BeaconMedaes Lifeline Manual

Installation, Operation and Maintenance Instructions
Lifeline Medical Systems
Liquid Pressure Fully-Automatic Manifold
Basic/TAE
NFPA/ISO
Part number 4107 9013 94
Revision 03
28 March 2018
U.S. Design Patent No. D734,854
LQLQ X
Liquid x Liquid Models

Part number 4107 9013 94
Revision 03
28 March 2018
Installation, Operation and Maintenance Manual
Lifeline Medical Systems
Liquid by Liquid Fully-Automatic Manifold
This unit is purchased from:
Date purchased:
Model number:
Serial number:
Option(s) included:
Any information, service or spare parts requests should include the machine serial number and be
directed to:
BeaconMedæs
1059 Paragon Way
Rock Hill, SC 29730
Telephone: (888) 463-3427
Fax: (803) 817-5750
BeaconMedæs reserves the right to make changes and improvements to update products sold
previously without notice or obligation.

i
Liquid by Liquid Manifold
4107 9013 94.03
Table of Contents
1.0 Introduction
1.1 Audience
1.2 Abbreviations
1.3 Definition of Statements
1.4 Product Description
1.5 Environmental Considerations
1.6 Environmental Declarations
2.0 Installation
2.1 Precautions
2.2 Manifold System Components
2.3 Wall Mounting Instructions
2.4 Floor Mounting Instructions
2.5 Wall Mounting HP Reserve Header
2.6 Main Outlet and Relief Valve Connection
2.7 HP Reserve Header Connection
2.8 Power Supply
2.9 Reserve Low Pressure Switch Wiring
2.10 Remote Alarm Connection
2.11 Pigtail/Cylinder Connection
2.12 Initial Power Up and Operational Testing
2.13 Leak Test
3.0 Operation
3.1 Precautions
3.2 Manifold Specifications
3.3 Flow Characteristics
3.4 Manifold Components
3.5 Gas Flow Through The Manifold
3.6 Manifold Changeover

ii
Liquid by Liquid Manifold
4107 9013 94.03
4.0 Testing and Adjustments
4.1 Performance Verification
4.2 Bank Regulator Pressure Adjustment
4.3 Line Regulator Pressure Adjustment
4.4 Reserve Header Regulator Adjustment
4.5 Changeover pressure Switch Adjustment
4.6 Reserve Low Pressure Switch Adjustment
5.0 Service Procedures
5.1 Precautions
5.2 Routine Maintenance
5.3 Techniques For Leak-Tight Connections
5.4 Changeover Pressure Switch /
Transducer Replacement
5.5 Bank Regulator Maintenance
5.6 Line Regulator Maintenance
5.7 Reserve Header Regulator Maintenance
5.8 Reserve Low Pressure Switch/Transducer
Replacement
5.9 Check Valve/Ball Valve Replacement
5.10 Control Board Replacement
5.11 Wiring Diagrams
6.0 TotalAlert Embedded (TAE)
6.1 Remote Monitoring
6.2 Set Up: Physical Connection
6.3 Set Up: Network Configuration
6.4 Set Up: Connecting the the Embedded
Website of the Manifold
6.5 Log in to Setup Pages
6.6. Device Setup
6.7 Network Setup
6.8 System Trend Setup
6.9 Electronic Notification Setup
6.10 Navigating the Website
7.0 Optional Reserve Header (ISO
Versions)
7.1 Reserve Header
7.2 Wall mounting HP Reserve Header
7.3 Initial Power Up and Operational Testing
Table of Contents (continued)

