Aurora T8 User manual

Document Version - IS_T8LED_V2
T8 LED TUBES
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION
LEAVE A COPY FOR THE USER / MAINTENANCE ENGINEER FOR FUTURE REFERENCE
IMPORTANT INSTALLATION INFORMATION
WARNING
RISK OF ELECTRIC SHOCK
Disconnect power before performing installation or maintenance
T8 LED tubes operate at 100-277V~ 50/60Hz.
NB: T8 LED tubes cannot be dimmed and should not be connected to
existing dimming switch/equipment.
Verify that supply voltage is correct by comparing it with the luminaire
label information.
When modifying an existing T8 fluorescent luminaire to accept T8
LED tubes it is the installer’s responsibility to ensure that all electrical
connections are in accordance with the latest edition of the National
Electric Code (NEC) and applicable local code requirements and ensure
that the luminaire is electrically safe.
If the supply wire is damaged. It must be replaced by the manufacturer
or its service agent or a similar qualified person in order to avoid a
hazard.
All wiring connections should be capped with UL approved wire
connections.
Caution-Risk of Electric Shock- The modified luminaire will no longer
operate with the original lamp and electronic ballast.
To reduce the risk of fire or electrical shock, do not expose this
apparatus to moisture or wet locations.
To reduce the risk of electrical shock, do not remove cover and caps,
fitting must be grounded.
If not qualified, do not attempt installation. Contact a qualified
electrician.
Use in dry & damp locations only.
WARNING
CAUTION
Suitable for mounting on normally flammable surfaces.
Do not dispose of electrical appliances as unsorted municipal waste,
use separate collection facilities.
If electrical appliances are disposed of in landfill or dumps, hazardous
substances can be damaging to health and well-being.
Contact your local government for information regarding the collection
system available.
This device is not intended for use with emergency exit fixtures or
emergency exit lights.
No user-serviceable parts inside. Refer servicing to qualified/licenced
service personnel.
Do not use when enclosure is broken.
To prevent wiring damage or abrasion do not expose wiring to edges of
sheet metal or other sharp objects.
T8 LED tubes can operate with single magnetic ballast, however for
optimum efficiency and performance; Aurora recommends that the
ballast is removed from the circuit.
T8 LED tubes must not be used with electronic ballasts.
To reduce the risk of fire or electrical shock, do not use this retrofit kit
in luminaires employing shunted bi-pin lampholders.
Note: Shunted lamp holders are found only in fluorescent luminaires
with Instant-Start ballasts. Instant-start ballasts can be identified by the
words “Instant Start” or “I.S.” marked on the ballast.
Do not make or alter any open holes in an enclosure of wiring or
electrical components during the kit installation.
Caution: do not stare directly into the luminaire in operation. May be
harmful to eyes
WARNING
RISK OF BURNS
Do not exceed maximum wattage on luminaire label.
Follow all manufacturer’s warnings and recommendations for the
driver type, mounting position, methods, replacements and recycling.
WARNING
RISK OF FIRE
Keep any combustable and other materials that can burn away from
the luminaires.
Incorrect installation may result in electrical shock or a risk of a fire
Only electrically licenced personnel should attempt to replace this LED
lamp retrofit kit.
Model Numbers
2FT: AR-T8610CL/35, AR-T8610FR/35, AR-T8610CL/40 and AR-T8610FR/40
4FT: AR-T8618CL/35, AR-T8618FR/35, AR-T8618CL/40 and AR-T8618FR-40

