Banner SSA-EB1PL 0D Series User manual

SSA-EB1PLx-0Dx Series Lighted
Emergency Stop Button with ISD
Instruction Manual
Original Instructions
215157 Rev. A
3 August 2020
©Banner Engineering Corp. All rights reserved
215157

Contents
1 Product Overview ........................................................................................................................................................... 3
1.1 Models ............................................................................................................................................................................................. 3
1.2 Important... Read this before proceeding! ......................................................................................................................................3
1.3 Emergency Stop Considerations .................................................................................................................................................... 4
1.4 Overview ......................................................................................................................................................................................... 4
2 Installation Instructions ...................................................................................................................................................5
2.1 Mechanical Installation ................................................................................................................................................................... 5
2.2 Installation Requirements ............................................................................................................................................................... 5
2.3 Output Signal Switching Devices (OSSDs) and External Device Monitoring (EDM) .......................................................................6
2.3.1 Fault-Tolerant Output Feature .................................................................................................................................................7
2.4 Wiring for a Single E-Stop .............................................................................................................................................................. 7
2.4.1 Wire the Device in Series .........................................................................................................................................................7
2.4.2 Wire the Device in Series Using the Quick Disconnect (QD) ...................................................................................................8
2.5 Checkout .......................................................................................................................................................................................10
2.6 Resetting the Inputs ......................................................................................................................................................................10
2.7 In-Series Diagnostic (ISD) Information ..........................................................................................................................................11
2.8 Installing the Silicone Cover ......................................................................................................................................................... 11
3 Specifications ................................................................................................................................................................ 12
3.1 Dimensions .................................................................................................................................................................................... 12
4 Accessories ................................................................................................................................................................... 14
4.1 Cordsets ........................................................................................................................................................................................ 14
4.2 Brackets ........................................................................................................................................................................................16
4.3 Adapters and Other Accessories ...................................................................................................................................................16
4.4 Safety Controllers .......................................................................................................................................................................... 16
4.5 Universal (Input) Safety Modules .................................................................................................................................................. 17
5 Product Support and Maintenance .............................................................................................................................. 18
5.1 Maintenance and Service ............................................................................................................................................................. 18
5.2 Status Indicators ............................................................................................................................................................................18
5.3 EU Declaration of Conformity (DoC) .............................................................................................................................................. 18
5.4 Information Available Using ISD ................................................................................................................................................... 18
5.5 Contact Us .....................................................................................................................................................................................20
5.6 Banner Engineering Corp. Limited Warranty ................................................................................................................................ 20
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD

1 Product Overview
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
Figure 1. 30 mm mount model
Figure 2. Flush mount model
• Rugged design; easy installation with no assembly or individual wiring
required
• Push-to-stop, twist-to-release, or pull-to-release operation per EN 60947-5-5
• Latching design complies with ISO 13850; direct (positive) opening operation
per EN 60947-5-1
• Compliant with ANSI B11.19, ANSI NFPA79, and IEC/EN 60204-1
Emergency Stop requirements
• "Safe Break Action" ensures OSSDs turn off if the contact block is separated
from the actuator
• 8-pin M12/Euro-style quick disconnect
• Armed state indication options include YELLOW, GREEN or no indication
(OFF), depending on model
• All models illuminate with flashing red when actuated (button pushed)
• "Emergency Stop" legend included
• Two, solid-state, PNP current sourcing OSSD outputs
• In-Series Diagnostic (ISD) for button health and status information when used
with a compatible Banner Safety Controller
• All models have a 40 mm "mushroom style" push button
1.1 Models
Model Mounting Style Reset Function Armed Illumination Color
SSA-EB1PLYR-0DECQ8
30 mm
No
Yellow
SSA-EB1PLXR-0DECQ8 None
SSA-EB1PLGR-0DECQ8 Green
SSA-EB1PLYR-0DECQ8R
Yes
Yellow
SSA-EB1PLXR-0DECQ8R None
SSA-EB1PLGR-0DECQ8R Green
SSA-EB1PLYR-0DED1Q8
Flush
No
Yellow
SSA-EB1PLXR-0DED1Q8 None
SSA-EB1PLGR-0DED1Q8 Green
SSA-EB1PLYR-0DED1Q8R
Yes
Yellow
SSA-EB1PLXR-0DED1Q8R None
SSA-EB1PLGR-0DED1Q8R Green
1.2 Important... Read this before proceeding!
The user is responsible for satisfying all local, state, and national laws, rules, codes, and regulations relating to the use of
this product and its application. Banner Engineering Corp. has made every effort to provide complete application,
installation, operation, and maintenance instructions. Please contact a Banner Applications Engineer with any questions
regarding this product.
The user is responsible for making sure that all machine operators, maintenance personnel, electricians, and supervisors are
thoroughly familiar with and understand all instructions regarding the installation, maintenance, and use of this product, and
with the machinery it controls. The user and any personnel involved with the installation and use of this product must be
thoroughly familiar with all applicable standards, some of which are listed within the specifications. Banner Engineering
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 3