1-1
Liquid by Liquid Manifold
4107 9013 94.03
1.0 Introduction
1.1 Audience
This manual provides information related to
the installation and operation of the Lifeline
Liquid container manifold manufactured by
BeaconMedæs. Service information contained in
this manual is intended for use by technicians or
personnel qualified to repair and service medical
equipment.
1.2 Abbreviations
AR Argon
CGA Compressed Gas Association
CO2Carbon Dioxide
N2Nitrogen
N2O Nitrous Oxide
NPTF National Pipe Thread Female
NPTM National Pipe Thread Male
NER Normal Evaporation Rate
O2Oxygen
PSI Pounds Per Square Inch
scfm Standard Cubic Feet Per Minute
scfh Standard Cubic Feet Per Hour
VAC Voltage, Alternating Current
VDC Voltage, Direct Current
1.3 Definition of Statements
Statements in this manual preceded by following
words are of special significance.
WARNING: Means there is a possibility of
injury or death to yourself or others.
CAUTION: Means there is a possibility of
damage to unit or other property.
NOTE: Indicates points of particular interest for
more ecient and convenient operation.
1.4 Product Description
Lifeline automatic changeover manifold system
is designed to provide a reliable, uninterrupted
supply of gas to a hospital or other medical
facility. A typical manifold system consists of a
manifold control panel with two banks of liquid
containers and a separate high-pressure reserve
header assembly.
The manifold control panel utilizes multiple liquid
containers divided into two equal banks and is
often referred to as “liquid x liquid” or “LQ x LQ”.
One bank is designated as the “Primary” source
of gas while other bank stands in reserve as the
“Secondary” source.
The manifold control module is connected to an
external high pressure reserve header assembly
consisting of multiple high-pressure cylinders.
Lights on the front of the manifold control module
indicate the status of gas supply. Each manifold
bank has a green (IN USE), green (READY), and red
(EMPTY) light, a yellow (RESERVE IN USE) and red
(RESERVE LOW) light also located on the manifold.
When the manifold’s primary bank of liquid
containersisdepleted,thesystemwillautomatically
switch to the secondary bank of liquid cylinders.
When the liquid containers are replenished, the
manifold will automatically switch back to the
primary (left) bank. If the primary bank of liquid
containers and the secondary bank of liquid
cylinders are depleted, the manifold system will
automatically switch to the external high-pressure
reserve header assembly.
Normally-closed dry switch contacts are supplied
for each alarm condition listed below. Switch
contacts are typically wired to the external master
alarm panels and will open when an alarm
condition occurs.
• Changeover
• Reserve In Use
• Reserve Low

1-2
Liquid by Liquid Manifold
4107 9013 94.03
Product Description (Cont.)
A power supply converts 100-250 VAC to 24 VDC
to power the manifold. Two sets of dry normally
closed alarm contacts can be accessed inside the
manifold control module.
The Lifeline manifold is designed in accordance
with the National Fire Protection Association
(NFPA) 99 and International Organization for
Standardization (ISO) 7396-1.
1.5 Environmental Considerations
Manifolds are to be installed in accordance with
requirements stated by NFPA 99, ISO 7396-1, CGA
and all applicable local codes.
The BeaconMedaes Lifeline manifold has been
environmentally tested to MIL STD 810F. The
power supply and control board is fully contained
inside a NEMA 4 enclosure, allowing for outdoor
installations. The manifold can be used in high
humidity conditions and was successfully tested
at 86°F (30°C) - 140°F (60°C) with 95% relative
humidity, per MIL STD 810F.
The power supply and electrical components have
a pollution degree 1 classification. The manifold
components will be used in a pollution degree 4
environment.
The manifold components are designed to work
best over a temperature range of 0° F (-18° C)
through 130° F (54° C). Wider temperature
variations may cause manifold malfunctions to
occur. The manifold is designed to be used below
2,000 meters, for higher elevations contact the
factory.
Installinganitrousoxideorcarbondioxidemanifold
and high-pressure reserve header assembly in a
location that exposes it to ambient temperatures
below 32° F (0° C) is not recommended.
Disposal of Materials
Dispose contaminated substances and materials
separately, according to local applicable
environmental legislations.
NOTE:
This concept can only succeed with your
help.
Support us by disposing professionally.
By assuring a correct disposal of the
product you help to prevent possible
negative consequences for environment and
health that can occur with inappropriate
waste handling.
Recycling and re-usage of materials helps to
preserve natural resources.
1.6 Environmental Declarations
Disposal
General
When developing products and services,
BeaconMedæs tries to understand, address, and
minimize the negative environmental eects that
the products and services may have, when being
manufactured, distributed, and used, as well as at
their disposal.
Recycling and disposal policies are part of the
development of all BeaconMedæs products.
BeaconMedæs company standards determine
strict requirements.
When selecting materials the substancial
recycability, the disassembly possibilities and the
separability of the materials and assemblies are
considered as well as the environmental perils
and dangers to health during the recycling and
disposal of the unavoidable rates of non-recycable
materials.
BeaconMedæs products for the most part consist
of metallic materials that can be remelted in
steelworks and smelting works and that is therefore
almost infinitely recyclable. The plastic use is
labeled; sorting and fractioning of the materials
for recycling in the future is foreseen.

