Carel humiFog User manual

NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
ENG
INSTALLATION MANUAL
humiFog
Zone panel
humiFog
+0300114EN - ENG
Up to date version available on
www.carel.com


3
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
GENERAL WARNINGS
FAILURE TO CAREFULLY HEED THE WARNINGS SHOWN IN THIS MAN-
UAL COULD LEAD TO FIRE OR EXPLOSION AND CONSEQUENT DAM-
AGE TO PROPERTY, INJURY OR DEATH.
CAREL Industries humidiers are advanced products, whose operation is
specied in the technical documentation supplied with the product or
can be downloaded, even prior to purchase, from the website www.carel.
com. Each CAREL product, in relation to its advanced level of technology,
requires setup/conguration/programming to be able to operate in the
best possible way for the specic application. Failure to complete such
operations, which are required/indicated in the user manual, may cause
the nal product to malfunction; CAREL accepts no liability in such cases.
The customer (manufacturer, developer or installer of the nal equipment)
accepts all liability and risk relating to the conguration of the product in
order to reach the expected results in relation to the specic nal instal-
lation and/or equipment. CAREL may, based on prior agreements, act as
a consultant for the installation/commissioning/use of the unit, however
in no case does it accept liability for the correct operation of the humid-
ier and the nal installation if the warnings or suggestions provided in
this manual or in other product technical documents are not heeded. In
particular, as well as observing the above warnings and suggestions, the
following warnings must be observed for correct use of the product:
ELECTRIC SHOCK HAZARD: the humidier contains live electrical
components. Disconnect the mains power supply before accessing
inside parts or during maintenance and installation.
WATER LEAK HAZARD: the humidier automatically and constantly
lls/drains certain quantities of water. Malfunctions in the connections
or in the humidier may cause leaks.
CAUTION
The installation of the product must include an earth connection, using
the special yellow-green terminal available in the humidier.
Caution:
• Disconnect the appliance from the mains power supply before access-
ing any internal parts.
• Environmental and power supply conditions must conform to the val-
ues specied on the product rating labels.
• The product is designed exclusively to humidify rooms either directly or
through distribution systems (ducts).
• Only qualied personnel who are aware of the necessary precautions
and able to perform the required operations correctly may install, oper-
ate or carry out technical service on the product.
• Only water with the characteristics indicated in this manual must be
used to produce the spray.
• All operations on the product must be carried out according to the
instructions provided in this manual and on the labels applied to the
product. Any uses or modications that are not authorised by the manu-
facturer are considered improper. CAREL declines all liability for any such
unauthorised use.
• Do not attempt to open the appliance in any way other than described
in the manual.
• Observe the standards in force in the place where the humidier is installed.
• The appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of expe-
rience and knowledge, unless they have been given supervision or in-
struction concerning use of the appliance by a person responsible for
their safety.
• Do not install and use the product near objects that may be damaged
when in contact with water (or condensate). CAREL declines all liability
for direct or indirect damage following water leaks from the humidier.
• Do not use corrosive chemicals, solvents or aggressive detergents to
clean the inside and outside parts of the humidier, unless specically
indicated in the user manual.
• Do not drop, hit or shake the humidier, as the inside parts and the lin-
ings may be irreparably damaged,
CAREL adopts a policy of continual development. Consequently, CAREL
reserves the right to make changes and improvements to any product
described in this document without prior warning. The technical speci-
cations shown in the manual may be changed without prior warning.
The liability of CAREL in relation to its products is specied in the CAREL
general contract conditions, published on the website www.carel.com
and/or by specic agreements with customers; specically, to the extent
where allowed by applicable legislation, in no case will CAREL, its employ-
ees or subsidiaries/aliates be liable for any lost earnings or sales, losses of
data and information, costs of replacement goods or services, damage to
things or people, downtime or any direct, indirect, incidental, actual, puni-
tive, exemplary, special or consequential damage of any kind whatsoever,
whether contractual, extra-contractual or due to negligence, or any other
liabilities deriving from the installation or use of the product, even if CAREL
or its subsidiaries/aliates are warned of the possibility of such damage.
DISPOSAL
Fig. 1 Fig. 2
PLEASE READ AND KEEP.
WITH REFERENCE TO EUROPEAN UNION DIRECTIVE 2012/19/EU IS
SUED ON 4 JULY 2012 AND RELATED NATIONAL LEGISLATION, PLEASE
NOTE THAT:
• Waste Electrical and Electronic Equipment (WEEE) cannot be disposed
of as municipal waste but must be collected separately so as to allow
subsequent recycling, treatment or disposal, as required by law;
• users are required to take Electrical and Electronic Equipment (EEE) at
end-of-life, complete with all essential components, to the WEEE collec-
tion centres identied by local authorities. The directive also provides
for the possibility to return the equipment to the distributor or retailer
at end-of-life if purchasing equivalent new equipment, on a one-to-one
basis, or one-to-zero for equipment less than 25 cm on their longest
side;
• the equipment may contain hazardous substances: the improper use or
incorrect disposal of such may have negative eects on human health
and on the environment;
• the symbol (crossed-out wheeled bin, see Figure 1), if shown on the
product or on the packaging, indicates that the equipment must be dis-
posed of separately at end-of-life;
• if at end-of-life the EEE contains a battery (Figure 2), this must be re-
moved following the instructions provided in the user manual before
disposing of the equipment. Used batteries must be taken to appropri-
ate waste collection centres as required by local regulations;
• in the event of illegal disposal of electrical and electronic waste, the
penalties are specied by local waste disposal legislation.
Warranty on materials: 2 years (from production date, excluding consum-
ables).
Approval: the quality and safety of CAREL products are guaranteed by the
ISO 9001 certied design and production system, as well as the
, and marks.
Avvertenze