Corp. makes no claim regarding a specific recommendation of any organization, the accuracy or effectiveness of any
information provided, or the appropriateness of the provided information for a specific application.
WARNING:
•Not a safeguarding device
• Failure to follow these instructions could result in serious injury or death.
• This device is not considered a safeguarding device because it requires an overt action by an
individual to stop machine motion or hazards. A safeguarding device limits or eliminates an
individual's exposure to a hazard without action by the individual or others. This device cannot be
substituted for required safeguarding. Refer to the applicable standards to determine those
requirements.
1.3 Emergency Stop Considerations
ANSI NFPA 79, ANSI B11.19, IEC/EN 60204-1, and ISO 13850 specify emergency stop requirements, including the
following:
• Emergency-stop push buttons shall be located at each operator control station and at other operating stations
where emergency shutdown is required.
• Stop and emergency-stop push buttons shall be continuously operable and readily accessible from all control and
operating stations where located. Do not mute or bypass E-stop buttons.
• Actuators of emergency-stop devices shall be colored red. The background immediately around the device actuator
shall be colored yellow (where possible). The actuator of a push-button-operated device shall be of the palm or
mushroom-head type.
• The emergency-stop actuator shall be a self-latching type.
WARNING:
•Do not mute or bypass any emergency stop device
• Muting or bypassing the safety outputs renders the emergency stop function ineffective.
• ANSI B11.19, ANSI NFPA79 and IEC/EN 60204-1 require that the emergency stop function
remain active at all times.
WARNING:
•Connect two or more devices to the same safety module (controller) in series
• Connecting devices in parallel defeats the switch contact monitoring ability of the module and
creates an unsafe condition that could result in serious injury or death.
• Failure to test each device individually in this manner could result in undetected faults and create
an unsafe condition that could result in serious injury or death.
• Connect the contacts of the corresponding pole of each switch in series. Never connect the
contacts of multiple switches in parallel. Individually actuate (engage) each device, then release
(or re-arm) and reset the safety module. This allows the module to check each switch and its
wiring to detect faults. Perform this check during the prescribed checkouts.
1.4 Overview
The SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD is a mushroom-style electro-mechanical emergency
stop push button. When the button is armed and the device input requirements are satisfied, the two, solid-state PNP
output signal switching devices (OSSDs) are on (conducting). When the button is pushed, the OSSDs are off (not
conducting). The OSSDs remain in this condition until the push button is manually re-armed by pulling or twisting clockwise
the red push button actuator.
The SSA-EB1PLx-0Dx..ECQ.. series has a 30 mm mounting base similar to Banner's OTB, VTB, and STB Optical Touch
Buttons for ease of mounting without requiring an additional enclosure. The SSA-EB1PLx-0Dx..ED1Q.. series has a flat
mounting base for ease of mounting without requiring an additional enclosure.
The illumination provides easy identification of a pushed/actuated button. An armed button will light a steady yellow or
green illumination or be OFF (depending on model). A pushed/actuated button is indicated by a red flashing illumination.
Internal or external faults are indicated by a double-flashing red illumination.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
4 www.bannerengineering.com - Tel: + 1 888 373 6767

2 Installation Instructions
2.1 Mechanical Installation
The SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD is supplied with all necessary mounting hardware.
Important: Install the emergency stop in a manner that discourages tampering or defeat. Mount
emergency stops to prevent bypassing at the terminal chamber or quick disconnect (QD) connection.
The hardware supplied with the 30 mm mount SSA-EB1PLx-0Dx..ECQ.. series includes a jam nut, lock washer, lock ring,
and seal washer. Use the lock ring to prevent rotation if a 5 mm keyway is provided in the 30 mm mounting hole. The
threaded base contains external M30 threads for the supplied jam nut, as well as internal ½-14 NPSM threads for an
alternate mounting option.
The hardware supplied with the flush mount SSA-EB1PLx-0Dx..ED1Q.. series includes four M5 screws and nuts.
M30 jam nut
Torque to 4.5 N-m
(40 in-lbf)
Lock Ring
To be used in place of lock
washer when mounted
through a keyed hole
Figure 3. Mounting the ..ECQ (30 mm) models
4X M5 hardware
Torque to 0.56 N-m
(5 in-lbf)
Figure 4. Mounting the ..ED1Q (flush mount) model
2.2 Installation Requirements
The device is intended for indoor use only and must not be affected by environmental conditions. Install the device so that
operation is not impeded, but protected against inadvertent operation (for example, accidental actuation by being bumped
or leaned against). Do not operate the switch using a tool. Do not expose the switch to excessive shocks and vibrations,
otherwise the switch may be deformed or damaged, causing malfunction or operation failure.
Electrical installation must be made by qualified personnel1and must comply with NEC (National Electrical Code), ANSI/
NFPA 79 or IEC/EN 60204-1, and all applicable local standards. It is not possible to give exact wiring instructions for a
device that interfaces to a multitude of machine control configurations. The following is general in nature; it is recommended
to perform a risk assessment to ensure appropriate application, interfacing/connection, and risk reduction (see ISO 12100
or ANSI B11.0).
1A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and
experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 5

