manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Argus Security
  6. •
  7. Security Sensor
  8. •
  9. Argus Security S2000 User manual

Argus Security S2000 User manual

L20-S2000-0001 (v1.0)
S2000
CONVENTIONAL PHOTO & CLASS A1R HEAT DETECTOR
Picture 2 - Wiring
used when the
alarm current is
limited by the
control panel.
TECHNICAL SPECIFICATIONS
Power supply 10 - 30 Vdc
Average standby current 90 uA @ 24 V
Maximum allowed alarm current 40 mA (externally limited)
Maximum allowed remote device
current 20 mA (externally limited)
Operating temperature range -30 °C / +70 °C
(no condensation)
Humidity 95% RH
(no condensation)
Ingress protection rating IP 21C
Alarm temperature threshold
(class A1R) 58 °C
ARGUS SECURITY S.R.L. - Via Archimede 42, 20041, Agrate Brianza, Milano, Italy www.argussecurity.it [email protected]
LINE IN
POSITIVE (+)
LINE IN
NEGATIVE (-) LINE OUT
POSITIVE (+)
LINE OUT
NEGATIVE (-)
REMOTE INDICATOR
END OF LINE RESISTOR
WIRING - BASE WITHOUT RESISTOR
This configuration is to be used only when the control panel limits the alarm current to less than the sensor’s allowed maximum value
(picture 2).
IMPORTANT INSTALLATION WARNINGS
CONFIRM YOUR SYSTEM’S COMPATIBILITY BY CONSULTING WITH YOUR SUPPLIER OR WITH THE CONTROL PANEL’S
MANUFACTURER.
FOR SPECIFIC INFORMATION REGARDING DETECTOR AND DEVICE’S SPACING, PLACEMENT AND SPECIAL APPLICA-
TIONS REFER TO YOUR SPECIFIC NATIONAL OR INTERNATIONAL STANDARD CODES OF PRACTICE.
BEFORE INSTALLATION ENSURE THAT POWER IS REMOVED FROM THE SYSTEM.
DURING DEVICE’S CABLING, REMEMBER THAT CONNECTIONS TO THE TERMINALS ARE POLARITY SENSITIVE: SO,
PLEASE, CHECK THEM BY REFERRING TO THE WIRING INFORMATION GIVEN IN THIS MANUAL.
REMEMBER THAT THE ALARM CURRENT ABSORBED BY THE SENSOR MUST BE LIMITED IN ORDER TO AVOID PERMA-
NENT DAMAGE (SEE THE FOLLOWING PARAGRAPHS).
LIMITATION OF THE ALARM CURRENT
When alarmed, the detector absorbs more current than usually does when quiescent: the absorbed current by the sensor in this state
is indicated as “alarm current”; since:
IF THE ALARM CURRENT EXCEEDS THE MAXIMUM SPECIFIED VALUE (SEE THE TECHNICAL SPECIFICATIONS TABLE),
THE DETECTOR CAN BE PARMANENTLY DAMAGED!
So, the alarm current must be limited in two different ways:
1) having a control panel which limits the alarm current through an in-built limiter.
2) By limiting the alarm current through a resistor fitted on the detector base (see the following wiring paragraphs).
If a remote LED indicator or another remote device is connected to the adaptor base and, so, the sensor, remember that:
ITS ABSORBED CURRENT WILL BE ADDED THE SENSOR’S ALARM CURRENT.
ADAPTOR BASE INSTALLATION
In order to fix a sensor to the wall it is necessary to use its adequate adaptor base. So:
1) select the position where you want to install the sensor and the base.
2) Install the base in the selected position by inserting the screws in the points indicated in picture 1.
Picture 1 - Wall fixing screw entry
points on the adaptor base.
ARGUS SECURITY S.R.L.
Via Archimede, 42
20041, Agrate Brianza,
Milano
Italy
EN 54-7
Point type smoke detector
(optical)
EN 54-5
Point type heat detector
Class A1R
S2000
Technical data: see docu-
ment TDS-S2000 held by
the manufacturer.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to
environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the
devices in order to minimize the risk of reduced performance caused by external factors. Ensure that this
device is only used with compatible control panels. Detection systems must be checked, serviced and
maintained on a regular basis to confirm correct operation.
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice
should be sought for special risks. Sensors cannot respond correctly if barriers exist between them and
the fire location and may be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engineering stan-
dards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and up-
dated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manu-
facturing defects, effective from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling
or usage.
Product must be returned via your authorized supplier for repair or replacement together with full informa-
tion on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon request.
GENERAL DESCRIPTION
This type of detector continuously samples the air and the temperature variation in the protected area to provide the earliest warning
of fire and yet offers a high level of false alarm rejection. This device benefits from a “Double Dust Trap” incorporated into the design
of the smoke entry ports, hence limiting potential contamination and extending periods between maintenance without compromising
sensitivity of response. These detectors are designed for open area protection and must only be connected to conventional control
panels. The centrally positioned red LED indicator provides 360°visibility and thus does not require any orientation during installation.
An in-built magnet test allows easy activation to verify correct functioning of the detectors on site.
REMOTE OUTPUT CAPABILITY
Remote output capability is available as a standard feature so a remote indication lamp or a compatible platform sounder (check
power requirements) may be wired to the base terminals.