4
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022

5
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
Index
1. PURPOSE OF THE MANUAL ..................................... 7
2. HOW TO READ THE MANUAL .................................. 7
3. General safety information and instructions ...... 8
3.1 Intended use........................................................................................................8
3.2 General safety instructions .........................................................................8
3.3 Personal protective equipment...............................................................9
4. Introduction............................................................. 10
4.1 Components..................................................................................................... 10
4.2 Air handling unit (AHU)..............................................................................10
4.3 Pumping station............................................................................................. 13
4.4 Opening the packaging ............................................................................ 13
4.5 Positioning.........................................................................................................14
4.6 Opening...............................................................................................................14
4.7 Identication.....................................................................................................15
4.8 Structure..............................................................................................................15
5. Installation notes .................................................... 16
5.1 Network connection....................................................................................16
5.2 Distribution system ......................................................................................17
6. Installation ............................................................... 18
6.1 Electrical connections.................................................................................18
6.2 Control connections....................................................................................19
6.3 Solenoid valve connections.................................................................... 22
6.4 Inputs and outputs.......................................................................................24
7. Technical data.......................................................... 25
7.1 Technical specications............................................................................. 25
7.2 Terminal tightening torque.....................................................................25
7.3 Fuse chart ...........................................................................................................25
8. Checklist ................................................................... 26
9. ANNEXES .................................................................. 27
Annex A: Wiring diagrams...................................................................................27
Annex B: Accessories and spare parts kits.................................................28
Indice


