AUMA SAEx 25.1 User manual

Control
→Parallel
Profibus DP
Modbus RTU
Modbus TCP/IP
Foundation Fieldbus
HART
Profinet
Multi-turn actuators
SAEx 25.1 –SAEx 40.1
SAREx 25.1 –SAREx 30.1
Control unit - electromechanical
with actuator controls
ACExC 01.2 on wall bracket
Assembly, operation, commissioningOperation instructions

Read operation instructions first.
●Observe safety instructions.
●These operation instructions are part of the product.
●Store operation instructions during product life.
●Pass on instructions to any subsequent user or owner of the product.
Target group:
This document contains information for assembly, commissioning and maintenance staff.
Reference documents:
●Manual (Operation and setting ) of actuator controls ACExC 01.2 Parallel
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
61. Safety instructions................................................................................................................. 61.1. Prerequisites for the safe handling of the product 61.2. Range of application 71.3. Warnings and notes 71.4. References and symbols
92. Identification........................................................................................................................... 92.1. Short description 102.2. Name plate
153. Transport and storage........................................................................................................... 153.1. Transport 163.2. Storage
174. Assembly................................................................................................................................ 174.1. Mounting position 174.2. Handwheel fitting 184.3. Multi-turn actuator: mount to valve/gearbox 184.3.1. Design of output drive type A 184.3.1.1. Stem nut for output drive type A: finish machining 204.3.1.2. Multi-turn actuator with output drive type A:mount 214.3.2. Design of output drive types B and E 214.3.2.1. Multi-turn actuator with output drive type B:mount 224.4. Accessories for assembly 224.4.1. Stem protection tube for rising valve stem
245. Electrical connection............................................................................................................. 245.1. Basic information 265.2. Cable installation for wall bracket and control box 285.3. Electrical connection of actuator 285.3.1. Motor connection 285.3.1.1. Motor connection compartment: open 295.3.1.2. Motor cables: connect 305.3.1.3. Motor connection compartment: close 305.3.2. Electrical connection (K/KR) 305.3.2.1. Terminal compartment: open
2
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Table of contents ACExC 01.2

315.3.2.2. Cable connection 325.3.2.3. Terminal compartment: close 335.4. Electrical connection of actuator controls 335.4.1. KP/KPH electrical connection 345.4.1.1. Terminal compartment: open 355.4.1.2. Cable connection 365.4.1.3. Terminal compartment: close 375.4.2. KES electrical connection 385.4.2.1. Terminal compartment: open 395.4.2.2. Cable connection 405.4.2.3. Terminal compartment: close 415.4.3. KT/KM electrical connection 425.4.3.1. Terminal compartment: open 435.4.3.2. Cable connection 455.4.3.3. Terminal compartment: close 465.5. External earth connection 475.6. Accessories for electrical connection 475.6.1. Parking frame
486. Operation................................................................................................................................ 486.1. Manual operation 486.1.1. Engage manual operation 496.1.2. Manual operation: disengage 496.2. Motor operation 496.2.1. Operating the actuator from local controls 506.2.2. Actuator operation from remote 506.3. Menu navigation via push buttons (for settings and indications) 516.3.1. Menu layout and navigation 526.4. User level, password 536.4.1. Password entry 536.4.2. Password change 546.5. Language in the display 546.5.1. Language change
567. Indications.............................................................................................................................. 567.1. Indications during commissioning 567.2. Indications in the display 577.2.1. Feedback indications from actuator and valve 597.2.2. Status indications according to AUMA classification 607.2.3. Status indications according to NAMUR recommendation 627.3. Indication lights of local controls 637.4. Optional indications 637.4.1. Mechanical position indication via indicator mark
648. Signals (output signals)......................................................................................................... 648.1. Status signals via output contacts (digital outputs) 648.1.1. Assignment of outputs 648.1.2. Coding the outputs 648.2. Analogue signals (analogue outputs)
659. Commissioning (basic settings)........................................................................................... 659.1. Heat-up time for low temperature version 659.2. Type of seating: set
3
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Table of contents