WARNING:
•Risk of electric shock
• Use extreme caution to avoid electrical shock. Serious injury or death could result.
• Always disconnect power from the safety system (for example, device, module, interfacing, etc.),
guarded machine, and/or the machine being controlled before making any connections or
replacing any component. Lockout/tagout procedures might be required. Refer to OSHA
29CFR1910.147, ANSI Z244-1, or the applicable standard for controlling hazardous energy.
• Make no more connections to the device or system than are described in this manual. Electrical
installation and wiring must be made by a Qualified Person2and must comply with the applicable
electrical standards and wiring codes, such as the NEC (National Electrical Code), ANSI NFPA79,
or IEC 60204-1, and all applicable local standards and codes.
2.3 Output Signal Switching Devices (OSSDs) and External Device
Monitoring (EDM)
The SSA-EB1PLx-0Dx is able to detect faults on OSSD1 and OSSD2. These faults include short circuits to +24 V DC and 0
V, and between OSSD1 and OSSD2.
Both OSSD outputs must be connected to the machine control so that the machine's safety-related control system
interrupts the circuit or power to the machine primary control element(s) (MPCE), resulting in a non-hazardous condition.
Final switching devices (FSDs) typically accomplish this when the OSSDs go to an OFF state.
Refer to the output specifications and these warnings before making OSSD output connections and interfacing the SSA-
EB1PLx-0Dx to the machine.
WARNING:
•Interfacing both output signal switching devices (OSSD)
• Failure to follow these instructions could result in serious injury or death.
• Unless the same degree of safety is maintained, never wire an intermediate device(s) (PLC, PES,
PC) between the safety module outputs and the master stop control element it switches such
that a failure causes a loss of the safety stop command or the failure allows the safety function to
be suspended, overridden, or defeated.
• Connect both OSSD outputs to the machine control so that the machine’s safety-related control
system interrupts the circuit to the machine primary control element(s), resulting in a non-
hazardous condition.
WARNING:
•Interfacing OSSD Outputs to Machine Inputs
• Failure to properly interface the OSSD Outputs to the guarded machine could result in serious
injury or death.
• To ensure proper operation, the Banner device output parameters and machine input parameters
must be considered when interfacing the Banner device OSSD outputs to machine inputs. Design
the machine control circuitry so that the maximum load resistance value is not exceeded and the
maximum specified OSSD Off-state voltage does not result in an On condition.
External device monitoring (EDM) is a function used to monitor the state of the external, positively guided (mechanically
linked) machine control contacts (Final Switching Devives (FSD) and/or MPCEs). The SSA-EB1PLx-0Dx does not include the
EDM function. As a result, the SSA-EB1PLx-0Dx should be used with an external safety monitoring device that monitors the
status of the two SSA-EB1PLx-0Dx OSSDs and is capable of providing the EDM function.
Examples of appropriate external safety monitoring devices include the Banner SC10-2ro Safety Controller.
WARNING:
•The SSA-EB1PLx-0Dx does not have external device monitoring (EDM).
• If EDM is required for the application, it must be implemented in the external control.
2A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and
experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
6 www.bannerengineering.com - Tel: + 1 888 373 6767

2.3.1 Fault-Tolerant Output Feature
Faults that do not immediately compromise the safe operation of the SSA-EB1PLx-0Dx (for example safety output to
external potential, crosswire short safety output) result in a delayed switch-off of the safety outputs.
The safety outputs switch off when the error warning exceeds 20 minutes. In case of error warning, the E-stop will double-
flash red.
Use this fault-tolerant output feature to run down the machinery in a controlled manner. After fixing the fault, the error
message is confirmed by a voltage reset. The safe outputs enable and allow a restart.
Faults that directly affect the safe operation of the emergency stop device immediately cause a lockout condition and the
OSSDs turn off.
2.4 Wiring for a Single E-Stop
24
34
14
+24Vdc
+24Vdc
0Vdc
0Vdc
L2/-V
L1/+V
EDM
SC10
23
33
13
Safety Relay Outputs 43/44,
53/54 and 63/64 can be
wired similarly, but require a
separate EDM or AVM input
for monitoring.
MPCE1
MPCE2
Arc Suppressors
Machine
Control
Circuit
Feedback Loop (optional)
5 - Grey
1 - White
6 - Pink
2 - Brown
3 - Green
7 - Blue
8 - Red
4 - Yellow
+24 V dc
+
I1
I2
Q1
–0V dc
n.c.
n.c.
OSSD1
OSSD2
SSA-EB1PL.. with ISD
Q2 IN4
IN3
Figure 5. Single SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD with SC10-2ro.
The SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD can be connected in series or individually to a
compatible Banner XS26-2 or SC10-2ro Safety Controller. See the XS26-2/SC10 Safety Controller Instruction Manual for
additional details regarding input terminal combinations compatible with ISD.
2.4.1 Wire the Device in Series
To connect two or more SSA-EB1PLx-0Dx buttons in series, follow these steps.
1. Connect the safety outputs of the last emergency stop device to a safety monitoring unit.
2. Connect the safety inputs of the first emergency stop device of the series to + 24 V DC.
3. Connect the safety outputs of the first emergency stop device to the safety inputs of the second emergency stop
(and second to third, etc).
4. When all the emergency stop devices are armed, the last emergency stop device of the series connection will turn
on its safety outputs.
5. If you are using an optional In-Series Diagnostic (ISD) module (SI-RFA-DM1), integrate the diagnostic module
between the last emergency stop device and the safety monitoring module in the series connection.
The status information can be retrieved from the diagnostic device.
Important: Verify the SSA-EB1PLx-0Dx emergency stop device and the safety monitoring module are
powered from the same power supply or the commons of the separate supplies are the same.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 7