7
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
This manual contains instructions for the installation, use and maintenance of the models of humiFog unit manufactured by:
CAREL INDUSTRIES
Via dell’Industria, 11, 35020
Brugine - Padova (Italy)
Tel. (+39) 049.9716611 - Fax (+39) 049.9716600
e-mail: carel@carel.com - www.carel.com
1. PURPOSE OF THE MANUAL
The manual is divided into chapters and paragraphs. Each paragraph is a sub-level of the corresponding chapter. References to
headings or paragraphs are indicated by the abbreviation“Chap.” or “Par.”followed by the number.
Example:“Chap. 2”or “Par. 2.1”.
The gures in this manual are numbered consecutively according to the corresponding chapter, for example Figure 1.c is the
third gure in chapter one. References to the gures are indicated by the abbreviation “Fig.” followed by the number. Example:
“Fig. 1.c”.
The components shown in the gures are marked with numbers. A reference to component 1 in gure 2, chapter 3 will be indi-
cated as follows:“See 1 - Fig. 3.b”or simply “(1 - Fig. 3.b)”.
IMPORTANT
The gures shown in this manual are purely indicative. The actual components may vary from those illustrated. If in doubt,
contact an authorised service centre.
In addition to the instructions for installation, use and maintenance, this manual contains safety information that requires special
attention. This information is denoted by the symbols described below:
DANGER
Failure to comply with this warning will lead to an imminently hazardous situation which, if not avoided, will result in death
or serious injury.
WARNING
Failure to comply with this warning will lead to potentially hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION
Failure to comply with this warning will lead to a potentially hazardous situation which, if not avoided, may result in minor
or moderate injury.
IMPORTANT
Failure to comply with this warning will lead to a potentially hazardous situation which, if not avoided, could cause minor
damage to the unit.
Notice: provides supplementary information to the above safety instructions.
2. HOW TO READ THE MANUAL

8
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
3. GENERAL SAFETY INFORMATION AND
INSTRUCTIONS
3.1 Intended use
humiFog is a high pressure adiabatic humication system for humidity control and evaporative cooling. It can be used both to
condition the air in an AHU (air handling unit), and for direct humidication or cooling in rooms.
IMPORTANT: the product must only be used for its intended purpose, as envisaged by CAREL. CAREL declines all
liability, both contractual and extra-contractual, for any damage to people, animals or things due to installation, control or main-
tenance errors or improper use.
3.2 General safety instructions
When using products that require electricity and a source of high-pressure water, a number of fundamental safety rules need to
be observed, including:
• The appliance must not be used by children or people with reduced physical, sensory or mental capabilities, or people lacking
the necessary experience or knowledge or who are not familiar with the operating instructions.
• People without specic qualications and skills must not use the pumping station.
• People must not come into contact with the appliance if barefoot or any of the parts of their body are wet.
• No technical or cleaning operations are allowed until the appliance has been isolated from the power supply by moving the
main system switch to“o”and the main switch on the appliance to “OFF”.
• The safety and control devices must never be adjusted without the manufacturer’s authorisation.
• The pictograms and labels axed to the pumping station must not be removed. These must remain legible and the corre-
sponding instructions must be observed at all times. If they are no longer legible, they must be replaced with equivalent
pictograms or safety labels.
• The water connections must never be loosened during operation. Improperly secured pipes or hoses may detach without
warning, resulting in injury.
• Do not block or obstruct the water drain.
• Do not pull, disconnect or twist the electrical cables coming out of the appliance, even when this is disconnected from the
mains power supply.
• Never expose the appliance to the elements. It is designed for indoor use only.
• Do not dispose of the packaging material in the environment and keep it out of the reach of children, as it is a potential hazard.
It must be disposed of in accordance with current legislation.
• Do not activate the pumping station without it being adequately supplied with water.
• The customer is responsible for ensuring that the humidication system complies with local guidelines on occupational
health and safety and prevention of bacterial proliferation.
• In the event of water leaks, disconnect the pumping station from the power supply, shut o the water supply and promptly
notify CAREL’s Technical Service or other professionally qualied personnel.
• Periodically check that the water circuit operating pressure is above 1 bar and below than the maximum limit specied for the
appliance. Otherwise, contact CAREL’s Technical Service or other professionally qualied personnel.
• If the pumping station is not used for an extended period, the following operations need to be carried out:
– Turn the main switch on the appliance to“OFF”
– Turn the main system switch to “o”
– Close the system water taps
– Empty the system if there is the risk of freezing.
• This instruction manual is an integral part of the appliance and consequently must be kept with care and must ALWAYS
accompany the pumping station even if it is transferred to another owner or installed in another system. If damaged or loss,
another copy can be ordered from CAREL’s local Technical Service.
• Read this instruction manual read carefully to ensure proper and safe installation, operation and maintenance of the appli-
ance. The owner must be adequately informed and trained on how to use the appliance. Users must be familiar with all the
information needed for safe operation of the system.
• Before connecting the pumping station to the water and power supply, it can be exposed to temperatures between -10°C and
40°C. Once commissioned, it can be exposed to temperatures between 5°C and 40°C.
• Periodically check that the water drains are not blocked.