2-1
Liquid by Liquid Manifold
4107 9013 94.03
2.0 Installation
2.1 Precautions
WARNING:
• Tampering with gas specific connections
shall be prohibited. Do not alter, remove or
modify gas specific connections.
• Keep all manifold parts, tools and work
surfaces free of oil, grease and dirt. These and
other flammable materials may ignite when
exposed to high pressure oxygen or nitrous
oxide.
• Do not use chemicals, lubricants or sealants
unless specified in these instructions.
• Before connecting cylinder to manifold,
momentarily open and close cylinder valve
to blow out dirt and debris.
• After connecting cylinder to manifold, open
cylinder valve s-l-o-w-l-y to allow heat of
compression to dissipate.
• Do not use flame or “sni” tests for leaks.
• Do not apply heat to any part of the manifold
system.
• Always secure high-pressure cylinders
with racks, straps, or chains. Unrestrained
cylinders may fall over and damage or break
o cylinder valve.
• Do not repeatedly bend, sharply bend, or
twist copper pigtails as damage to tubing
may occur.
• Do not bend flexible pigtails into a radius
smaller than 3”.
• After manifold wall bracket has been
mounted, one person alone should not
attempt to lift and hang the manifold cabinet.
• Do not put manifold into operation until
verified by a qualified person per NFPA 99 or
ISO 7396-1
2.2 Manifold System Components
The manifold system may be shipped in more
than one carton, depending on the number of
cylinder connections. The main carton contains
the following items:
• Manifold control module
• Wall mounting bracket (attached to manifold
control panel)
• ¾” source shut-o valve
• High-pressure reserve header inlet fittings
(attached to manifold on NFPA model only)
• Installation, Operation, and Service Manual
Additional cartons contain the appropriate
number of header extensions and cylinder pigtail
assemblies. High Pressure cylinders for reserve
header (NFPA) must be placed in a double row
“staggered” configuration. High Pressure pigtails
for gases other than oxygen and N2O are 24” length
stainless-steel flexible type.
Pigtails for all liquid containers are 72” length
flexible type. The manifold is designed to mount
directly to a wall, or be freestanding floor-mounted
with addition of a manifold control module floor
stand kit and an appropriate number of header
floor stand kits for reserve header assembly (sold
separately).

2-2
Liquid by Liquid Manifold
4107 9013 94.03
2.3 Wall Mounting Instructions
1. Remove manifold control module from
shipping carton and place face up on cardboard
packaging insert.
2. Remove the control module enclosure by
releasing the two latches on each side and set
the cover aside.
3. Remove the four M8 hex head bolts from the
mounting bracket as shown in Figure Lift the
manifold away from the mounting bracket and
set aside.
4. Mark wall 77-½” from finished floor in
location where manifold will be mounted.
Convert mark to level horizontal line
approximately 8” long.
Figure 1
Manifold Control
Module
M8 Hex Head Bolt
(4 Places)
Mounting Bracket

2-3
Liquid by Liquid Manifold
4107 9013 94.03
5. Place bracket flat against wall as shown
in Figure 2 and align top of bracket with
level horizontal line. Vertical center line of
bracket will be vertical center line of installed
manifold. Mounting top of bracket at 77-½”
height will net a 65-¾” height from center of
header to finished floor.
6. Mark locations of mounting holes. Remove
bracket and drill mounting holes. Attach
bracket to wall with appropriate anchors
(by others). ⅜” diameter anchors are
recommended.
WARNING:
Do not attempt to lift manifold alone. Two
people are recommended in order to hang
manifold onto wall mounting bracket.
Wall Mounting Instructions (cont.)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
.XX .02
.XXX .005
.XXXX .0005
ANGLES .5
2 of 8
D
Sheet
Date:Revised: Date: Drawn:
ARE IN INCHES AND TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS
DOCUMENT
DO NOT SCALE THIS
Scale:
Description:
MDB 7/9/2013
BEACONMEDÆS
Drawing Number:
Rev:
DN:
79-3/4"
TO FLOOR
Figure 2
Locate Bracket Per
Level Horizontal
Line
Mark Location of
Mounting Holes
4 plcs 77-½”
TO FLOOR

