.
To unlock the detector, insert the tip of a screwdriver into the side slot of the base by exerting only a light pressure (figure 7), and
release the detector by turning it anticlockwise.
LED INDICATORS
This detector is equipped with two red LEDs; their flash pattern indicate the present condition of
the detector itself:
Blinking: indicates the normal operative status of the detector; the performance of this pattern
depends upon the control panel’s model and its settings.
Continuous: indicates an alarmed condition of the detector.
Fault conditions are not indicated by LEDs, but only on the control panel.
Positioning of these LEDs is illustrated in figure 8.
IDENTIFICATION TAB
The adaptor base is equipped with a plastic tab where identification data can be visibly displayed.
Detach the tab from the base; write or label it with the required information, then insert it into its adaptor base’s slot.
TESTING THE DETECTORS - PRELIMINARY NOTE
Detectors should be tested after installation and during periodic maintenance visits; it is recommended each device should be tested
at least once per year.
After each test reset the system and allow at least one minute for power stabilisation.
AEROSOL TEST (SIMULATED SMOKE TEST)
For this test only use test aerosols from an approved manufacturer, in accordance with their application instructions, in order to
prevent contamination or possible damage to the detector. We suggest to spray the aerosol into the detector by using a recommend-
ed applicator. The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should
be activated by the control panel itself.
If the detector does not respond to the tests correctly it may be necessary to clean it: in this case follow the instructions indicated in
the “MAINTENANCE” paragraph.
If testing fails again after maintenance then replace the detector with a new one and return the faulty one for servicing.
Figure 8
Power supply *from 18 V (min) to 40 V (max)
Average standby current consumption 55 uA @ 24 V
Remote output max current consumption (externally limited) 20 mA
Compatible adaptor bases LAB1000 - “Low Profile Adaptor Base”
Thermal alarm threshold (ROR A1R category) 58 °C
Operating temperature range -30 °C / +70 °C (no icing)
Humidity 95% RH (no condensation)
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy
EN 54-5:2017 + A1:2018
EN 54-7:2018
CEA 4021: July 2003
A2000L
For use in compatible fire detection and
alarm system.
Category A1R
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it [email protected] L20-A200L-0001 (vA.5)
Figure 7
Figure 6
Figure 9
2831 0832
14 21
AT5010CPR AT5010UK

This manual suits for next models

1

Other Argus Security Security Sensor manuals

Argus Security TAURUS TW-DO-01 User manual

Argus Security

Argus Security TAURUS TW-DO-01 User manual

Argus Security ALTAIR LITE Series User manual

Argus Security

Argus Security ALTAIR LITE Series User manual

Argus Security L-MC-SG User manual

Argus Security

Argus Security L-MC-SG User manual

Argus Security V100 User manual

Argus Security

Argus Security V100 User manual

Argus Security Taurus TW-DT-01/916 User manual

Argus Security

Argus Security Taurus TW-DT-01/916 User manual

Argus Security L-OP-SG Operating and maintenance instructions

Argus Security

Argus Security L-OP-SG Operating and maintenance instructions

Argus Security TW-DM-01/916 User manual

Argus Security

Argus Security TW-DM-01/916 User manual

Argus Security TAURUS TW-DM-01/BL User manual

Argus Security

Argus Security TAURUS TW-DM-01/BL User manual

Argus Security TAURUS TW-DT-01/BL User manual

Argus Security

Argus Security TAURUS TW-DT-01/BL User manual

Argus Security V350 User manual

Argus Security

Argus Security V350 User manual

Argus Security TAURUS TW-MI-S-01/916 User manual

Argus Security

Argus Security TAURUS TW-MI-S-01/916 User manual

Argus Security Taurus TW-SK-01 User manual

Argus Security

Argus Security Taurus TW-SK-01 User manual

Argus Security L-HT-SG User manual

Argus Security

Argus Security L-HT-SG User manual

Argus Security Taurus TW-DT-01/BL User manual

Argus Security

Argus Security Taurus TW-DT-01/BL User manual

Argus Security Taurus TW-MO-SB-01/916 User manual

Argus Security

Argus Security Taurus TW-MO-SB-01/916 User manual

Argus Security V200 User manual

Argus Security

Argus Security V200 User manual

Argus Security L-MC-SG/865 User manual

Argus Security

Argus Security L-MC-SG/865 User manual

Argus Security TAURUS TW-DT-01 User manual

Argus Security

Argus Security TAURUS TW-DT-01 User manual

Argus Security VCP100 User manual

Argus Security

Argus Security VCP100 User manual

Argus Security SG200 User manual

Argus Security

Argus Security SG200 User manual

Argus Security ALTAIR Series User manual

Argus Security

Argus Security ALTAIR Series User manual

Argus Security SG200-IS User manual

Argus Security

Argus Security SG200-IS User manual

Argus Security ALTAIR Series User manual

Argus Security

Argus Security ALTAIR Series User manual

Argus Security LW-DMCO-01 User manual

Argus Security

Argus Security LW-DMCO-01 User manual

Popular Security Sensor manuals by other brands

Tongdy PMD-18 Series manual

Tongdy

Tongdy PMD-18 Series manual

GasTech F-GUARD IR3-HD user manual

GasTech

GasTech F-GUARD IR3-HD user manual

Baumer URDK 10P8914/KS35A quick start guide

Baumer

Baumer URDK 10P8914/KS35A quick start guide

2M Technology 2MTHFR-2M user manual

2M Technology

2M Technology 2MTHFR-2M user manual

Recco R9 quick guide

Recco

Recco R9 quick guide

SKYLOTEC LORY Series Instructions for use

SKYLOTEC

SKYLOTEC LORY Series Instructions for use

Comunello Automation DART Installation and user manual

Comunello Automation

Comunello Automation DART Installation and user manual

GASTRON GTL-200 instruction manual

GASTRON

GASTRON GTL-200 instruction manual

Eaton MAB50R Installation and operation manual

Eaton

Eaton MAB50R Installation and operation manual

WatchGas NEO user manual

WatchGas

WatchGas NEO user manual

Optex URX-P01WH Installation instructions and operators manual

Optex

Optex URX-P01WH Installation instructions and operators manual

Inficon IRwin quick start guide

Inficon

Inficon IRwin quick start guide

PCB Piezotronics Tourmaline ICP 138A02 Installation and operating manual

PCB Piezotronics

PCB Piezotronics Tourmaline ICP 138A02 Installation and operating manual

Powerfix Profi PMDL 5 A1 operating instructions

Powerfix Profi

Powerfix Profi PMDL 5 A1 operating instructions

Satel ASD-100 manual

Satel

Satel ASD-100 manual

Chauvin Arnoux 760N user manual

Chauvin Arnoux

Chauvin Arnoux 760N user manual

THORLABS PDA50B2 user guide

THORLABS

THORLABS PDA50B2 user guide

Siemens FDOOT241-A3 manual

Siemens

Siemens FDOOT241-A3 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.