8
Rd
1
Wh
5
Gy
2
Bn
4
Ye
3
Gn
6
Pk
+ Q1Do Q2I1I2 –
24V 24V24V
n.c.
7
Bu
Safety
Controller
8
Rd
1
Wh
5
Gy
2
Bn
4
Ye
3
Gn
6
Pk
+ Q1Do Q2I1I2 –
SSA-EB1PL.. 1 SSA-EB1PL.. 2 SSA-EB1PL.. 3
n.c.
7
Bu
8
Rd
1
Wh
5
Gy
2
Bn
4
Ye
3
Gn
6
Pk
+ Q1Do Q2I1I2 –
n.c.
7
Bu
Figure 6. Series connection of multiple SSA-EB1PLx-0Dx.. without reset function wiring diagram.
Do
7
Bu
1
Wh
5
Gy
6
Pk
+Reset
I1I2
24V
8
Rd
2
Bn
4
Ye
3
Gn
Safety
Controller
Q1 Q2 –Do
7
Bu
1
Wh
5
Gy
6
Pk
+Reset
I1I2
24V
8
Rd
2
Bn
4
Ye
3
Gn
Q1 Q2 –Do
7
Bu
1
Wh
5
Gy
6
Pk
+Reset
I1I2
SSA-EB1PL.. Q8R 1 SSA-EB1PL.. Q8R 2 SSA-EB1PL.. Q8R 3
24V
8
Rd
2
Bn
4
Ye
3
Gn
Q1 Q2 –
Figure 7. Series connection of multiple SSA-EB1PLx-0Dx..Q8R with reset function wiring diagram.
After the emergency device is rearmed, the optional reset function requires a manual acknowledgement before the safety
output of the device is switched on (only that individual emergency stop device, not the entire chain).
2.4.2 Wire the Device in Series Using the Quick Disconnect (QD)
When connecting units in series, simplify the wiring using special t-adapters and low cost unshielded four-wire double-
ended cables.
A similar configuration is shown except the connections are all made using quick disconnects. The SSA-EB1PLx-0Dx E-
Stops and SI-RFD switches can be combined in a single chain.
1. Connect the female 4-pin M12/Euro-style cable to the male 4-pin M12/Euro-style of the series connection t-adapter
(SI-RFA-TS).
2. If a manual reset model emergency stop device is used, connect the female 8-pin M12/Euro-style of the Reset T-
Adapter (SI-RFA-TK) to the male 8-pin M12/Euro-style connector of the series connection t-adapter. Connect a
female 4-pin M12/Euro-Style cable to the male 4-pin M12/Euro-style QD of the t-adapter for connected a reset
switch.
3. Connect the SSA-EB1PLx-0Dx to the male 8-pin M12 connector of the t-adapter. Use DEE2R-8xxD extensions
cables as needed.
4. Connect the male 4-pin M12 end of a double-ended cable to the female 4-pin M12 of the t-adapter. Connect the
female 4-pin M12 end of the double ended cable to the next series connection t-adapter (SI-RFA-TS).
5. At the end of the line a terminating plug (SI-RFA-P) is required to properly truncate the system.
6. The wired end of the 4-pin M12 cable (from step 1) can be wired directly to a Safety Monitoring Module or can be
wired through an In-Series Diagnostic (ISD) module then to the Safety Monitoring device.
Verify that the SSA-EB1PLx-0Dx and the safety monitoring module are powered from the same power supply or the
commons of the separate supplies are the same. Ensure that the voltage level at SSA-EB1PLx-0Dx #1 (furthest from the
power supply) is above 19.5 V for the system to operate properly.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
8 www.bannerengineering.com - Tel: + 1 888 373 6767

SI-RFA-TS
4-pin male connection
SI-RFA-TK
SI-RFA-P Termination
MQDEC-4xxSS (3) and DEE2R-8xxD (1)
MQDC-4xx (2)
ONLY FOR E-Stop 4
Power Safety
Monitoring
Module
24Vdc 0Vdc
OSSDs
Bn Bu
Wh
Bk
Bn
Wh
Reset
12 3
4
Component Key
8-pin female connection
SI-RFA-TS
SI-RFA-P
SI-RFA-TS SI-RFA-TS SI-RFA-TS
DEE2R-8xxD
SI-RFA-TK
MQDEC-4xxSS MQDEC-4xxSS MQDEC-4xxSS
MQDC-4xx
MQDC-4xx
24Vdc
0Vdc
Figure 8. SSA-EB1PLx-0Dx E-Stops with ISD Series Connection
In a long series or series with many ISD devices, the voltage at all devices must stay above 19.5 V for proper operation.
An additional power supply may be required to maintain a minimum of 19.5 V at all devices. For examples of how to
properly connect a second power supply, refer to Figure 9 on p. 9 and Figure 10 on p. 9.
For guidance on maximum total cable length and maximum number of devices before an additional power supply may be
needed, refer to Figure 11 on p. 10. For using ISD information to monitor the individual device voltages, see In-Series
Diagnostic (ISD) Information on p. 11.
There are two options to connect an additional power supply.
1
8
SI-RFA-TSSI-RFA-TS SI-RFA-TS SI-RFA-TS SI-RFA-TS SI-RFA-TS
Power
#2
24Vdc 0Vdc
Bn Bu
Safety
Monitoring
Module
24Vdc 0Vdc
OSSDs
Bn Bu
Wh
Bk
24Vdc
0Vdc
Power
#1
SI-RFA-TK
SI-RFA-P
MQDEC-4xxSS
Figure 9. Option 1: Use a SI-RFA-TK Reset Connector in series with ISD Device. If available, set the power supplies for parallel output.
1 8
SI-RFA-TSSI-RFA-TS SI-RFA-TS SI-RFA-TS SI-RFA-TS SI-RFA-TS
Safety
Monitoring
Module
24Vdc 0Vdc
OSSDs
Bn Bu
Wh
Bk
24Vdc
0Vdc
Power
#1
Connect OSSD1 and
OSSD2 to +24 V dc
MQDEC-4xxSS
Power
#2
24Vdc
0Vdc
Bn
Bu
DEER2-8xxD
Figure 10. Option 2: Replace the terminator with a power supply. The OSSD1 and OSSD2 wires at power supply #2 must be connected to +24 V DC. If
available, set the power supplies for parallel output.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 9