9
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
3.3 Personal protective equipment
DANGER: strictly follow the instructions provided in the manual.
Personal protective equipment (PPE) means any equipment intended to be worn and kept by workers in order to protect them-
selves against one or more risks likely to threaten their health or safety during work, as well as any device or accessory intended
for this purpose.
All PPE described in this manual are intended to protect personnel from health and safety risks.
Below is a list of personal protective equipment to be used and the procedures to be adopted to protect workers from the re-
sidual risks that exist during the various phases of the humidier’s life cycle.
GLOVES TO PROTECT AGAINST PHYSICAL ELEMENTS:
these must protect the person's hands against cuts, abrasion and heat.
NON-SLIP SAFETY FOOTWEAR: these must prevent falls on slippery surfaces and protect the person's feet from
impact, crushing and puncture wounds.
SAFETY HARD HAT: this must protect the person's head against bumps or material accidentally falling from above.
SAFETY GLASSES: these must protect the person's eyes from all risks due to contact with hazardous substances or
materials.
PROTECTIVE MASK: this protects the wearer’s respiratory tract against all risks associated with the inhalation of
dangerous substances.
PROTECTIVE CLOTHING: this guarantees the body adequate protection against thermal and chemical agents.
EARMUFFS: these must attenuate noises that would otherwise be harmful to the person's hearing.
INSTRUCTION MANUAL: this must be referred to whenever necessary, in order to avoid adopting unsafe proce-
dures.

10
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
4. INTRODUCTION
4.1 Components
• Pumping station, comprising the system pump and the electrical panel;
• zone electrical panel;
• distribution system and droplet separator for humidication in air handling units;
• blower unit for in-room humidication.
The range includes the pumping station in the humiFog multizone and humiFog multizone Touch versions, which dier in terms
of the components supplied, the accessories available and the dierent system conguration modes.
The system can comprise:
• single zone: 1 pumping station with 1 atomisation system;
• multizone: 1 pumping station that supplies up to 12 independent atomisation systems.
Notice:
• to connect the pumping station to the blowers, use the water circuit assemblies and electrical panels supplied separately by
Carel (see the list of accessories);
• to facilitate commissioning, plates already equipped with electrical connectors are available for simply and quickly connecting
the electrical panels to the solenoid valves on the distribution manifolds.
The following diagrams provide an overview of the systems that can be implemented.
4.2 Air handling unit (AHU)
Internal rack valves
1
10
6
7
8
9
3
5
4
2
Fig. 4.a
Ref. Description
1 Pumping station
2 Electrical cables
3 Distribution manifolds
4 Zone-electrical panel
5 Droplet separator
6 Drain trap
7 Open funnel drain (after droplet separator)
8 Open funnel drain (before droplet separator)
9 High pressure water line
10 Line drain valve
Tab. 4.a

11
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
Multizone
2
1
3
3
Fig. 4.b
Ref. Description
1 Pumping station
2 Ethernet cable
3 Zone electrical panel
Tab. 4.b
Notice: for the Ethernet connection from the pumping station to the zone electrical panels, see“Installation notes”.