2-4
Liquid by Liquid Manifold
4107 9013 94.03
Figure 3
Wall Mounting Instructions (cont.)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
.XX .02
.XXX .005
.XXXX .0005
ANGLES .5
3 of 8
D
Sheet
Date:Revised: Date: Drawn:
ARE IN INCHES AND TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS
DOCUMENT
DO NOT SCALE THIS
Scale:
Description:
MDB 7/9/2013
BEACONMEDÆS
Drawing Number:
Rev:
DN:

2-5
Liquid by Liquid Manifold
4107 9013 94.03
7. Hang manifold control panel on tab of
mounting bracket (Figure 3). Using M8 hex
bolt, attach manifold to wall bracket through
slots in black plate (4 places).
8. For all manifolds, additional shipping cartons
contain extension headers and master valves.
Attach master valve and appropriate header
extension to manifold control panel. Position
cylinder inlet connections of each header
extension so they are pointing out (away from
the wall) and tighten header extension (Figure
4).
NOTE:
A mounting height of 65-¾” allows for
adequate clearance beneath reserve header
assembly when utilizing standard “H” size
cylinders (55” tall overall). Bracket mounting
height should be increased proportionally if
taller cylinders are to be used.
CAUTION:
Do not use thread sealant on header or pigtail
connections.
Wall Mounting Instructions (cont.)
Figure 4

2-6
Liquid by Liquid Manifold
4107 9013 94.03
For floor mounting the manifold control panel
and headers, a manifold control panel stand kit
and an appropriate number of manifold header
stand kits should have been ordered separately.
One manifold control panel stand kit contains
all items needed to mount the control panel.
Depending on the number of header segments,
one or more header stand kits are required. A
header stand is required for each header segment.
Each header stand kit contains two vertical stands
and all necessary items to support one 2-cylinder
or 3-cylinder header segment on each side of the
manifold. Verify contents of stand kits (Figures 6
and 7):
1. Remove manifold control module from
shipping carton and place face up on cardboard
packaging insert.
2. Remove the control module enclosure by
releasing the two latches on each side and set
the cover aside.
3. Remove the four M8 hex head bolts from the
mounting bracket as shown in Figure 1.
4. Only bracket will be needed at this time.
Set manifold control panel aside for
installationlater.
5. Attach post base to one end of each 80-inch
channel as shown in Figure 8, Detail A. Use
two each ⅜” bolts, flat washers and channel
nuts per base. Tighten all four bolts.
6. Stand each channel / base side by side. Attach
manifold mounting bracket to both bases as
shown in Figure 8, Detail C. Use four each ⅜”
bolts, flat washers and channel nuts perbase.
Top of bracket should be level and positioned
77 ½” above floor. Tighten all fourbolts.
2.4 Floor Mounting Instructions
7. Position entire assembly in desired manifold
mounting location. Mark location of eight base
mounting holes. Move assembly aside and
drill holes. Minimum ⅜” diameter mounting
boltsare recommended (by others).
8. Reposition assembly over holes and install
mounting hardware (by others). Tighten all
mounting bolts.
9. Hang manifold control module on tab of
mounting bracket (Figure 3). Using M8 hex
bolt, attach manifold to wall bracket through
slots in black plate (4 places).
10. Additional cartons containing mastervalves
and header assemblies will be shipled loose.
Attach the master valves and appropriate
header extensions to the manifold control
panel.Position cylinder inlet connections of
each header extension so they are pointing
out (away from the wall) and tighten header
extension (Figure 4).
11. Set header stand in a vertical position roughly
in alignment with two vertical control panel
stands. Position header bracket against
channel and on bottom side of header as
shown in Figure 5. Attach bracket to channel as
shown in Figure 8, Detail B. Use two each ⅜”
bolts, flat washers and channel nuts. Tighten
all bolts.
12. Align header stand with two control panel
vertical stands, centering the header bracket
between two pigtail connections. Mark
locations of all four base mounting holes.
Move header stand aside and drill holes.
Minimum ⅜” diameter mounting bolts are
recommended (by others).
13. Reposition header stand over holes and install
mounting hardware (by others). Tighten all
mounting bolts.
NOTE: Return control panel to shipping carton if
necessary to protect it and keep it clean.