669.3. Switch compartment: open 679.4. Torque switching: set 679.5. Limit switching: set 689.5.1. End position CLOSED (black section): set 689.5.2. End position OPEN (white section): set 699.6. Test run 699.6.1. Direction of rotation at mechanical position indicator: check 709.6.2. Direction of rotation at hollow shaft/stem: check 709.6.3. Limit switching: check 719.6.4. Reference operation position feedback: perform 719.7. Switch compartment: close
7210. Commissioning (optional equipment settings)................................................................... 7210.1. Potentiometer 7210.1.1. Potentiometer: set 7210.2. RWG electronic position transmitter 7310.2.1. Measuring range: set 7410.3. Intermediate positions: set 7410.3.1. Running direction CLOSE (black section): set 7410.3.2. Running direction OPEN (white section): set 7510.4. Mechanical position indicator: set
7611. Corrective action.................................................................................................................... 7611.1. Faults during commissioning 7611.2. Fault indications and warning indications 8011.3. Fuses 8011.3.1. Fuses within the actuator controls 8111.3.2. Fuse replacement 8111.3.2.1. Replace fuses F1/F2 8211.3.2.2. Test/replace fuses F3/F4 8211.3.3. Fuses within the control box 8311.3.4. Motor protection (thermal monitoring)
8512. Servicing and maintenance................................................................................................... 8512.1. Preventive measures for servicing and safe operation 8612.2. Disconnection from the mains 8612.2.1. Disconnection from the mains with KP/KPH and KES electrical connection 8712.2.2. Disconnection from the mains with KT/KM electrical connection 8812.3. Maintenance 8812.4. Disposal and recycling
9013. Technical data......................................................................................................................... 9013.1. Technical data Multi-turn actuators 9313.2. Technical data Actuator controls 9713.3. Technical data Control box
9814. Spare parts............................................................................................................................. 9814.1. Multi-turn actuators SAEx 25.1 –SAEx 40.1/SAREx 25.1 –SAREx 30.1 10014.2. Actuator controls ACExC 01.2 KP/KPH 10214.3. Actuator controls AUMATIC ACExC 01.2 KES 10414.4. Actuator controls ACExC 01.2 KT/KM 10614.5. ExC wall bracket
4
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Table of contents ACExC 01.2

108Index........................................................................................................................................
111Addresses...............................................................................................................................
5
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Table of contents

1. Safety instructions
1.1. Prerequisites for the safe handling of the product
Standards/directives The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others standards and directives such as IEC 60079 “Explosive
atmospheres".
●Part 14: Electrical installations design, selection and erection.
●Part 17: Electrical installations inspection and maintenance.
Safety instructions/
warnings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Work performed in potentially explosive atmospheres is subject to special regulations
which have to be observed.The end user or contractor of the plant is responsible
for respect and control of these regulations, standards, and laws.
Commissioning Prior to commissioning, imperatively check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
●Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●Only operate the device if it is in perfect condition while observing these instruc-
tions.
●Immediately report any faults and damage and allow for corrective measures.
●Observe recognised rules for occupational health and safety.
●Observe national regulations.
●During operation,thehousing warms upandsurfacetemperatures >60°C may
occur.To prevent possible burns, we recommend checking the surface temper-
ature using an appropriate thermometer and wearing protective gloves, prior
to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
The devices described below are approved for use in the potentially explosive
atmospheres of zones 1, 2, 21, and 22.
6
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Safety instructions ACExC 01.2

