+050000164 - rel 1.2 - 8 May 2012
compactSteam
: Cylinder replacement instructions /
Cylinder replacement instructions
The humidifier and the cylinder contain live electrical components and very hot
surfaces. All service and maintenance operations must be carried out by qualified
personnel who are aware of the necessary precautions. Before performing any
operations on the cylinder, make sure that the humidifier is disconnected from the
power supply. Remove the cylinder from the humidifier only after having drained
it completely. Check that the model number of the new cylinder corresponds
with the unit you are servicing.
Conductivity
Conductivity is a measure of the amount of minerals in the water and the cylinders
are designed to be used with a particular conductivity level. The cylinder should be
matched to the proper conductivity range in the below table to allow the cylinder
to operate to its maximum number of hours.
Steam cylinder reference chart
cylinder conductivity compactSteam
CY0S1A0000 350-1250 μS/cm CH*01*1*** (1.6 kg/h – 3.5 lbs/hr 110 Vac 1-phase)
CY0S1A0000 100-350 μS/cm CH*01*1*** (1.6 kg/h – 3.5 lbs/hr 110 Vac 1-phase)
CY0S1A0000 350-1250 μS/cm CH*02*1*** (2.5 kg/h – 5.5 lbs/hr 110 Vac 1-phase)
CY0S1A0000 100-350 μS/cm CH*02*1*** (2.5 kg/h – 5.5 lbs/hr 110 Vac 1-phase)
CY0S1B0000 350-1250 μS/cm CH*01*2*** (1.6 kg/h – 3.5 lbs/hr 230 Vac 1-phase)
CY0S1C0000 100-350 μS/cm CH*01*2*** (1.6 kg/h – 3.5 lbs/hr 230 Vac 1-phase)
CY0S1B0000 350-1250 μS/cm CH*03*2*** (3.2 kg/h – 7 lbs/hr 230 Vac 1-phase)
CY0S1C0000 100-350 μS/cm CH*03*2*** (3.2 kg/h – 7 lbs/hr 230 Vac 1-phase)
CY0S1C0000 350-1250 μS/cm CH*05*2*** (5.4 kg/h – 12 lbs/hr 230 Vac 1-phase)
CY0S1D0000 100-350 μS/cm CH*05*2*** (5.4 kg/h – 12 lbs/hr 230 Vac1-phase)
Measuring Supply Water Conductivity
Water sample should be taken from the humidifier supply connection. The water
sample can be tested on site by available portable cup, or dip style testers. Tester
Manufactures: Hanna instruments, Oakton Instruments, Myron L. Company, Mettler-
Toledo, Denver Instrument Company, and Electro-Chemical Devices, Inc.
REMOVING AND CLEANING COMPONENTS
WARNING: The cylinder may reach high temperatures. Let it cool down before
touching it or wear protective gloves.
1) To remove the Cylinder
a) Remove the cover
b) Completely drain the cylinder, holding the“drain”button until the cylinder
is empty
c) Turn the humidifier off and disconnect the main power supply
2) A: Duct injection units
a) Remove the steam hose from the cylinder
b) Disconnect the wiring from the top of the cylinder by loosening and
removing grey cap and top nut.
Lift off ring terminals from the top of the cylinder.
c) Lift up the cylinder support bracket and lift the cylinder out of the unit,
and into a bucket to catch residual water from the cylinder.
2) B: Built-in fan units
a) Unscrew the two bolts on the built-in fan
b) Disconnect the wiring from the top of the cylinder by loosening and
removing grey cap and top nut.
Lift off ring terminals from the top of the cylinder.
c) Disconnect the blower from the cylinder and lift the cylinder out of the
unit, and put it into a bucket to catch residual water from the cylinder.
3) Cleaning the fill, drain tempering valve, drain pump or drain valve, and
drain pan;
a) With power disconnected, turn water supply off and disconnect water
supply hose
b) Remove valves and drain pump/valve by removing screws; check the
condition of inlet filter of the valves
c) Clean with solution of vinegar or diluted acetic acid and a soft brush
d) Rinse parts with fresh water
e) Replace any components that show excessive wear or could not be
completely cleaned. Ensure that the washer and spring are properly
reassembled in the drain valves.
REASSEMBLYING AND RESTARTING
The following operations shall be performed with a COLD cylinder.
1) Replace any components that were removed for servicing.
2) To install the Cylinder:
a) Install the new cylinder in the humidifier, performing the same
operations in the reverse order.
L’umidificatore e il cilindro contengono componenti elettrici sotto tensione e
superfici molto calde. Le operazioni di assistenza e manutenzione devono essere
eseguite solamente da personale qualificato, che sia a conoscenza delle precauzioni
necessarie. Prima di effettuare qualsiasi operazione sul cilindro, assicurarsi che
l’umidificatore sia scollegato dall’alimentazione elettrica. Rimuovere il cilindro
dall’umidificatore solo dopo averlo svuotato completamente dell’acqua contenuta.
Vericare che il numero del modello del nuovo cilindro corrisponda