2-7
Liquid by Liquid Manifold
4107 9013 94.03
CAUTION:
Do not use thread sealant on header or
pigtail connections.
2.4 Floor Mounting Instructions Cont.
14. Assemble u-bolt and bracket hardware
asshown in Figure 6. Tighten u-bolt nuts.
15. Additional header extensions may be
attached end to end if required.
16. Install large nut and plug on end of last
header extension. Tighten large nut.
Figure 6
Figure 5
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
.XX .02
.XXX .005
.XXXX .0005
ANGLES .5
1 of 3
D
Sheet
Date:Revised: Date: Drawn:
ARE IN INCHESAND TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED ALL DIMENSIO NS
DOCUMENT
DO NOT SCALE THIS
Scale:
Description:
MDB 10/3/2013
BEACONMEDÆS
Drawing Number:
Rev:
DN:
is loaned without the expressed w ritten permission from BeaconMedæs Engineering.
BeaconMedæs and may not be used for other than the purpose for whic h it
This drawing and the information contained thereon remai n the property of
Form F-007 Rev. 01
FOR QUOTE ONLY
80" CHANNEL (X 2)
POST BASE (X 2)
3/8-16 X 1" BOLT (X 8)
3/8" FLAT WASHER (X 8)
3/8-16 CHANNEL NUT (X 8)
STAND KIT, MANIFOLD CONTROL PANEL
P/N 6-135000-KT
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
.XX .02
.XXX .005
.XXXX .0005
ANGLES .5
2 of 3
D
Sheet
Date:Revised: Date: Drawn:
ARE IN INCHESAND TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED ALL DIMENSIO NS
DOCUMENT
DO NOT SCALE THIS
Scale:
Description:
MDB 10/3/2013
BEACONMEDÆS
Drawing Number:
Rev:
DN:
3/8-16 X 1" BOLT (X 8)
3/8" FLAT WASHER (X 8)
3/8-16 CHANNEL NUT (X 8)
POST BASE (X 2)
66" CHANNEL (X 2)
STAND KIT, MANIFOLD HEADER
P/N 6-135001-KT
STAND KIT, MANIFOLD HEADER
STAND KIT, MANIFOLD CONTROL PANEL

2-8
Liquid by Liquid Manifold
4107 9013 94.03
DETAIL A
DETAIL B
DETAIL C
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
.XX .02
.XXX .005
.XXXX .0005
ANGLES .5
3 of 3
D
Sheet
Date:Revised: Date: Drawn:
ARE IN INCHES AND TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS
DOCUMENT
DO NOT SCALE THIS
Scale:
Description:
MDB 10/3/2013
BEACONMEDÆS
Drawing Number:
Rev:
DN:
Figure 7
CAUTION:
Each header segment must be supported by
a header bracket before additional header
segments are added.
MANIFOLD CONTROL AND
HEADER STAND KIT ASSEMBLY

2-9
Liquid by Liquid Manifold
4107 9013 94.03
2.5 Wall Mounting HP Reserve
Header (If Equippped)
High pressure reserve header components may
be shipped in several cartons. One carton will
contain the control section assembly consisting
of regulator assembly, and reserve low pressure
switch as shown in Figure 8. Additional shipping
cartons contain header extensions, cylinder
pigtails, header wall brackets, master valve, and
plug and nut. Depending on the number of
cylinders, header extensions are configured with
two or three cylinder inlets. Large reserve headers
may also include combinations and multiples of
each type of header extension.
1. Attach master valve to the control assembly.
Attach appropriate header extension to control
section. Position cylinder inlet connections of
each header extension so they are pointing
out . Additional header extensions may be
attached end to end if required. Install large
nut and plug on end of last header extension
(Figure 10).
2. Mark wall 65-¾” from finished floor in
location where high-pressure reserve header
will be mounted. Convert mark to level
horizontal line approximately as long as
assembled high-pressure reserve header.
3. Depending upon number of header
extensions, two or more header brackets
will be provided. Header brackets should
be positioned along length of high-pressure
reserve header assembly and should contact
header directly between cylinder connections.
A header bracket will typically be provided
for each header extension. Measure centerline
distance between header brackets and
transfer those measurements to horizontal
line described in step 2 as shown in Figure 10.
4. Position header bracket against wall and align
top of bracket with horizontal line. Center
brackets with centerline marks from step 3.
Attach brackets to wall using appropriate
anchors (by others). ⅜” diameter anchors are
recommended.
5. Set complete reserve header on top of wall
brackets and assemble u-bolt and bracket
hardware as shown. Tighten u-bolt nuts.
6. One more wall bracket should be installed to
support left side of reserve header assembly
as shown in Figure 10.
7. Tighten all header extension unions and
plugs. Ensure all cylinder connections point
away from wall.