0
0
20
40
60
80
100
120
140
160
4 8 12 16 20 24 28 32
Max. Total Series Cable (m)
Number of ISD Devices
Max. Total Series Cable (m)
Single Power Supply
SI-RF
E-Stops
Figure 11. Maximum total cable length for a single power supply
WARNING:
•Safety devices with OSSDs and without ISD, such as safety light curtains, are not compatible.
• Failure to follow these instructions could result in serious injury or death.
• Do not use safety devices with OSSDs and without ISD in a series connection of multiple ISD
devices.
2.5 Checkout
At machine set up, a
Designated Person
3should test each safety point for proper machine shutdown response. A
Designated Person
should check the safety point for proper operation, physical damage, button looseness, and excessive
environmental contamination. This should take place on a periodic schedule determined by the user, based on the severity
of the operating environment and the frequency of switch actuations.
Adjust, repair, or replace components as needed. If inspection reveals contamination on the switch, thoroughly clean the
switch and eliminate the cause of the contamination. Replace the switch and/or appropriate components when any parts or
assemblies are damaged, broken, deformed, or badly worn; or if the electrical/mechanical specifications (for the
environment and operating conditions) have been exceeded.
Always test the control system for proper functioning under machine control conditions after performing maintenance,
replacing the safety point, or replacing any component of the device.
2.6 Resetting the Inputs
The reset function forces a local confirmation that the safety outputs are switched on after resetting the individual
emergency stop button.
If an emergency stop button with a reset function is actuated and then armed/re-armed (pulled out), close and open the
external reset switch within 0.25 seconds (minimum) to 1 second (maximum) to turn the e-stop buttons outputs on
(assuming its inputs are satisfied).
3A
Designated Person
is identified in writing by the employer as being appropriately trained to perform a specified checkout procedure. A Qualified
Person possesses a recognized degree or certificate or has extensive knowledge, training, and experience to solve problems relating to the
emergency stop installation.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
10 www.bannerengineering.com - Tel: + 1 888 373 6767

The reset function only applies to the emergency stop button models with the reset functionality. This reset feature allows
for a local reset at a given emergency stop button but does not allow for an entire safety system reset.
If a chain of ISD devices are cascaded (see Wire the Device in Series on p. 7), the reset function only applies to the
individual emergency stop button (1, 2, or 3 but not the series). If emergency stop button 2 is actuated then armed/re-
armed, engaging the external reset switch of emergency stop buttons 1 or 3 will have no effect. Only engaging the external
reset switch of emergency stop button 2 switches the chain's outputs on.
CAUTION: When power is switched on and the emergency stop buttons are in the on (armed) position,
the safety outputs of the emergency stop buttons with the reset function will switch on without activating
the reset button.
WARNING:
• Use of Auto or Manual Restart
• Failure to follow these instructions could result in series injury or death.
• Applying power to the Banner device, returning the emergency stop to the armed position, or
resetting a manual restart condition MUST NOT initiate dangerous machine motion.
• Design the machine control circuitry so that one or more initiation devices must be engaged (in a
conscious act) and the Banner device must be in Run mode to start the machine.
2.7 In-Series Diagnostic (ISD) Information
The information transmitted via the In-Series Diagnostic (ISD) interface is not safety related. The diagnostic technology
allows a wide range of device information to be loaded into the machine control system.
To interpret this information, Banner diagnostic modules are available, including the SI-RF-DM1 Diagnostic Module and the
SC10-2roe Safety Controller. Refer to the instruction manuals for detailed information on the diagnostic devices. By means
of diagnostics, the following information can be transmitted, among others:
• Button Status (armed, off, faulted)
• Under-voltages in the series connection (chain)
• Attempts to remove buttons from the chain
• Wrong order of devices in the chain
At this time this information can be refined using the following interfaces:
• USB—Displays device information on the PC (requires using an SI-RF-DM1 or SC10-2roe Safety Controller)
• IO-Link—Bus independent data reading into the control system (requires using the SI-RF-DM1 and an IO-Link
master)
• Industrial Ethernet Protocols—Bus data reading into the control system (requires using the SC10-2roe Safety
Controller)
2.8 Installing the Silicone Cover
To properly install the FDA-grade silicone cover and achieve an IEC IP69 rating, follow these
instructions.
1. Turn the cover inside-out, except for the top portion the button fits into.
2. Place the cover on top of the emergency stop unit.
3. Roll the cover onto the e-stop unit.
4. Continue rolling the cover down, around the base of the e-stop unit, until the entire unit is
covered.
5. Mount the e-stop and cover assembly to a bracket wide enough to cover the base of the
assembly. The cover should be clamped firmly between the e-stop button and the
bracket.
Note: This cover is suitable for applications with pull-to-release resetting
methods.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 11