If other equipment is connected to the remote output, its supply current must be eventually limited by using an adequate
resistor. Consult the TECHNICAL SPECIFICATIONS table and assess the external device current absorption’s value.
INSTALLATION
1.Position the detector centrally on its mounting base.
2.Rotate clockwise applying gentle pressure. The detector will
drop into its mechanical holding location.
3.Push the detector to win the force of the contacts.
4.Continue to rotate clockwise a few degrees until the detector is
firmly held on the detector base.
5.When the detector is firmly held verify the alignment between
the detector and the raised marks on the base (picture 5).
6.After installing all detectors, apply power to the fire security
system.
7.Test the detectors as described in the paragraph headed
“TESTING”.
Picture 3 - Wiring used
when the alarm current
is limited by the resistor
on the mounting base.
1. Position the detector.
2. Rotate.
3. Push.
4. Rotate.
CAUTION
Dust covers help to protect the devices during
shipping and when first installed. They are not
intended to provide complete protection against
contamination, therefore, sensors should be
removed before construction, major re-decoration
or other dust producing work is started. DUST
COVERS MUST BE REMOVED BEFORE THE
SYSTEM CAN BE MADE OPERATIONAL.
TESTING
Sensors should be tested after installation and during periodic maintenance visits (it is recommended each device should be tested at
least once per year). When the system has been reset, allow, after each test, at least one minute for power stabilisation before the
next test. Detectors can be tested as follows:
ANTI-TAMPER MECHANICAL BLOCK FEATURE
The sensor may be blocked onto its base by remov-
ing the small plastic element on the base’s detector
blocking tongue by using a suitable tool (e.g. a
small screwdriver) inserted through the access hole
on the side of the mounting base (picture 4).
To remove the sensor from the base, if mechani-
cally blocked, insert a suitable tool through the
access hole on the side of the mounting base
(picture 4).
TAMPER DETECTION
Each detector’s mounting base has two “–” marked terminals. These are electrically identical, but they are connected to each other
only when a detector is correctly fitted onto the base; this feature is used in combination with an appropriate “end of line” (EOL)
component, designated by the control panel manufacturer, in order to indicate a fault condition if a detector is removed from its
base. To enable the function to operate correctly it is important that incoming and outgoing negative wires are separated in the
above said way
Picture 4 - The anti-tamper block and its handling.
Picture 5 - The correctly installed detector.
Magnet
test position
(model TMD-01).
Alignment between base and detector.
ARGUS SECURITY S.R.L. - Via Archimede 42, 20041, Agrate Brianza, Milano, Italy www.argussecurity.it [email protected] L20-S2000-0001 (v1.0)
LINE IN
POSITIVE (+)
LINE IN
NEGATIVE (-) LINE OUT
POSITIVE (+)
LINE OUT
NEGATIVE (-)
REMOTE INDICATOR
END OF LINE RESISTOR
WIRING - BASE WITH RESISTOR AND BASE WITH RESITOR AND SCHOTTKY DIODE
This configuration is to be used when the alarm current depends only on the value of the resistor fitted on the base (picture 3).
Magnet test
Position the magnet (model TMD-01, optional) next to the sensor between the two raised
marks on the base (picture 5).
The magnet test verifies the function of all electronic circuits of the sensor and its com-
munication with the control panel.
The sensor should trigger an alarm condition on the control panel and turn the red LED
on.
Aerosol (simulated smoke) test
Use a test aerosol from an approved manufacturer in accordance with their application
instructions. This is important to prevent contamination or possible damage.
The red LED alarm indicator on the detector should illuminate (normally within 60 sec-
onds, but may vary) and trigger an alarm condition on the control panel.
Heat test
Use a hair dryer of 1000-1500 W or an heat tool from an approved manufacturer.
Direct the heat towards the sensor from its side. Hold the heat source at about 15 cm
away from the sensor in order to prevent damage to its cover during testing.
The red LED on the detector should latch into alarm and the control panel should
activate into alarm condition.
If testing fails after installation or maintenance then replace the sensor and return
it for servicing.
MAINTENANCE
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted fault conditions.
Remove the sensor from its mounting base to allow inspection in good light at ground level. Inspect the smoke entry ports around the
sensor and the thermistor area; use a small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs,
hairs, etc. Use a small vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small particles from the
smoke entry screen area and the thermistor area. Wipe the exterior housing of the sensor with a clean, damp, lint free cloth to re-
move any surface film that can later attract airborne contaminants. After all sensors have been inspected, repositioned on their
mounting bases and power has been re-applied, check correct operation as described under the “TESTING” paragraph.