2-10
Liquid by Liquid Manifold
4107 9013 94.03
Figure 8
Reserve Low
Pressure Switch
Regulator Assembly
NOTE:
Configuration and number of header extensions
will vary depending upon size of high-pressure
reserve header assembly (5-cylinder model
shown).
Wall Mounting HP Reserve Header (cont.)
Figure 9
Above finished floor
65 ¾”
Top of bracket aligned
with horizontal line on
wall. NOTE:
Distance between wall brackets to be
determined by installer. Depending upon
reserve header configuration, multiple
brackets may be required. A bracket is
provided for each header segment and
should contact header between cylinder
connections as shown in Figure 10.

2-11
Liquid by Liquid Manifold
4107 9013 94.03
Figure 10
Attach wall bracket at this location
in order to support control section.
Header Extesions
Nut & Plug
Wall Mounting HP Reserve Header (cont.)

2-12
Liquid by Liquid Manifold
4107 9013 94.03
The Power supply box contains a 24 VDC power
supply and terminal blocks for AC input power
and remote alarm connection. Holes for ½”
conduit are located on top of power supply box
for 100 to 250 VAC, 50/60 Hz power and remote
alarm wiring.
Current draw will be less than 250 milliamperes.
Fuse type is 5 x 20 mm, GMD-250mA.
Chassis grounding for manifold provided by
included wiring to back plate and enclosure door.
Only ground wire required is through incoming
power terminal.
2.9 Reserve Low Pressure Switch
Wiring (If Equipped)
The reserve low pressure switch is located on high
pressure reserve header assembly (Figure 8) and
must be wired to appropriate terminals inside
power supply (Figure 11). See wiring diagram
(Figures 32 and 33) for proper connection points.
The pressure switch is equipped with 20” wire leads
and a ½ NPTM conduit connection. Stranded wire
of at least 22 gauge is recommended. Maximum
recommended wire size is 14 gauge.
2.10 Remote Alarm Connection
For connection to a remote alarm or building
automation system, three sets of dry, normally
closed alarm contacts are available inside power
supply assembly. One of three sets is designated
for each alarm condition listed below.
• Changeover
• Reserve In Use
• Reserve Low
All three sets of contacts are independent of each
other and will be closed whenever manifold
is powered and operating normally (no alarm
condition). If any alarm condition above occurs,
the appropriate set of contacts will open. If AC
power to manifold is removed, all three sets of
contacts will open.
2.6 Main Outlet and Relief Valve
Connection
The manifold’s main outlet and the relief
valve outlet are supplied with zero clearance,
O-ring sealed unions. The main outlet con-
nection is ¾” MNPT and relief valve is ½”
FNPT. A ¾” source shut-o valve is also sup-
plied with a manifold control module. The
inlet side of the source shut-o valve is ¾”
MNPT for connection directly to the main
outlet union. The outlet side is a ¾” nominal
copper. A plugged, ⅛” FNPT port is provided
on the outlet side of the valve and may be
removed to aid in purging.
2.7 HP reserve Header Connection
(If Equipped)
High-pressure reserve header must be piped to
inlet on right side of manifold control panel. The
outlet of the reserve header is supplied with a
zero clearance, O-ring sealed union with ½” NPTF
connection.
NFPA models include a zero clearance, O-ring
sealed union with a ½” NPTF connection for the
reserve header on the manifold. This connection
must be ordered separately for ISO models.
Piping type and installation must be in accordance
with current NFPA 99 and ISO 7396-1 requirements.
2.8 Power Supply
A power supply assembly is provided with
manifold control module. The installer must
use 12-14 AWG copper supply wiring when
connecting to the manifold. Power supply shall
be connected to a building installed circuit
breaker. Circuit breaker shall be a maximum
15 amps and marked as disconnecting means
for manifold. It is recommended that circuit
breaker be in close proximity to manifold power
supply and properly sized according to local and
national regulations. The manifold has a
category II overvoltage rating.