all’apparecchio sul quale si sta eseguendo il servizio di assistenza.
Conducibilità
La conducibilità è una misura della quantità di minerali nell’acqua e i cilindri sono stati
progettati per essere usati con un livello particolare di conducibilità. Perché possa
funzionare per il numero massimo di ore possibile, il cilindro deve essere abbinato
all’intervallo di conducibilità adeguato riportato in tab.
Tabella di riferimento cilindri vapore
cilindro conducibilità compactSteam
CY0S1A0000 350-1250 μS/cm CH*01*1*** (1.6 kg/h – 3.5 lbs/hr 110 Vac 1-fase
CY0S1A0000 100-350 μS/cm CH*01*1*** (1.6 kg/h – 3.5 lbs/hr 110 Vac 1-fase)
CY0S1A0000 350-1250 μS/cm CH*02*1*** (2.5 kg/h – 5.5 lbs/hr 110 Vac 1-fase)
CY0S1A0000 100-350 μS/cm CH*02*1*** (2.5 kg/h – 5.5 lbs/hr 110 Vac 1-fase)
CY0S1B0000 350-1250 μS/cm CH*01*2*** (1.6 kg/h – 3.5 lbs/hr 230 Vac 1-fase)
CY0S1C0000 100-350 μS/cm CH*01*2*** (1.6 kg/h – 3.5 lbs/hr 230 Vac 1-fase)
CY0S1B0000 350-1250 μS/cm CH*03*2*** (3.2 kg/h – 7 lbs/hr 230 Vac 1-fase)
CY0S1C0000 100-350 μS/cm CH*03*2*** (3.2 kg/h – 7 lbs/hr 230 Vac 1-fase)
CY0S1C0000 350-1250 μS/cm CH*05*2*** (5.4 kg/h – 12 lbs/hr 230 Vac 1-phase)
CY0S1D0000 100-350 μS/cm CH*05*2*** (5.4 kg/h – 12 lbs/hr 230 Vac1-phase)
Misurazione della conducibilità dell’acqua di alimentazione
Prendere dei campioni di acqua di alimentazione dell’umidificatore per poterli
testare in loco tramite un tester portatile. Produttori dei tester: Hanna Instruments,
Oakton Instruments, Myron L. Company, Mettler-Toledo, Denver Instrument
Company ed Electro-Chemical Devices, Inc.
RIMOZIONE E PULIZIA DEI COMPONENTI
AVVERTENZA: il cilindro potrebbe essere caldo. Lasciarlo raffreddare prima di
toccarlo od utilizzare guanti protettivi.
1) Per rimuovere il cilindro
a) Togliere il frontale dell’unità
b) Eliminare completamente l’acqua contenuta all’interno del cilindro
tenendo premuto l’apposito pulsante (‘drain’) finché il cilindro non è vuoto
c) Spegnere l’umidificatore e scollegarlo dall’alimentazione elettrica
2) A: Unità per condotta:
a) Rimuovere il tubo del vapore dal cilindro
b) Scollegare i cavi nella parte superiore del cilindro togliendo i cappucci
grigi e svitando il dado superiore. Rimuovere il capocorda ad anello del
cavo dal terminale del cilindro
c) Sollevare la staffa di supporto del cilindro, estrarre quest’ultimo
dall’apparecchio e deporlo in un secchio per raccogliere l’acqua residua
contenuta al suo interno
2) B: Unità con ventilatore a bordo
a) Svitare i due bulloni sul ventilatore
b) Scollegare i cavi nella parte superiore del cilindro togliendo i cappucci
grigi e svitando il dado superiore. Rimuovere il capocorda ad anello del
cavo dal terminale del cilindro
c) Scollegare il ventilatore dal cilindro ed estrarre quest’ultimo dall’apparecchio
sollevandolo e deponendolo in un secchio per raccogliere l’acqua residua
contenuta al suo interno
3) Pulizia della valvola di alimentazione, miscelazione, la pompa di drenaggio o
la valvola di drenaggio
a) Con l’alimentazione elettrica scollegata, chiudere l’alimentazione
dell’acqua e scollegare il relativo tubo
b) Rimuovere le valvole e la pompa/valvola di drenaggio togliendo le
apposite viti; verificare la condizione del filtro di ingresso delle valvole
c) Pulire con una soluzione di aceto o acido acetico diluito utilizzando un
pennello a setole morbide
d) Sciacquare le parti con acqua fresca
e) Sostituire eventuali componenti che mostrano segni di eccessiva usura
o che non possono essere puliti completamente. Assicurarsi che la
guarnizione sia montata adeguatamente nelle valvole di drenaggio
RIASSEMBLAGGIO E RIAVVIO
Le seguenti operazioni devono essere eseguite con il cilindro a temperatura
ambiente.
1) Sostituire eventuali componenti diffettosi
2) Per installare il cilindro:
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: [email protected] - www.carel.com +050000164 - rel 1.2 - 8 May 2012
b) Connect the wiring to the top of the cylinder by removing top nut.
Replace ring terminals to the top of the cylinder.
Replace top nut, tighten according to label and reposition grey cap.
c) Replace the steam hose and adapter to the cylinder.
Warning: ensure that the components, hoses and cylinder are replaced with
correct O-rings, and gaskets. Open water supply and check for leaks. Ensure
that the steam hose clamp is snug, but not over-tightened.
d) Reconnect the power supply.
3) Start with the new cylinder:
a) Switch the unit off. While pressing and holding both the
“reset”and “drain”buttons, switch the unit on. When the wrench
blinks release the two buttons.
b) Press and hold “reset” until the display shows 04