RETROFIT LUMINAIRE WITH ONE LAMP
RETROFIT LUMINAIRE WITH TWO LAMPS AND ONE BALLAST
IMPORANT INFORMATION
Aurora LED T8 tubes has a dedicated internal driver and are suitable to replace T8 fluorescent lamps in fixtures containing standard non-shunted rapid start G13
(medium bi-pin) sockets
NOTE: T8 LED tubes cannot be dimmed and should not be connected to existing dimming switch/equipment.
T8 LED tubes can operate with a single magnetic ballast, however for optimum efficiency and performance; Aurora recommends that the ballast is removed from the
circuit.
T8 LED tubes must not be used with electronic ballasts.
IMPORTANT an existing T8 luminaire was designed to be used with standard fluorescent tubes and either electronic or magnetic ballasts. To retrofit LED tubes,
the luminaire must be modified, i.e. components removed and wiring altered as per the below instructions. Any modifications to a luminaire will nullify the original
manufacturer’s certification and declaration of conformity. The person or company modifying the luminaire will take full responsibility for safety, conducted and radiated
emissions in accordance with FCC Pt.15, environmental features, product markings and any legal issues resulting from the modification.
Existing markings or labels must be removed and new labeling must be added to the luminaire.
When installing or replacing Aurora T8 LED tubes the free end cannot be ‘LIVE’ and will not cause an electrical shock hazard
EMERGENCY LUMINAIRES
Existing emergency pack will not be compatible with T8 LED tubes and may either cause damage to the tubes or will not operate correctly. Aurora will not guarantee
to give the specified levels or emergency duration time. Existing luminaires used for emergency lighting will require the addition of an emergency pack designed to be
used with T8 LED tubes.
LED TUBE REPLACEMENT
Disconnect power and check that the luminaire is suitable for use with T8 LED tubes. If a fluorescent lamp is fitted then the luminaire will require modification.
Remove the old T8 LED tube and replace with a new one of the same specification.
WIRING METHOD WITH MAGNETIC BALLAST SINGLE LAMP
1. Turn off power
2. Remove diffuser (if applicable) and fluorescent lamp.
3. Open\Remove Wiring Compartment Cover
4. Remove any existing labeling and apply new labeling and ensure that no reference to fluorescent lamps remains.
5. Close up wiring compartment.
6. Install LED tube with the side with “AC input” label into the holder with the Line and Neutral.
(NB! the tube will not be damaged if installed in reverse)
7. Switch on power.
WIRING METHOD BYPASSING THE BALLAST (ELECTRONIC OR MAGNETIC)
1. Turn off power
2. Remove diffuser (if applicable) and fluorescent lamp.
3. Open\Remove Wiring Compartment Cover.
4. Cut off all wires connected to ballast (s).
5. Connect one wire from the socket to branch circuit L (Live wire) & other wire from socket to the branch Circuit N (Neutral wire) Be sure they are non-shunted rapid
start socket(s)
6. Reinstate any ground connections to the luminaire
7. Remove any existing labeling and apply new labeling ensure that no reference to fluorescent lamps remains.
8. Close up wiring compartment.
9. Install LED tube with the side with “AC input” label into the holder with the Line and Neutral. (NB! the tube will not be damaged if installed in reverse)
10. Switch on power.
11. Repeat steps 4 to 7 for each additional lamp\ballast based on illustration below.
Electronic
Ballast
Fluorescent Lamp
AC
Mains
Electronic
Ballast
AC
Mains LED
Electronic
Ballast
Fluorescent Lamp
Fluorescent Lamp
AC
Mains
Electronic
Ballast
AC
Mains
LED
LED

RETROFIT LUMINAIRE WITH THREE LAMPS / FOUR LAMPS AND ONE BALLAST
Fig.1 Fig. 2 Fig. 3
ROTATABLE END CAPS - INSTALATION
Before instalation, press down the locking tab and rotate the end cap to the desired angle, repeat the process, opposite end of the tube. (See Fig.1 & 2)
Release lock, this will automatically lock the selected angle and the lamp can now be installed in the luminaire. (See Fig.3)
WARRANTY
This product has a warranty of period of 3 years from the date of purchase. The warranty is invalid in the case of improper use, installation, tampering, and removal of the
Q.C. date label, installation in an improper working environment or installation not according to the current edition of the National Electric Code. Should this product fail during
the warranty period it will be replaced free of charge, subject to correct installation and return of the faulty unit. Aurora does not accept responsibility for any installation costs
associated with the replacement of this product. Aurora reserves the right to alter specifications without prior notice.
Electronic
Ballast
Fluorescent Lamp
Fluorescent Lamp
Fluorescent Lamp
Fluorescent Lamp
AC
Mains
Electronic
Ballast
AC
Mains
LED
LED
LED
Fluorescent Lamp
Fluorescent Lamp
Fluorescent Lamp
Fluorescent Lamp
Electronic
Ballast
AC
Mains
Electronic
Ballast
AC
Mains
LED
LED
LED
LED
Table of contents
Other Aurora Lighting Equipment manuals

Aurora
Aurora GU10 User manual

Aurora
Aurora AU-ST106A Series User manual

Aurora
Aurora AU-ST100IP User manual

Aurora
Aurora AU-ST324RGB User manual

Aurora
Aurora AU-A1ZBKWC Instruction manual

Aurora
Aurora AU-LED0635CC User manual

Aurora
Aurora AU-A1BTSCD User manual

Aurora
Aurora AOne Technical manual

Aurora
Aurora AU-ST901 User manual

Aurora
Aurora AU-DMX1500 User manual