3 Specifications
Important: Connect the SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD only to a SELV
(Safety Extra-Low Voltage) for circuits without earth ground or a PELV (Protected Extra-Low Voltage) for
circuits with earth ground power supply.
Rated Supply Voltage (Ue)
24 V DC + 15%, -20% (PELV/SELV power supply)
The external voltage supply must be capable of buffering brief mains
interruptions of 20 ms, as specified in IEC/EN 60204-1.
Rated Isolation Voltage (Ui)
75 V DC
Rated Impulse Withstand Voltage (Uimp)
500 V
Rated Conditional Short-Circuit Current
100 A
No-load Current
100 mA typical at 24 V DC
120 mA maximum at 19.2 V DC
OSSD Outputs
Two, solid-state, current sourcing PNP outputs
Switching element function: PNP, NO
Voltage level: according to Type 3 EN 61131-2
Maximum operating current: 30 mA
Leakage current: ≤ 1 mA DC
On-state voltage: ≥ Ue – 3 V
Protection: Sustained short-circuit and overload protection; thermal /
digital (clocking)
Test pulse duration: 70 μs
Test pulse rate: 1 s
Reset Input (specific models)
High Signal: 10 to 30 V DC
Low Signal: 0 to 3 V DC
Power Up Delay
≤ 2 s
Response Time
40 ms maximum + (7 ms × number of following ISD devices)
Housing/Button (Flush mount models)
Polycarbonate / Polyamide #10 or M5 (M5 hardware included); Max.
tightening torque: 0.56 N·m (5 in·lbf)
Housing/Button (30 mm models)
Polycarbonate / Polyamide Threaded base has M30 by 1.5 external
threads Max. tightening torque: 4 .5 N·m (40 in·lbf)
Indication
(varies with model)
Yellow (590 nm) Green (525 nm) Red (618 nm)
Maximum Cable Length Between E-Stops
30 m
EMC
According to EN 61326-1 and EN 61326-3-1
Safety Data
SIL 3 (IEC 61508)
SILCL 3 (EN 62061)
Category 4, PL e (EN ISO 13849-1)
PFHD: 6.9 × 10-9 1/h according to EN 62061
Service Life: 20 years
B10d: 100,000 cycles
Operating Conditions
–25 °C to +50 °C (–13 °F to +122 °F)
45% to 85% relative humidity (no condensation)
Vibration Resistance
Operating extremes: 10 Hz to 500 Hz, amplitude 0.35 mm acceleration
50 m/s2
Environmental Ratings
For Indoor Use Only
IEC IP65 (EN 60529)
For the 30 mm models only with cover model SSAEB1P-ECWC
installed: IEC IP67, IEC IP69 (EN 60529)
3.1 Dimensions
All measurements are listed in millimeters, unless noted otherwise.
19
[.75]
59,5
[2.34]
33
[1.30]
119,8
[4.72]
80
3.15[ ]
M30 X 1.5
M12 X 1
1/2 -14 NPSM
5,0
[0.19]
32,8
[1.29] 30,0
[1.19]
12,7
[0.50]
Preferred Alternative
10,0
[0.38]
Hole Dimensions
Figure 12. 30 mm Models
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
12 www.bannerengineering.com - Tel: + 1 888 373 6767

97.5 mm
64.5 mm
86 mm dia
3 mm
58 mm dia
2 mm
46 mm dia
Figure 13. Washdown silicone cover SSA-EB1P-ECWC
DTM1
102.1
[4.02]
109.5
[4.31]
65
[2.56]
65
[2.56]
33
[1.30]
14.7
[0.58]
80.3
[3.16]
80.8
[3.18]
4X 5.5
0.22[ ]
10.2
[0.40]
Figure 14. Flush mount models
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 13

4 Accessories
4.1 Cordsets
8-Pin Threaded M12/Euro-Style Cordsets—Flying Leads
Model Length Style Dimensions Pinout (Female)
SXA-815D 4.57 m (15 ft)
Straight
44 Typ.
ø 14.5
M12 x 1
5
4
3
2
8
1
7
6
SXA-825D 7.62 m (25 ft)
SXA-850D 15.24 m (50 ft)
SXA-8100D 30.48 m (100 ft)
1 = White
2 = Brown
3 = Green
4 = Yellow
5 = Gray
6 = Pink
7 = Blue
8 = Red
5-Pin Threaded M12/Euro-Style Cordsets—Single Ended
Model Length Style Dimensions Pinout (Female)
MQDC1-501.5 0.5 m (1.5 ft)
Straight
44 Typ.
ø 14.5
M12 x 1
2
3
4
1
5
1 = Brown
2 = White
3 = Blue
4 = Black
5 = Gray
MQDC1-506 2 m (6.5 ft)
MQDC1-515 5 m (16.4 ft)
MQDC1-530 9 m (29.5 ft)
MQDC1-506RA 2 m (6.5 ft)
Right-Angle
32 Typ.
[1.26"]
30 Typ.
[1.18"]
ø 14.5 [0.57"]
M12 x 1
MQDC1-515RA 5 m (16.4 ft)
MQDC1-530RA 9 m (29.5 ft)
4-Pin Threaded M12/Euro-Style Cordsets—Single Ended
Model Length Style Dimensions Pinout (Female)
MQDC-406 2 m (6.56 ft)
Straight
44 Typ.
ø 14.5
M12 x 1
2
3
4
1
1 = Brown
2 = White
3 = Blue
4 = Black
MQDC-415 5 m (16.4 ft)
MQDC-430 9 m (29.5 ft)
MQDC-450 15 m (49.2 ft)
MQDC-406RA 2 m (6.56 ft)
Right-Angle
32 Typ.
[1.26"]
30 Typ.
[1.18"]
ø 14.5 [0.57"]
M12 x 1
MQDC-415RA 5 m (16.4 ft)
MQDC-430RA 9 m (29.5 ft)
MQDC-450RA 15 m (49.2 ft)
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
14 www.bannerengineering.com - Tel: + 1 888 373 6767