12
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
4.2.1 Room
Single zone
Direct Box
Direct Box
1
5
3
Sensore
di umidità
Quadro
elettrico
di zona
4
2
Fig. 4.c
Multizone
Direct Box
Direct Box
1
2
6
5
Direct Box
Direct Box
Quadro
elettrico
di zona
Zona 1 Zona 2
Sensore
di umidità 1
Sensore
di umidità 2
3
4
Alimentazione
Fig. 4.d
Ref. Description
1 Pumping station
2 Directbox hydraulic
3 Blower unit
4 Zone electrical panel
5 Directbox electric
6 Ethernet cable
Tab. 4.c
Sensore
di umidità
Sensore
di umidità 1
Sensore
di umidità 2
Alimentazione
Zona 1 Zona 2
Quadro
elettrico
di zona
Quadro
elettrico
di zona

13
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
4.3 Pumping station
4.3.1 Part numbers
UA000SD500 | UA000S2500 | UA000SU500
U A **** * 5 0
Range Model Power supply and approval Revision no. Customisation
UA: humiFog 000S: humiFog zone
panel
D: 230 Vac 50/60 Hz, 1~, CE
2: 230 Vac 50/60 Hz, 1~, UL
U: 208 Vac 50/60 Hz, 1~, UL
5: Fifth revision 00: Carel
Tab. 4.d
Notice: for CE in accordance with the requirements of EN60204-1; EN61000-6-2-; EN61000-6-4 in the most recent editions.
For UL approved versions
in accordance with UL 508A requirements.
4.3.2 Dimensions - mm (in)
433
(17)
380
(15)
(R0.19)
R5
1
5
5
(
6.
1
)
1
0
,
5
(
0
.4
)
4
91
(
1
9.
3
3
)
(
14
.
6
)
3
7
2
(
16
.
5
)
4
2
0
Fig. 4.e
4.3.3 Weight - kg (lb)
Zone panel Weight with/without packaging [kg] (lb)
UA000SD500/UA000S2500/UA000SU500 22.2 / 19.6 (48.9 / 43.2)
Tab. 4.e
4.4 Opening the packaging
• check that the packaging is intact upon delivery and notify the carrier immediately, in writing, of any damage that may be due
to improper or negligent transport;
• move the zone panel to the installation site before removing the packaging.
• place it near the position where it will be installed;
• remove the packaging.
4.4.1 Material supplied
After opening the packaging and removing the front panel, check that the following are present:
• 1 cable gland (A) for the power supply cable;
• 6 cable glands (B) for the electrical cables coming out of the pumping station;
• installation manual
A B
Fig. 4.f

14
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
4.5 Positioning
Install the zone panel indoors, in order to guarantee:
• opening of the front panel;
• easy access to the internal parts;
• power and control electrical connections.
min
500 mm
(20 in)
min
500 mm
(20 in)
min
500 mm
(20 in)
min
500 mm
(20 in)
min
1000 mm (39 in)
Fig. 4.g
Notice:
• check with a spirit level that the unit is placed on a horizontal surface;
• if the unit is positioned up against a wall, do not place any objects on it that block the cooling air.
4.6 Opening
Open the panel by unscrewing the side screws (Figure 4i) with a Phillips-head screwdriver, so as to access the electrical panel.
Pannello Frontale
Viti lateraliViti laterali
Fig. 4.h
min
min
min
min
min
Front panel
Side screwsSide screws

15
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
4.7 Identication
The zone panel can be identied by the rating plate located inside the electrical panel.
TYPE
Pnom kW
Qnom kW
G20(nat.gas)
G25(nat.gas)
Vac
Hz
PH
kW
kg / h
IP
NOx cl
Date
CODE
IP
Date
Part No.
Serial No.
Rev.
MADE IN ...
CAREL INDUSTRIES
Via dell'Industria, 11, 35020 Brugine
(Padova) Italy
Fig. 4.i
IMPORTANT: tampering, removal or absence of the rating plate or anything else that does not allow certain identi-
cation of the product will make any installation or maintenance operations dicult and will void the manufacturer’s warranty.
4.8 Structure
3
2
1
6
4
5
7
8
9
Fig. 4.j
Ref. Description
1 Electronic controller
2 Fuses
3Connector T4 to T8
4 Transformer A
5 Transformer B
6 Fuses
7 On/O switch
8 Ethernet connectors
9 Connector for external terminal
Tab. 4.f

