13.
Technical data
PD9-M-DALI/DSI(-GH)
11. Wiring diagram
12. PD9-M-DALI/DSI(-GH) - Connections
MAN 5976 – 071209–5
14. LED-functional indicators, fault-finding
The functional indicators in the case of the
LUXOMAT®
PD9-MASTER-DALI/DSI (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when
an attempt is made to input twilight-value are too
bright or too dark
Green LED as an acknowledgement of receipt for
commands from the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
8. Manual Dimming - Preset /User
(for IR-PD-DALI functions see page 1)
You can dim manually by pressing the pushbutton for
a long time (> 2 sec). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET –the luminance set point is set during start-up
operation by the installer and remains unchanged.
The luminance set- point congured through manual
dimming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set articial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER - can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user (Conformation
through relay clicking!)
The constant light regulation remains activated!
7. Fully / Semi automatic mode
(for IR-PD-DALI functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on.
Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF Dimm).
9. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the congured
follow up time.
L
N
Terminal connection for MASTER-/SLAVE-operation
N – N L – L R – R
MASTER SLAVE
230V
~
DA DA
DALI-EB 1
230V
~
DA DA
DALI-EB 2-12
R S N L DALI
T5 und T8
uorescent
lamps
Type FC
PD9-M-DALI/DSI – Master 92920
PD9-M-DALI/DSI-GH – Master 92938
PD9-S – Slave 92905
PD9-S-GH – Slave
92928
LUXOMAT®Remote control:
IR-PD-DALI (incl. wall bracket) 92094
Accessory:
Wall bracket for remote control as replacement
92100
10. Article / Part-Nr. / Accessory
Circuit diagram
L
N
S1S2
up to 12 EBs
EB 1
EB 2
EB 12
For T5 and
T8 uorescent
lamps
SLAVE
20%
LUXOMAT®IR-PD-DALI
RESET TEST
30
min
15
min
10
min
5
min
1
min
OFF
60
min
30
min
10
min
1
min
ON
-
-
-
max
++
+
PD9-M-DALI/DSI
PD9-M-DALI/DSI-FC
= up to 12 electronic ballasts (EB) are
connectable.
Power supply: 230 V~ +6 %/-10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class:
IP20 / II
Settings:
by remote control
Light values - IR-PD-DALI:
50 - 1500Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range of coverage Ø H 2.50m / T = 18°C:
PD9-M-DALI/DSI
seated
2.50 m
/
tangential
10 m /
radial
6 m
PD9-M-DALI/DSI-GH max. Ø
5.40 m
Recommended height for mounting:
PD9-M-DALI/DSI
2 - 3 m
PD9-M-DALI/DSI-GH 5 - 10 m
Light measurement:
mixed light, daylight and artificial light
• DALI-Output
digital BUS control wire, 2-core, no polarity
(broadcast only)
Max. no. of series-connected electronic ballasts:
up to 12
Time-settings:
1 - 30min. / Test
Dimensions H x Ø [mm]:
PD9-M-DALI/DSI
Ø 45 x H 28 mm
PD9-M-DALI/DSI-GH
Ø 45 x H 40 mm
Power supply L 165 x W 24 x H 24 mm
Declaration of Conformity:
The product complies with