
Sensor and power supply in one case for onwall-, ceiling- and
flushmounting
Power supply: 230 V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class:
FC IP20 / II
Settings: locally and by remote control
Light values remote control:
50 - 1500 Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range of coverage Ø H 2,50 m / T = 18°C:
seated 6.
40m
/ tangential 24 m /
radial 8 m
Recommended height for mounting:
2 - 3 m
Light measurement:
Mixed light, daylight + artificial light
Lux values potentiometers:
10 - 2000 Lux
• Channel 1 for light-connection
Type of contact:
NOC/with pretravel tungsten
contact
Contact load:
2300 W cos ϕ=1 /
1150 VA cos ϕ= 0.5, µ-Contact
DIM-Outputs:
1 x (1-10V)
Max. no. of series-connected electronic ballasts: max. 50 electronic
ballasts by one single supply with max. 100 m cable run and a
conductor cross-section of 0.75 mm²
Time-settings:
1 - 30min. / Test
•
Channel 2 for control devices (only reacts on motion)
Contact load
:
230 V~, 16 A cosϕ=1, µ-Contact
Time-settings
:
5 min. - 120 min. with time delay of
5 min. for follow-up time > 15 min./
Alarm impulse
Dimensions H x Ø [mm]
103x98
Visible portion when built into ceiling: 38 x 98 mm
Technical data PD4-Slave
Power supply: 230 V~ ±10 %
Impulse output: Optocoupler max. 2 W
Impulse duration: 2 sec. or 9sec.
Dimensions: see above
Declaration of Conformity: The product complies with the low
voltage recommendation 2006/95/EC and the EMV recommenda-
tion 2004/108/EC.
19. Technical data PD4-M-DIM-HVAC 16 A
14. Wiring diagrams
15. Connections
Type SM FC FM
PD4-M-DIM-HVAC 16 A
(Master) –92547 –
PD4-S (Slave) 92142 92254 92163
LUXOMAT®Remote control
IR-PD-DIM-HKL (incl. wall bracket) 92114
Accessory:
BSK Ball basket guard 92199
Occupancy detectors – Covering IP23 92206
17. Article / Part nr. / Accessory
MAN 7508 – PD1245-DIM-2C-V12 – 281112– 4
In case the sensing area of the LUXOMAT®PD4-M-DIM-HVAC
is too large or areas are being covered that should not
be monitorerd, the range can be reduced or limited
through use of the enclosed masking clips
18. Exclude sources of interference
13. Range
11. Manual Dimming – Preset /User
(for IR-PD-DIM-HKL functions see page 1)
You can dim manually by pressing the push button for
a long time (> 2 sec). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET – the luminance set point is set during start-up
operation by the installer and remains unchanged.
The luminance set-point congured through manual
dimming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set articial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER – can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user (Conformation
through relay clicking!) The constant light regulation
remains activated!
The system switches over when the “Doublelock” push-
button is open (see remote control functions, page 1).
Each time a push-button is pressed, the current operating
mode is indicated:
Red lights for 3 sec. = Preset
Green lights for 3sec. = User
10. Fully / Semi automatic mode
(for IR-PD-DIM-HKL functions see page 1)
The system switches over when the “Light” push-button is
open (see remote control functions, page 1).
Each time a push-button is pressed, the current operating
mode is indicated by the red LED:
Red lights for 3 sec. = Fully automatic mode
Green lights for 3 sec. = Semi-automatic mode
Fully automatic operation
In this operating mode, the lighting switches automatically on
and off for increased comfort, depending on presence and
brightness.
Semi automatic operation
(Semi automatic can only be activated via the remote control!)
In this operating condition, in order to gain increasedsav-
ings, the lighting is energized only after being manually
switched on. Switch-off takes place automatically. The
semi automatic mode basically behaves like the fully
automatic. However, the difference is that switching-on
must always be carried out manually!
As many (closer-contact) buttons as desired can be wired in
parallel on the “S” button input (ON/OFF Dimm).
12. Manual Switching
The light will remain switched on or off, as movements are
detected in the area. After the last detected movement the
light will be off for the duration of the set-up time. The device
will then return independently to the Operation mode (Full or
Semi automatic).
20. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT®
PD4-M-DIM-HVAC (red and green LED‘s)
Red LED indicating self-checking mode (over a period of 60
seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from
the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt is
made to input twilight-value are too bright or too dark
Green LED as an acknowledgement of receipt for commands from
the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
White LED
Lights permanently
Semi-automatic active (shines)
Illuminates 4 seconds, then 1sec. off
Semi-automatic and active corridor
Illuminates 1 seconds, then 4sec. off
Only active corridor
e
1
2
3
Walking across
Walking towards
Seated
24 m
8 m
6,40 m
24 m
360°
2.50 m
2
3
1
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED
LIGHTS A 100h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES )
FUNCTION TAKES PLACE .
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN
DOES NOT TAKE PLACE .
Standard mode with master-DIM-HVAC-occupancy detectors
M1 = HVAC-Function
optional
T1 = NO button for Light-Channel
T2 = NO button for HVAC-Channel
Slave to the extension of coverage
PD4-M-DIM-HVAC-FC
L
N
R
Slave
L' NO NO
LR
T2
N
L
+
–
E1
1-10 V
EB
M1
16. Manual switching HVAC-Channel
230VAC for 0.1 - 1 second on the slave port R
Lay on the slave port R for 0.1 - 1 second to 230VAC,is this
like a key signal for the HVAC channel interpreted.
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
–
+
Master Slave
L
N
E1 1-10 V EB
N
L
+
-
RSL L´1N -+NLR
T1
C1 C1
NO
HVAC
NO
HVAC
T2
N S
T1
PD4-M-DIM-HKL_16A_4lang+DK_291112.indd 2 12/5/2012 12:14:39 PM