Other Argus Security Security Sensor manuals

Argus Security L-HT-SG User manual

Argus Security

Argus Security L-HT-SG User manual

Argus Security TAURUS TW-DT-01 User manual

Argus Security

Argus Security TAURUS TW-DT-01 User manual

Argus Security Taurus TW-MO-SB-01/916 User manual

Argus Security

Argus Security Taurus TW-MO-SB-01/916 User manual

Argus Security TAURUS TW-DO-01 User manual

Argus Security

Argus Security TAURUS TW-DO-01 User manual

Argus Security Taurus TW-DT-01/916 User manual

Argus Security

Argus Security Taurus TW-DT-01/916 User manual

Argus Security Taurus TW-SK-01 User manual

Argus Security

Argus Security Taurus TW-SK-01 User manual

Argus Security L-OP-SG Operating and maintenance instructions

Argus Security

Argus Security L-OP-SG Operating and maintenance instructions

Argus Security SG200-IS User manual

Argus Security

Argus Security SG200-IS User manual

Argus Security L-MC-SG/865 User manual

Argus Security

Argus Security L-MC-SG/865 User manual

Argus Security V200 User manual

Argus Security

Argus Security V200 User manual

Argus Security TAURUS TW-MI-S-01/916 User manual

Argus Security

Argus Security TAURUS TW-MI-S-01/916 User manual

Argus Security VCP100 User manual

Argus Security

Argus Security VCP100 User manual

Argus Security A3500 User manual

Argus Security

Argus Security A3500 User manual

Argus Security L-HT-SG User manual

Argus Security

Argus Security L-HT-SG User manual

Argus Security TW-DM-01/916 User manual

Argus Security

Argus Security TW-DM-01/916 User manual

Argus Security A2000L User manual

Argus Security

Argus Security A2000L User manual

Argus Security ALTAIR LITE Series User manual

Argus Security

Argus Security ALTAIR LITE Series User manual

Argus Security SG350-IS User manual

Argus Security

Argus Security SG350-IS User manual

Argus Security LW-DMCO-01 User manual

Argus Security

Argus Security LW-DMCO-01 User manual

Argus Security V350 User manual

Argus Security

Argus Security V350 User manual

Argus Security L-MC-SG User manual

Argus Security

Argus Security L-MC-SG User manual

Argus Security ALTAIR Series User manual

Argus Security

Argus Security ALTAIR Series User manual

Argus Security V100 User manual

Argus Security

Argus Security V100 User manual

Argus Security Taurus TW-DM-01 User manual

Argus Security

Argus Security Taurus TW-DM-01 User manual

Popular Security Sensor manuals by other brands

Tongdy PMD-18 Series manual

Tongdy

Tongdy PMD-18 Series manual

GasTech F-GUARD IR3-HD user manual

GasTech

GasTech F-GUARD IR3-HD user manual

Baumer URDK 10P8914/KS35A quick start guide

Baumer

Baumer URDK 10P8914/KS35A quick start guide

2M Technology 2MTHFR-2M user manual

2M Technology

2M Technology 2MTHFR-2M user manual

Recco R9 quick guide

Recco

Recco R9 quick guide

SKYLOTEC LORY Series Instructions for use

SKYLOTEC

SKYLOTEC LORY Series Instructions for use

Comunello Automation DART Installation and user manual

Comunello Automation

Comunello Automation DART Installation and user manual

GASTRON GTL-200 instruction manual

GASTRON

GASTRON GTL-200 instruction manual

Eaton MAB50R Installation and operation manual

Eaton

Eaton MAB50R Installation and operation manual

WatchGas NEO user manual

WatchGas

WatchGas NEO user manual

Optex URX-P01WH Installation instructions and operators manual

Optex

Optex URX-P01WH Installation instructions and operators manual

Inficon IRwin quick start guide

Inficon

Inficon IRwin quick start guide

PCB Piezotronics Tourmaline ICP 138A02 Installation and operating manual

PCB Piezotronics

PCB Piezotronics Tourmaline ICP 138A02 Installation and operating manual

Powerfix Profi PMDL 5 A1 operating instructions

Powerfix Profi

Powerfix Profi PMDL 5 A1 operating instructions

Satel ASD-100 manual

Satel

Satel ASD-100 manual

Chauvin Arnoux 760N user manual

Chauvin Arnoux

Chauvin Arnoux 760N user manual

THORLABS PDA50B2 user guide

THORLABS

THORLABS PDA50B2 user guide

Siemens FDOOT241-A3 manual

Siemens

Siemens FDOOT241-A3 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.