Warning: DO NOT confirm any value higher than 04. If 05 or higher is
displayed, press “reset”until the display goes back to the normal operating
mode and restart from step a).
c) Press “drain” (minimum 1 second). The cleaning cycle starts. During the
cylinder cleaning cycle, the electrodes are powered and the cylinder is filled
with water until one of the following conditions occurs:
• the level of the water reaches the maximum level sensor;
• the phase current is equal to 20A.
The cylinder will empty. Carel recommends two cleaning cycles.
Go back and repeat from step a). After the second cleaning cycle has
ended, the humidifier will start normally.
4) Resetting the cylinder hour counter:
a) Switch unit off. While pressing and holding both the “reset”
and“drain”buttons, switch the unit on. When the wrench blinks
release the two buttons.
b) Press and hold “reset” until the display shows 03
c) Press “drain” (minimum 1 second) to confirm. The hour counter will be
reset once the unit goes back to normal operation.
5) Final Check:
a) Turn unit off and disconnect power supply.
b) Recheck for water leaks, and replace unit cover.
c) Reconnect power and turn unit on.
a) Installare il nuovo cilindro nell’umidificatore, eseguendo a ritroso le stesse
operazioni effettuate precedentemente.
b) Collegare i cavi di potenza agli elettrodi del cilindro rimuovendo il dado
superiore e poi serrandolo secondo l’etichetta gialla e riposizionando i
cappucci grigi
c) Ricollegare il ventilatore e/o il tubo del vapore al cilindro
Avvertenza: assicurarsi che i componenti, i tubi ed il cilindro siano
riposizionati con gli O-ring e le guarnizioni corrette. Aprire l’alimentazione
dell’acqua e verificare che non vi siano perdite. Accertarsi che la fascetta
stringi tubo del vapore sia stretto ma non eccessivamente serrato.
d) Ricollegare l’alimentazione elettrica
3) Avvio con il nuovo cilindro:
a) Spegnere l’apparecchio. Mentre si tengono premuti i due
pulsanti ‘reset’ e ‘drain’, accendere l’apparecchio. Quando il
simbolo della chiave inglese lampeggia, lasciare i due pulsanti.
b) Tenere premuto il pulsante‘reset’ finché sul display non compare la cifra 04.
Avvertenza: NON confermare nessun valore superiore a 04. Se viene
visualizzata una cifra pari o superiore a 05, premere il tasto ‘reset’ finché il
display non torna alla normale modalità operativo, e ripartire dal punto a).
c) Premere il tasto ‘drain’ (minimo 1 secondo). Il ciclo di pulizia si avvia. In
questa fase gli elettrodi vengono alimentati e il cilindro si riempie di acqua
finché non si verifica una delle seguenti condizioni:
• il livello dell’acqua raggiunge il sensore di riempimento massimo;
• la corrente di fase è pari a 20A.
Il cilindro si svuota. Carel consiglia due cicli di pulizia.
Tornare indietro e riprendere dal punto a). Una volta terminato il secondo
ciclo di pulizia, l’umidificatore si riavvia normalmente.
4) Azzeramento del contatore orario del cilindro:
a) Spegnere l’apparecchio. Mentre si tengono premuti i pulsanti
‘reset’ e ‘drain’, accendere l’apparecchio. Quando chiave inglese
lampeggia, lasciare i due pulsanti.
b) Tenere premuto il tasto‘reset’ finché il display non mostra la cifra 03
c) Premere il tasto‘drain’(minimo 1s) per confermare. Il contatore orario verrà
azzerato una volta che l’apparecchio tornerà a funzionare normalmente.
5) Controllo finale:
a) Spegnere l’apparecchio e scollegare l’alimentazione elettrica.
b) Verificare nuovamente che non ci siano perdite d’acqua e riposizionare il
coperchio dell’apparecchio.
c) Ricollegare l’alimentazione elettrica e riaccendere l’apparecchio.
1
2
3
4
Key
/ Legenda:
1)
Grey cap
/ Tappo grigio
2)
Top nut
/ Dado superiore
3)
Power terminal
/ Cavo di
alimentazione
4)
Retainer
/ Ferma dado
CAREL si riserva la possibilità di apportare modifiche o cambiamenti
ai propri prodotti senza alcun preavviso.
Smaltimento del prodotto: L’apparecchiatura (o il
prodotto) deve essere oggetto di raccolta separata in
conformità alle vigenti normative locali in materia di
smaltimento.
L’installazione del prodotto deve obbligatoriamente
comprendere la connessione di messa a terra, usando
l’apposito morsetto giallo-verde in morsettiera. Non
utilizzare il neutro come connessione a terra.
CAREL reserves the right to modify the features of its products
without prior notice.
Disposal of the product
The appliance (or the product) must be disposed of
separately in accordance with the local waste disposal
legislation in force
The product must be installed with the earthconnected,
using the special yellow-green terminal on the terminal
block. Do not use the neutral for the earth connection.