If temperatures >40 °C are to be expected at the valve flange or the valve stem (e.g.
due to hot media), please consult AUMA.Temperatures > 40 °C are not considered
with regards to the non-electrical explosion protection.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
●Industrial trucks according to EN ISO 3691
●Lifting appliances according to EN 14502
●Passenger lifts according to DIN 15306 and 15309
●Service lifts according to EN 81-1/A1
●Escalators
●Continuous duty
●Buried service
●Continuous submersion (observe enclosure protection)
●Potentially explosive areas of zones 0 and 20
●Potentially explosive areas of group I (mining)
●Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
These operation instructions are only valid for the “clockwise closing”standard
version, i.e. driven shaft turns clockwise to close the valve. For “counterclockwise
closing”version, a supplement must be observed in addition to these operation
instructions.
1.3. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning results in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk.Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning could result in minor or moderate injury. May also be
used with property damage.
Potentially hazardous situation. Failure to observe this warning could result
in property damage. Is not used for personal injury.
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
7
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Safety instructions

Symbol for OPEN (valve open)
Via the menu to parameter
Describes the menu path to the parameter.When using the push buttons of local
controls, the required parameter can be quickly found on the display. Display texts
are shaded in grey: Display.
Wiring diagram Texts extracted from other documents
Texts extracted from other documents are highlighted in a different font.For example
Wiring diagram.
➥Result of a process step
Describes the result of a preceding process step.
8
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Safety instructions ACExC 01.2

2. Identification
2.1. Short description
Multi-turn actuator Definition in compliance with EN 15714-2/EN ISO 5210:
A multi-turn actuator is an actuator which transmits torque to a valve for at least one
full revolution.It is capable of withstanding thrust.
Figure 1: Example, Multi-turn actuator SAEx 25.1
AUMA multi-turn actuators SAEx 25.1 –SAEx 40.1/SAREx 25.1 –SAREx 30.1 are
driven by an electric motor and are capable of withstanding thrust in combination
with output drive type A.For manual operation, a handwheel is provided. Switching
off in end positions may be either by limit or torque seating.Actuator controls are
required to operate or process the actuator signals.
Actuator controls ACExC 01.2 actuator controls are used to operate AUMA actuators and are supplied
ready for use.In combination with multi-turn actuators SAEx 25.1 –SAEx 40.1/SAREx
25.1 –SAREx 30.1, they are mounted separately on a wall bracket.For high nominal
motor currents of the actuator, the switchgear of the actuator controls additionally
require a control box.
Figure 2: Actuator controls and control box
[1] Actuator controls on wall bracket
[2] Control box
The functions of actuator controls include standard valve control in OPEN-CLOSE
duty, positioning, process control, logging of operating data right through to diagnostic
functions.ACExC 01.2
Local controls/
AUMA CDT Operation, setting, and display can be performed directly at the actuator controls.
When set to local control, it is possible to
●operate the actuator via the local controls (push buttons and display) and perform
settings (contents of these instructions).
●read in or out data or modify and save settings via AUMA CDT software (ac-
cessory), using a computer (laptop or PC).The connection between computer
and actuator controls is wireless via Bluetooth interface (not included in these
instructions).
9
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Identification

2.2. Name plate
Figure 3: Arrangement of name plates
[1] Actuator name plate
[2] Actuator controls name plate
[3] Motor name plate
[4] Additional plate, e.g. KKS plate (Power Plant Classification System)
[5] Explosion protection approval plate
Actuator name plate
Figure 4: Actuator name plate (example)
(= manufacturer logo); (= CE mark)
[1] Name of manufacturer
[2] Address of manufacturer
[3] Type designation
[4] Order number
[5] Serial number
[6] Speed
[7] Torque range in direction CLOSE
[8] Torque range in direction OPEN
[9] Type of lubricant
[10] Permissible ambient temperature
[11] Can be assigned as an option upon customer request
[12] Enclosure protection
[13] Data Matrix code
10
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Identification ACExC 01.2