2-13
Liquid by Liquid Manifold
4107 9013 94.03
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
.XX .02
.XXX .005
.XXXX .0005
ANGLES .5
5 of 5
D
Sheet
Date:Revised: Date: Drawn:
ARE IN INCHES AND TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS
DOCUMENT
DO NOT SCALE THIS
Scale:
Description:
MDB 7/16/2013
BEACONMEDÆS
Drawing Number:
Rev:
DN:
Standard Electronics Shown
Top View
Data
AlarmPower
Three ½” conduit knockouts for AC power
input and alarm output field wiring
Ground
Neutral
Line
100-250 VAC
Input Power
Power Supply Wiring Control
Figure 11
Connection Terminals
for Remote Alarms
(See wiring diagram for
connection points)
2.10 Remote Alarm Connection Cont.
Refer to Figure 11 for power supply
connections.

2-14
Liquid by Liquid Manifold
4107 9013 94.03
WARNING:
• All pigtail assemblies are shipped in sealed
bags and are cleaned as if for oxygen use.
Manifold control panel and reserve header
connections are clean and capped. Do not
unpackage or remove any cap until ready
to install. During installation use care to
maintain cleanliness.
• Do not connect 72” black flex pigtail to high
pressure reserve header assembly. This type
of pigtail must only be connected between
manifold control panel and liquid containers.
• Do not repeatedly bend, sharply bend, or
twist copper pigtails as damage to tubing
may occur.
• Do not bend high-pressure flexible pigtails
into a radius smaller than 3”.
• Always secure high-pressure cylinders
with racks, straps, or chains. Unrestrained
cylinders may fall over and damage or break
o cylinder valve.
CAUTION:
• Do not use thread sealant on header or
pigtail connections.
• Prior to connecting pigtail to cylinder, slightly
open and close each cylinder valve to blow
out dirt and debris.
NOTE:
Both ends of flexible pigtails are the same. Either
end may be connected to manifold header.
Rigid copper pigtails on oxygen manifolds are
pre-formed and must be connected as shown in
Figure 14.
2. Connect one end of pigtail assembly to
reserve header connection. Coiled end of rigid
copper pigtails attaches to reserve header
connection.
3. Position gas cylinders as shown in Figures 13
and 14. Secure each cylinder to wall or floor
stand with chains or straps.
4. Connect pigtails to each cylinder. Rigid
copper pigtails used on oxygen systems are
pre-formed to approximate required shape.
Lower end of rigid copper pigtails must be
bent 90° toward cylinder outlets.
5. Tighten all pigtail connections firmly. Do not
over-tighten.
2.11 Pigtail/Cylinder Connection
72” black flex pigtails are connected between
manifold control panel and liquid containers
(Figure 12). Remove plastic shipping caps from
manifold control panel inlets. Connect either end
of 72” black flex pigtail to manifold inlet. Connect
other end of pigtail to gas outlet of liquid container.
All high-pressure reserve header assemblies other
than oxygen utilize 24” length flexible stainless-
steel braided pigtails. Figure 13 illustrates a typical
5 cylinder high-pressure reserve header assembly
utilizing flexible pigtails.
Oxygen high-pressure reserve header assemblies
are supplied with pre-formed rigid copper pigtails.
Figure 14 illustrates a typical 5 cylinder high-
pressure reserve header assembly utilizing pre-
formed rigid copper pigtails.
To install high-pressure reserve header pigtails:
1. Remove plastic shipping caps from reserve
header pigtail connections.
Other manuals for Lifeline
1
Table of contents
Other BeaconMedaes Medical Equipment manuals

BeaconMedaes
BeaconMedaes Gemini Diamond II User manual

BeaconMedaes
BeaconMedaes Magnis Vac MSV Series Manual

BeaconMedaes
BeaconMedaes 6-211600-00 User manual

BeaconMedaes
BeaconMedaes MV80 Manual

BeaconMedaes
BeaconMedaes Z MED Medical Air System Manual

BeaconMedaes
BeaconMedaes Floor Pedestal User manual

BeaconMedaes
BeaconMedaes AGS Series User manual

BeaconMedaes
BeaconMedaes Lifeline Medical Systems Setup guide

BeaconMedaes
BeaconMedaes Gemini User manual

BeaconMedaes
BeaconMedaes TotalAlert Infinity User manual