Page 2
CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any useofthe detectorforpurposesotherthan theintended oneisconsideredimproper,andasaresultof whichBEINAT
S.r.l. therefore disclaims any responsibility for possible damages caused to people, animals or objects.
IMPORTANT: Do not test the device using the gas tap as this does not necessarily provide sufficient concentration
to activate the main alarm.
TERMSand EXPECTATIONS: The installation of the CHCO gasdetector, its ordinary and extraordinary maintenance,
every six months, and its out of service removal atthe end of the functional life guaranteed by the manufacturer, must
be carried out by authorized or specialized personnel.
Inorder to achieve long and satisfactory use of your CHCOgas detector,, use itby respecting the following precautions.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the detector could work poorly.
Above about +40°C, the detector could become very sensitive, and generate false alarms.
Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high
levels of humidity.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Technical Specifications
Power supply ............................................................................................ 230Vac 50 /60 Hz +/- 10%
Power consumption ......................................................................................................................... 1W
Change-over relays for explosive gas detection .......................................................... 10A 250V ~ resistive
Change-over relays for CO toxic gas detection ........................................................... 10A 250V ~ resistive
Insulation ........................................................................................................................... Class II
Explosive Gas
Explosive gas sensor ..................................................................................................................... Catalytic
Explosion Alarm Threshold .............................................................................................. At 10% of L.E.L
ToxicGas
CO toxic gas sensor ................................................................................................ Electrochemical Cell
CO detector alarm sensitivity ................................................................................................ 30 ÷300ppm
CO gas detector alarm threshold according to norm EN 50291 on gas accumulation:
ALARMS
30 ppm within 120 minutes
50 ppm within 60 minutes
100 ppm within 10 minutes
300 ppm within 3 minutes
Audible and visual signal alarm by ............................................................................... LED diode and buzzer
Sensors’ faults detected by Fault Circuit ................................................... Interruption, short circuit, or wear
Functioning Temperature ..................................................................................................-10°C to +40°C
Functioning Humidity ........................................................................................ 0÷90% RH non condensed
External degree of protection ......................................................................................................... IP42
Mounting ................................................................................. External wall mount, or embedded box 503
Body material ....................................................................................................... ABS self-extinguishing
Dimensions ......................................................................................................................... 115x150x52
Precautions
Operating specifications of the gas sensors
The ELECTROCHEMICAL CELL technology sensor has a duration of: 5 years.
The CATALYTIC technology sensor has a duration that can vary: from 5 to 6 years.
The sensor’s functioning temperature, independently of the technology used, ranges from -10°C to +40°C
ATTENTION!
The CATALYTIC probe does not tolerate a gas detection exceeding 100% of L.E.L., with consequent natural
death of the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
To test the toxic gas, issue gas from a pre-calibrated aerosol from 30 to 300 ppm, into the grey sensor.
Please see point 6. Using other types of gas is useless and could damage the sensor.
The detector must be tested by simulating the presence of gas issuing it from a pre-calibrated aerosol.
MAINTENANCE
The user periodically (every 6 months) must perform a check of the operation of the control unit by
spraying a suitable test gas at the base of the probes connected until the alarm condition is reached.
• At least once a year make a more accurate check by a specialist technician.
• Disabling the detector must be carried out by qualified personnel.