Actuator controls name plate
Figure 5: Actuator controls name plate
[1] Type designation
[2] Order number
[3] Serial number
[4] Actuator terminal plan
[5] Actuator controls terminal plan
[6] Mains voltage
[7] AUMA power class for switchgear
[8] Permissible ambient temperature
[9] Enclosure protection
[10] Control
[11] Data Matrix code
Motor name plate
Figure 6:Typenschild Motor (Beispiel)
(= manufacturer logo); (= CE mark)
[1] Motor type
[2] Motor article number
[3] Serial number
[4] Current type, mains voltage
[5] Rated power
[6] Rated current
[7] Type of duty
[8] Enclosure protection
[9] Motor protection (temperature protection)
[10] Insulation class
[11] Speed
[12] Power factor cos phi
[13] Mains frequency
[14] DataMatrix-Code
11
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Identification

Approval plate in explosion-proof version
Figure 7: Approval plates in explosion-proof version (examples)
[1] Ex symbol, CE mark, number of test authority
[2] Ex certificate (number)
Classification:
[3] Electrical gas explosion protection
[4] Electrical dust explosion protection
[5] Non-electrical explosion protection
[6] Threads for line bushings at electrical connection
[7] Not used
Descriptions referring to name plate indications
Type designation Figure 8:Type designation (example)
1. Type and size of actuator
2. Flange size
Type and size
These instructions apply to the following devices types and sizes:
●Type SAEx: Multi-turn actuators for open-close duty
Sizes: 25.1, 30.1, 35.1, 40.1
●Type SAREx = Multi-turn actuators for modulating duty
Sizes: 25.1, 30.1
●Type ACExC = AUMATIC actuator controls
Size: 01.2
Protection types
Table 1:
Description of the protection types for multi-turn actuators
Ex d= flameproof enclosureMotor compartment
Ex e= increased safetySwitch compartment
Ex e= increased safety (motor connection compartment and K/KR elec-
trical connection)
Terminal compartment
c = constructional safetyGear housing
Ex i= intrinsic safety (RWG 5020.2Ex)Position transmitter
12
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Identification ACExC 01.2

Table 2:
Description of the protection types for actuator controls
Ex d= flameproof enclosureActuator controls housing
Ex e= increased safety (with KP/KPH/KES electrical connection)
Ex d= flameproof enclosure (with KES-d electrical connection)
Terminal compartment
Ex e= increased safety (outer housing)
Ex d= flameproof enclosure (inner housing)
Control box
Ex e= increased safetyTerminal compartment of con-
trol box
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support > myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagramsandtechnical data (both inGerman and English),inspectioncertificate
and the operation instructions when entering the order number.
Actuator serial number Table 3:
Description of serial number (example of 0519MD12345)
MD123451905
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201919
Internal number for unambiguous product identificationMD12345
Actuator terminal plan Position 9 following TPA: Position transmitter version
0= Without position transmitter
A, B, J, K, L, N, R,T = Potentiometer
C, D, E, G, H, M, P, S, U = Electronic position transmitter
AUMA power class for
switchgear The switchgear used in the actuator controls (reversing contactors/thyristors) are
classified according to AUMA power classes (e.g.A1, B1, ....).The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for.The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate.For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to any power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Control Table 4:
Control examples (indications on actuator controls name plate)
DescriptionInput signal
Control voltage 24/48/60V DC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
24/48/60 V DC
Control voltage 100 –125V DC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
100 –125 V DC
Control voltage 100 –120V AC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
100 –120 V AC
Input current for setpoint control via analogue input0/4 –20 mA
Data Matrix code Whenregisteredasauthoriseduser, youmayuseourAUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
13
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Identification

Figure 9: Link to AUMA Assistant App:
For further Service & Support, software/apps/...refer to www.auma.com.
14
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Identification ACExC 01.2