This manual suits for next models

3

Other Carel Control System manuals

Carel FLSTDMAHUE User manual

Carel

Carel FLSTDMAHUE User manual

Carel m chiller User manual

Carel

Carel m chiller User manual

Carel infrared IR32CE Series User manual

Carel

Carel infrared IR32CE Series User manual

Carel Hecu CO2 User manual

Carel

Carel Hecu CO2 User manual

Carel MasterCella Split User manual

Carel

Carel MasterCella Split User manual

Carel Heez Manual

Carel

Carel Heez Manual

Carel DPWL Series User manual

Carel

Carel DPWL Series User manual

Carel MPXone series User manual

Carel

Carel MPXone series User manual

Carel humiFog User manual

Carel

Carel humiFog User manual

Carel pAD ADP 30 Series User manual

Carel

Carel pAD ADP 30 Series User manual

Carel WM00E 00 Series User manual

Carel

Carel WM00E 00 Series User manual

Carel PlantVisorPRO Manual

Carel

Carel PlantVisorPRO Manual

Carel TH TUNE User manual

Carel

Carel TH TUNE User manual

Carel IROPZ48500 User manual

Carel

Carel IROPZ48500 User manual

Popular Control System manuals by other brands

HEIDENHAIN TNC 150 B manual

HEIDENHAIN

HEIDENHAIN TNC 150 B manual

btsr SMART 200 MTC operating manual

btsr

btsr SMART 200 MTC operating manual

cytiva UNICORN 7.9 manual

cytiva

cytiva UNICORN 7.9 manual

Walthers 942-101 reference guide

Walthers

Walthers 942-101 reference guide

Carefree of Colorado BT12 Installation

Carefree of Colorado

Carefree of Colorado BT12 Installation

Precision Planting 20/20 SeedSense Operator's guide

Precision Planting

Precision Planting 20/20 SeedSense Operator's guide

PAW HeatBloC K33 Installation and operation instruction

PAW

PAW HeatBloC K33 Installation and operation instruction

Dynamic iPortal 2 installation manual

Dynamic

Dynamic iPortal 2 installation manual

Mitsubishi AE-200A Instruction book

Mitsubishi

Mitsubishi AE-200A Instruction book

ETC Eos Apex 5 user manual

ETC

ETC Eos Apex 5 user manual

WEIHONG Ncstudio V15 manual

WEIHONG

WEIHONG Ncstudio V15 manual

CNC4PC C82 user manual

CNC4PC

CNC4PC C82 user manual

Yaesu SCU-LAN10 Operation manual

Yaesu

Yaesu SCU-LAN10 Operation manual

Amada EZ-AIR Operation manual

Amada

Amada EZ-AIR Operation manual

Philips SBCSK310/05 Instructions for use

Philips

Philips SBCSK310/05 Instructions for use

BFT PHP ADA installation manual

BFT

BFT PHP ADA installation manual

ARCBRO F2000 Tube Series user manual

ARCBRO

ARCBRO F2000 Tube Series user manual

Pentair SCREENLOGIC INTERFACE installation guide

Pentair

Pentair SCREENLOGIC INTERFACE installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.