16
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
5. INSTALLATION NOTES
5.1 Network connection
See the technical data table for the specications of the connection cables.
5.1.1 Zone panel connection
The connection is made using an Ethernet cable from the pumping station to the zone panels, as shown in the gure.
IMPORTANT: the maximum allowed length of an Ethernet connection between two devices is 100 m (for longer dis-
tances, use switch P/N KITSE08000).
...
Quadro
di zona
1
Quadro
di zona
2
Quadro
di zona
12
NOL
Zona 1 Zona 2 Zona 12
NOV NOV NOV
Fig. 5.a
Ref. Description
NOL Normally open line drain valve
NOV Normally open vent valve
Tab. 5.a
5.1.2 Supervisor connection
The connection to the supervisor network can be made in two ways:
• between the Ethernet port on the pumping station and the supervisor network
• via RS485 serial link between the BMS2 port on the pumping station controller and the supervisor network. In the latter case,
the communication settings need to be changed when commissioning the system.
28
17
J25 BMS2
J25 BMS2
Tx/Rx
Tx/Rx
GND
GND
17
J25 BMS2
Tx/Rx GND
Fig. 5.b
Zone 1 Zone 2
Zone 1
panel
Zone 2
panel
Zone 12
panel
Zone 12

17
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
5.2 Distribution system
5.2.1 Atomisation system solenoid valve management
To manage the distribution system, the zone panel controls the following solenoid valves:
• distribution manifold ll/drain (normally closed NC / normally open NO, respectively). See the following diagrams;
• vent, used to facilitate the emptying of the distribution system (NOV, normally open);
Case 1: installation in an AHU (air handling unit)
• The water is atomised through a series of distribution manifolds (racks), equipped with nozzles.
• One or more manifolds can be grouped together to form a “step”. All of the manifolds in the same step are activated simulta-
neously to start/stop atomisation.
• Each rack can be managed by a zone panel. There are a maximum of 6 steps per rack.
• Each step comprises a maximum number of solenoid valves, as shown in the table; however the total number of powered
solenoid valves cannot exceed 22 (including the vent and line drain valves).
No. of steps Maximum no. of solenoid valves
1 5 NC + 5 NO (*)
2 3 NC + 3 NO
3 2 NC + 2 NO
4 4 NC + 4 NO
5 1 NC + 1 NO
6 1 NC + 1 NO
Tab. 5.b
(*) NC1a, NC1b, ..., NC1e +NO1a, NO1b, ..., NO1e
Case 2: installation of the blowers in the room
The water is atomised through the nozzles installed on blowers or on racks in the room. These can be grouped together to form
steps, in the same way as for the rack manifolds.
5.2.2 Drain valve management (NOL)
The zone panel manages and controls the line drain valve (NOL, normally open).
Notice: the line drain valve must be tted at the lowest point in the water circuit and wired to the nearest electrical pan-
el (pumping station or zone panel), so that when opened, the entire system is emptied.
Case 1: Pumping station located below the distribution manifolds
Connect the drain valve near the zone panel that will control its opening.
Case 2: Pumping station located above the distribution manifolds, placed at dierent heights.
The drain valve must be connected near to the lowest distribution manifold.
Notice: the control signal for the zone 12 drain valve is output J12 NO3 on the zone electrical panel controller. See the
corresponding manual.
Case 3: Distribution manifolds located both above and below the pumping station
Connect multiple drain valves at the lowest points in the water circuit.
...
Quadro
di zona
1
Quadro
di zona
11
Quadro
di zona
10
NOV
NOL
NOL
NOV NOV
Zona 1 Zona 2 Zona 11
Zona 12
Fig. 5.c
Panel
zone 11
Panel
zone
1
Panel
zone
10
Zone 1 Zone 2
Zone 12
Zone 11
Panel
zone
10