3. Transport and storage
3.1. Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Death or serious injury.
→Do NOT stand below hovering load.
→Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→Actuatorsmountedto gearboxes:Attach ropes orhooksforthepurpose oflifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
→Respect total weight of combination (actuator, actuator controls, gearbox, valve)
→Secure load against falling down, sliding or tilting.
→Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
Figure 10: Example: Lifting the actuator
Table 5:
Weight for ACExC 01.2 actuator controls
Weight approx.[kg]with electrical connection type:
14AUMA Ex plug/socket connector with screw-type terminals (KT)1)
12AUMA Ex plug/socket connector with screw-type terminals (KP)
14AUMAExplug/socket connector with terminalblocks (KES), increased
safety Ex e
16.5AUMAExplug/socket connector with terminalblocks (KES), increased
safety Ex d
Standard1)
15
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Transport and storage

Table 6:
Weights of multi-turn actuators SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
with 3-phase AC motors
Weight2)
Motor type1)
Type designation
Actuator approx. [kg]
155ADX... 90-...SAEx 25.1/
SAREx 25.1 165ADX... 132-...
195ADX... 112-...SAEx 30.1/
SAREx 30.1 265ADX... 160-...
415ADX... 132-...SAEx 35.1
430ADX... 160-...
515ADX... 160-...SAEx 40.1
Refer to motor name plate1) Indicated weight includes AUMA NORM multi-turn actuator with 3-phase AC motor, electrical con-
nection in standard version, output drive type B1 and handwheel.For other output drive types, heed
additional weights.
2)
Table 7:
Weights for output drive type
[kg]Flange sizeType designation
42F25A 25.2
69F30A 30.2
126F35A 35.2
202F40A 40.2
Table 8:
Weights for output drive type
[kg]Flange sizeType designation
61F25AF 25.2
103F30AF 30.2
180F35AF 35.2
320F40AF 40.2
3.2. Storage
Danger of corrosion due to inappropriate storage!
→Store in a well-ventilated, dry room.
→Protect against floor dampness by storage on a shelf or on a wooden pallet.
→Cover to protect against dust and dirt.
→Apply suitable corrosion protection agent to uncoated surfaces.
Risk of damage due to excessively low temperatures!
→Actuator controls may only be stored permanently down to –30 °C.
→On request, actuators controls may be transported in specific cases and for
short duration at temperatures down to –60 °C.
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx.6 months:
Check for corrosion.If first signs of corrosion show, apply new corrosion protec-
tion.
16
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Transport and storage ACExC 01.2

4. Assembly
4.1. Mounting position
The product described in this document can be operated without restriction in any
mounting position.
4.2. Handwheel fitting
Information Fortransport reason,handwheelswith a diameterof400 mmandlargerare supplied
separately within the scope of delivery.
Damage at the change-over mechanism due to incorrect assembly!
→Only pivot change-over lever manually.
→Do NOT use extensions as lever for operation.
→First engage manual operation correctly, then mount handwheel.
1. Manually lift the red change-over lever while slightly turning the shaft back and
forth until manual operation engages.
➥Manual operation is properly engaged if the change-over lever can be shifted
by approx. 85°.
Figure 11:
2. Push handwheel over the red change-over lever then onto the shaft.
Figure 12:
3. Release change-over lever (should snap back into initial position by spring ac-
tion, if necessary, push it back manually).
17
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Assembly

4. Secure handwheel using the retaining ring supplied.
Figure 13:
4.3. Multi-turn actuator: mount to valve/gearbox
Corrosion due to damage to paint finish and condensation!
→Touch up damage to paint finish after work on the device.
→After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
4.3.1. Design of output drive type A
Figure 14: Output drive type A
[1] Output mounting flange
[2] Stem nut with dog coupling
[3] Valve stem
Output mounting flange [1] with axial bearing stem nut [2] form one unit.Torque is
transmitted to valve stem [3] via stem nut [2].
To adapt the actuators to available output drive types A with flanges F10 and F14
(year of manufacture 2009 and earlier), an adapter is required.The adapter can be
ordered from AUMA.
4.3.1.1. Stem nut for output drive type A: finish machining
This working step is only required if stem nut is supplied unbored or with pilot bore.
Information For exact product version, please refer to the order-related technical data sheet or
the AUMA Assistant App.
18
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Assembly ACExC 01.2