4-Pin Threaded M12/Euro-Style Cordsets—Double Ended
Model Length Style Dimensions Pinout
MQDEC-401SS 0.31 m (1 ft)
Male Straight/
Female Straight
40 Typ.
[1.58"]
ø 14.5 [0.57"]
M12 x 1
44 Typ.
[1.73"]
ø 14.5 [0.57"]
M12 x 1
Female
2
3
4
1
Male
1
4
3
2
1 = Brown
2 = White
3 = Blue
4 = Black
MQDEC-403SS 0.91 m (2.99 ft)
MQDEC-406SS 1.83 m (6 ft)
MQDEC-412SS 3.66 m (12 ft)
MQDEC-420SS 6.10 m (20 ft)
MQDEC-430SS 9.14 m (30.2 ft)
MQDEC-450SS 15.2 m (49.9 ft)
MQDEC-403RS 0.91 m (2.99 ft)
Male Right-Angle/
Female Straight
44 Typ.
[1.73"]
ø 14.5 [0.57"]
M12 x 1
32 Typ.
[1.26"]
30 Typ.
[1.18"]
ø 14.5 [0.57"]
M12 x 1
MQDEC-406RS 1.83 m (6 ft)
MQDEC-412RS 3.66 m (12 ft)
MQDEC-420RS 6.10 m (20 ft)
MQDEC-430RS 9.14 m (30.2 ft)
MQDEC-450RS 15.2 m (49.9 ft)
8-Pin Threaded M12/Euro-Style Cordsets―Double Ended
Model (8-pin/8-pin )4Length Style Dimensions Pinout
DEE2R-81D 0.3 m (1 ft)
Female Straight/
Male Straight
40 Typ.
ø 14.5
M12 x 1
44 Typ.
ø 14.5
M12 x 1
Female
5
4
3
2
8
1
7
6
Male
5
6
7
1
8
2
3
4
DEE2R-83D 0.91 m (3 ft)
DEE2R-88D 2.44 m (8 ft)
DEE2R-815D 4.57 m (15 ft)
DEE2R-825D 7.62 m (25 ft)
DEE2R-850D 15.24 m (50 ft)
DEE2R-875D 22.86 m (75 ft)
DEE2R-8100D 30.48 m (100 ft)
1 = White
2 = Brown
3 = Green
4 = Yellow
5 = Gray
6 = Pink
7 = Blue
8 = Red
4Standard cordsets are yellow PVC with black overmold. For black PVC and overmold, add the suffix "B" to the model number (example,
DEE2R-81DB)
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 15

4.2 Brackets
SSA-MBK-EEC1
• Single 30 mm hole
• 8 gauge steel, black finish (powder coat)
• Front surface for customer applied labels
80
85 60 45
B
A
SSA-MBK-EEC2
• Two 30 mm holes
• 8 gauge steel, black finish (powder coat)
• Front surface for customer applied labels
170 60 45
80 B
A
SSA-MBK-EEC3
• Three 30 mm holes
• 8 gauge steel, black finish (powder coat)
• Front surface for customer applied labels
255
B
A
80
60 45
The SSA-MBK-EECx brackets offer:
• Horizontal and vertical (post) mounting
• Interchangeable positions of mounted devices (e.g. OTB/STB/VTB, E-Stop, K50s)
Hole size: A = ø 7 , B = ø 30
4.3 Adapters and Other Accessories
Model Description
SI-RFA-TS SI-RF T-adapter for series connection, 4 pin to 8 pin to 4 pin
SI-RFA-TK SI-RF T-adapter for connection of the reset button, 8 pin to 4 pin to 8 pin
SI-RFA-P SI-RF Termination plug M12
SI-RFA-DM1 SI-RF Diagnostic Module with 8 digital outputs and 1 diagnostic circuit
Interfaces: IO-Link, USB 2.0
SSA-EB1P-ECWC FDA-grade silicone cover
4.4 Safety Controllers
Safety Controllers provide a fully configurable, software-based safety logic solution for monitoring safety and non-safety
devices. For additional models and XS26 expansion modules, see instruction manual p/n 174868 (XS/SC26-2).
Non-Expandable Models Expandable Models Description
SC26-2 XS26-2 26 convertible I/O and 2 Redundant Solid State Safety Outputs
SC26-2d XS26-2d 26 convertible I/O and 2 Redundant Solid State Safety Outputs with Display
SC26-2e XS26-2e 26 convertible I/O and 2 Redundant Solid State Safety Outputs with Ethernet
SC26-2de XS26-2de 26 convertible I/O and 2 Redundant Solid State Safety Outputs with Display and Ethernet
SC10-2roe 10 Inputs, 2 redundant relay safety outputs (3 contacts each) (ISD compatible)
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
16 www.bannerengineering.com - Tel: + 1 888 373 6767

4.5 Universal (Input) Safety Modules
UM-FA-xA Safety Modules provide forced-guided, mechanically-linked relay (safety) outputs for the SSA-EB1PLx-0Dx
system when an external manual reset (latch) is desired or external device monitoring is required in the application. See
datasheet p/n 141249 for more information.
Model Description
UM-FA-9A 3 normally open (N.O.) redundant-output 6 amp contacts
UM-FA-11A 2 normally open (N.O.) redundant-output 6 amp contacts, plus 1 normally closed (N.C.) auxiliary contact
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 17