18
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
6. INSTALLATION
6.1 Electrical connections
Before making the connections, make sure that the unit is disconnected from the power supply: turn the main system switch
and pumping station switch to OFF.
Install the cable glands on the left and right side of the electrical panel for the electrical cables to pass through.
6.1.1 Electrical panel
2
3
4
1
7
6
5
Fig. 6.a
Ref. Description
1 Electronic controller
2 Fuses
3Connector T4 to T8
4 Transformer A
5 Transformer B
6 Power terminal
7 Transformer fuses
Tab. 6.a

19
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
6.1.2 Power supply
Notice: recommended cable size: 2.5 mm² (AWG 13).
Check that the unit’s power supply voltage corresponds to the rated data.
The connection must be made in compliance with national and local regulations in force.
IMPORTANT:
• cables must comply with local regulations;
• install a switch upstream of the pumping station to isolate it from the power supply line;
• provide a TT earth system, with earth fault current protection => 30 mA.
Alimentazione
monofase
PE
L
N
Fig. 6.b
6.2 Control connections
The type of control is selected on the user interface. See the humidication system commissioning manual.
Notice: for all control connections:
• recommended cable size: 0.3 - 0.5 mm² (AWG 22/20) up to 30 m
• recommended cable size: 0.8 - 1.3 mm2 (AWG 18/16) > 30 m
6.2.1 Enable zone production
Notice: the zone panel is supplied with the ID6 - G0A contacts jumpered. To enable the rack remotely, remove the jumper
and connect a voltage-free contact.
J5
GOAGOA
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
Fig. 6.c
Connector Terminals
J5 ID6-G0A
Tab. 6.b
6.2.2 Enable from air ow switch (FLUX): Air ow switch
Enable from air ow switch input.
Notice: the zone panel is supplied with the ID7 - GND terminals jumpered.
J5
GOAGOA
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
Fig. 6.d
Connector Terminals Device
J5 ID7 - GOA ow switch (contact open/closed = production
disabled/enabled)
Tab. 6.c
Single-phase
power supply

20
ENG
humiFog +0300114EN rel. 1.0 - 15.03.2022
6.2.3 On/o control signal
Notice: contact type: voltage-free.
A) ON/OFF
J6
U6
U7
U8
GND
Fig. 6.e
Connector Terminals
J6 GND - U6
Tab. 6.d
B) ON / OFF AND HUMIDITY/TEMPERATURE LIMIT PROBE
Inputs allowed for limit probe: 0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA; NTC
J6
U6
U7
U8
GND
J3
U4
GND
U5
GND
J2
U1
U2
U3
GND
Vdc
OUT H/T
M
+ (G)
Fig. 6.f
Connector Terminals Device
J6 U6 - GND Humidistat/thermostat
J6
U7 - GND -
Vdc
Active humidity/
temperature probe
U7 - GND NTC probe
Tab. 6.e
6.2.4 Modulating control signal
With a modulating control signal, depending on the type of controller, the following can be connected to the terminals:
• external controller
• external controller and humidity/temperature limit probe
• main humidity/temperature probe
• main humidity/temperature probe and humidity/temperature limit probe
• dual main humidity/temperature probe
• triple main humidity/temperature probe
• * rack temperature limit probe (can be used with some of the previous control congurations)
IMPORTANT: use shielded cables. The cables must not be placed near the power supply cables or contactors, to avoid
electromagnetic disturbance.
A) Modulating control with external controller
Possible inputs: 0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA.
J6
U6
U7
U8
GND
REF
OUT
Fig. 6.g
Connector Terminals Device
J6 U6 - GND Signal from external controller
Tab. 6.f
Other manuals for humiFog
1
Table of contents
Other Carel Control System manuals

Carel
Carel FLSTDMAHUE User manual

Carel
Carel DPWL Series User manual

Carel
Carel IROPZ48500 User manual

Carel
Carel Heez Manual

Carel
Carel pAD ADP 30 Series User manual

Carel
Carel TH TUNE User manual

Carel
Carel WM00E 00 Series User manual

Carel
Carel infrared IR32CE Series User manual

Carel
Carel CY0S1A0000 User manual

Carel
Carel MasterCella Split User manual