Figure 15: Output drive type A
[1] Stem nut
[2] Axial needle roller bearing
[2.1] Axial bearing washer
[2.2] Axial needle roller and cage assembly
[3] Spigot ring
Procedure 1. Remove spigot ring [3] from output drive.
2. Remove stem nut [1] together with axial needle roller bearings [2].
3. Remove axial bearing washers [2.1] and axial needle roller and cage assemblies
[2.2] from stem nut [1].
Information: For output drive types A from size 35.2 and larger: Record the
order of axial bearing washers [2.1].
4. Drill and bore stem nut [1] and cut thread.
5. Clean the machined stem nut [1].
6. Apply sufficient Lithium soap EP multi-purpose grease to axial needle roller and
cage assemblies [2.2] and axial bearing washers [2.1], ensuring that all hollow
spaces are filled with grease.
7. Place greased axial needle roller and cage assemblies [2.2] and axial bearing
washers [2.1] onto stem nut [1].
Information: For output drive types A from size 35.2: Observe correct order of
axial bearing washers [2.1].
8. Re-insert stem nut [1] with axial needle roller bearings [2] into output drive.
9. Screw in spigot ring [3] until it is firm against the shoulder.
19
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
ACExC 01.2 Assembly

4.3.1.2. Multi-turn actuator with output drive type A: mount
Figure 16: Assembly of output drive type A
[1] Valve stem
[2] Output drive type A
[3] Screws to actuator
[4] Valve flange
[5] Screws to output drive
Procedure 1. If output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2. Apply a small quantity of grease to the valve stem [1].
3. Place output drive type A on valve stem and turn until it is flush on the valve
flange.
4. Turn output drive type A until alignment of the fixing holes.
5. Fasten screws [5] between valve and output drive type A without completely
tightening them.
6. Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
➥The flanges are flush with each other if properly engaged.
7. Adjust multi-turn actuator until alignment of the fixing holes.
8. Fasten multi-turn actuator with screws [3].
9. Fasten screws [3] crosswise with a torque according to table.
Table 9:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class
A2-808.8
200214M16
392431M20
1,4221,489M30
2,4812,594M36
10. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive type A are firmly placed together.
11. Tighten screws [5] between valve and output drive type A crosswise applying
a torque according to table.
20
SAEx 25.1 –SAEx 40.1 / SAREx 25.1 –SAREx 30.1
Assembly ACExC 01.2
Other manuals for SAEx 25.1
3
This manual suits for next models
13
Table of contents
Other AUMA Controllers manuals

AUMA
AUMA SAEx 25.1 User manual

AUMA
AUMA LE 12.1 User manual

AUMA
AUMA SGM 04.1 User manual

AUMA
AUMA GST 10.1 Administrator Guide

AUMA
AUMA PROFOX PF-M100X User manual

AUMA
AUMA SQ 05.2 User manual

AUMA
AUMA PROFOX PF-Q80 User manual

AUMA
AUMA SA 25.1 User manual

AUMA
AUMA SAEx 07.2-UW User manual

AUMA
AUMA SAEx 25.1 User manual

AUMA
AUMA SG 03.3 User manual

AUMA
AUMA SQVEx 05.2 User manual

AUMA
AUMA SAE 07.2 Series Training manual

AUMA
AUMA SAVEx 07.2 User manual

AUMA
AUMA SA 25.1 User manual

AUMA
AUMA SAN 07.2 User manual

AUMA
AUMA SAEx 07.2 User manual

AUMA
AUMA SGM 04.1 User manual

AUMA
AUMA TIGRON TR-M30X User manual

AUMA
AUMA AUMATIC ACExC User manual