5 Product Support and Maintenance
5.1 Maintenance and Service
Do not use alcoholic cleaning agents.
The SSA-EB1PLx-0Dx is maintenance-free.
For long-term and trouble-free operation, please periodically check the following points:
• solid fit of all components
• reliable switching function
• if damage occurs, please exchange the relevant components
Liability disclaimer— By breach of the given instructions (concerning the intended use, the safety instructions, the
installation and connection through qualified personnel and the testing of the safety function) manufacturer’s liability
expires.
5.2 Status Indicators
Operating Mode OSSD Inputs Indication OSSD Outputs
Power-up X Armed color (yellow, green or off, depending on the model) on for
0.5 s
Red on for 0.5 s
Off for 0.5 s minimum
OFF
Armed (button not pressed) ON Yellow, green, or off (depending on the model) ON
Actuated (button pressed) X Flashing red OFF
Re-armed, reset needed (specific models) ON Red OFF
Armed OFF Armed indication (yellow, green or off, depending on the model) OFF
Fault detected (non-critical) X Double flash red ON
Fault detected (critical) X Double flash red OFF
Faults that do not immediately compromise the safe operation of the emergency stop device (for example safety output to
external potential, crosswire short safety output) result in a delayed switch-off of the OSSDs. The OSSDs will turn off when
the error warning exceeds 20 minutes. See Fault-Tolerant Output Feature on p. 7 for more details.
5.3 EU Declaration of Conformity (DoC)
Banner Engineering Corp. herewith declares that these products are in conformity with the provisions of the listed directives
and all essential health and safety requirements have been met. For the complete DoC, please go to
www.bannerengineering.com.
Product Directive
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button
with ISD
Machinery Directive 2006/42/EC
Representative in EU: Peter Mertens, Managing Director, Banner Engineering BV. Address: Park Lane, Culliganlaan 2F, bus
3,1831 Diegem, Belgium.
5.4 Information Available Using ISD
Obtain the following information from the ISD chain and a diagnostic unit or an ISD-enabled Safety Controller.
Cyclic Data about the Chain
Short Name Data Format Description
Count mismatch 1/0 The number of devices in chain does not match configuration
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
18 www.bannerengineering.com - Tel: + 1 888 373 6767

Cyclic Data about the Chain
Short Name Data Format Description
Order mismatch 1/0 The order of devices in the chain does not match the configuration
No ISD data detected 1/0 No (or corrupted) ISD data being transmitted (being received by diagnostic device)
Incompatible device 1/0 The chain or a unit in the chain has data but not ISD data
ISD detected not configured 1/0 ISD data detected on inputs that are not configured as ISD input
Terminator missing 1/0 Terminator plug not present (or inputs to first device low)
Actuator not taught 1/0 Not applicable
Wrong actuator detected 1/0 Not applicable
Internal unit error 1/0 A unit in the chain has an internal error
Output fault detected 1/0 A unit in the chain has an output fault and will turn off after the switch off delay period
Individual Unit Data - Flags
Short Name Data Format Description
Actuator detected 1/0 Not applicable
Wrong actuator detected/Button
armed
1/0 E-stop button is in the run state
Sensor not paired 1/0 Not applicable
Output 1 1/0 Output 1 is on
Output 2 1/0 Output 2 is on
Marginal range/Button armed 1/0 E-stop button is in the run state
Input 1 1/0 ISD device input 1 is on
Input 2 1/0 ISD device input 2 is on
Local reset expected 1/0 An ISD device with the latch feature requires a reset
Operating voltage warning 1/0 Voltage to the ISD device is at the limit of specifications
ISD data error 1/0 ISD error bit, corrupted data was received from the SI-RF ISD chain of switches.
Safety input fault 1/0 The system detected a fault on a safety input of an ISD device, power cycle required
Output error 1/0 ISD Device detects an output short to voltage or ground. This starts the "switch-off timer"
counter.
Operating voltage error 1/0 Voltage to the ISD Device is above (over 30 V DC) or below (less than 19.2 V DC) limit of range.
Power cycle required 1/0 ISD Device detects a fault, a power cycled required.
Individual Unit Data - Configuration
Short Name Data Format Description
Local reset unit 1/0 The ISD Device includes the latch feature
High coding level 1/0 Not applicable
Cascadable 1/0 The ISD Device includes the cascade feature Note: This will always be true for Emergency Stop
models with ISD.
Fault tolerant outputs 1/0 Indicates that the ISD Device includes the fault tolerant output feature where output faults cause a
20 minute off delay/fault delay. Note: This will always be true for Emergency Stop models with
ISD.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
www.bannerengineering.com - Tel: + 1 888 373 6767 19

Individual Unit Data - Values
Short Name Data Format Description
Device Type of ISD Device
Expected code Not applicable
Received code Not applicable
Teach-ins remaining number Not applicable
Number of voltage errors number The number of voltage warnings received in the last 60 seconds (voltage is checked every
second), a number between 0 and 60
Number of operations number The number of on/off cycles the device has experienced
Output switch-off time number The delay counter for certain output faults (0 - inactive, 20 to 1 - remaining minutes to device
lockout state)
Range warning count number Not applicable
Supply voltage number The actual input voltage detected by the ISD device.
Internal temperature number The internal temperature of the ISD device (°C)
Actuator distance number Not applicable
Expected company name Not applicable, value of 6 will be received
Received company name Not applicable, this is the code received from an actuator (for RFID switches)
5.5 Contact Us
Banner Engineering Corp. headquarters is located at:
9714 Tenth Avenue North
Minneapolis, MN 55441, USA
Phone: + 1 888 373 6767
For worldwide locations and local representatives, visit www.bannerengineering.com.
5.6 Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will
repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This
warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING
OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE
LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR
SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR
WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product
previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection
applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval
by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product
specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most
recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.
SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD
20 www.bannerengineering.com - Tel: + 1 888 373 6767
This manual suits for next models
12
Table of contents
Other Banner Safety Equipment manuals