EASY FREEZE (PZD*C0****):electronic controllers for low temperature ventilated refrigeration units
+050004122 - rel. 1.2 - 28.07.2011
Description
PJEZ* represent a range of electronic microprocessor controllers with LED display developed for the manage-
ment of refrigerating units, display cabinets and showcases.
Technical specifications
• Electronic controllers for low temperature ventilated refrigeration units
• Power supply 115 or 230Vac
• Ambient probe NTC
• Compressor relay 16A
• Defrost relay 8A
• Evaporator fan relay 8A
Display and functions
During normal operation, the controller displays the temperature read by probe 1. In addition, the display has
LEDs that indicate the activation of the control functions (see Table 1), while the 3 buttons can be used to
activate/deactivate some of the functions (see Table 2).
LEDs and associated functions
icon function normal operation start up
ON OFF blink
compressor on off request ON
fan on off request ON
defrost on off request ON
alarm all no alarm - ON
Tab. 1
Table of functions activated by the buttons
button
normal operation
start up
pressing the button alone pressed together
up
ON/OFF
more than 3 s:
toggle ON/OFF
Pressed together start/stop
continuous cycle
-
down
defrost
more than 3 s:
start/stop defrost
for 1 s display
firmware vers. code
set mute - 1 s.: display/set the setpoint
- more than 3 s: access parameter
setting menu (enter password ‘22’)
- mute audible alarm (buzzer)
- for 1 s RESET
current
EZY set
Tab. 2
Setting the setpoint (desired temperature)
Step Action Effect Meaning
1Keep SET button pressed for 2 s After 1 sec currently setpoint value will
flash on display
It’s regulation setpoint
currently active
2Press UP or DOWN buttons Setpoint value will chang Set desired value
3Press SET button Controller will visualize temperature
read by probes again
Setpoint is modified and
saved
Tab. 3
Accessing and setting the parameters
Step Action Effect Meaning
1Keep SET button pressed
for 3 s
After 3 sec display will visualize “PS” Password is requested
2Press SET button again Display will visualize “0” blinking
3Press UP or DOWN button Visualized value on display will change Insert password “22”
4Press SET button After 5 sec the first parameter, “/5”, will be
visualized on display
It’s the name of the first
parameter
5Press UP or DOWN button Parameter list will be scrolled on display
(refer to Table of parameters)
Select desired parameter
6Press SET button Display will visualize value of the selected
parameter
It’s the currently parameter
value
7Press UP or DOWN button Parameter value visualized on display will
change
Set desired value
8Press SET button Display will visualize parameter name
again
Attention: parameters
updating is not yet active
9Repeat steps 5, 6, 7 and 8
for all desired parameters
10 Keep SET button
pressed for 5 s
Controller will visualize temperature read
by probes again
Attention: now parame-
ters updating will be active
Tab. 4
Dimensions (mm)
71x29
10
3
33
74
81
36
58
65,29
28.5
Fig.1
Panel mounting
Front (with 2 screws ø 2,5x12 mm)
max 2,5
123
Pozidriv type
Do not tighten
excessively
Fig.2
Rear (with 2 quick-fit side brackets)
12
PUSH
serial conv. IROPZ485S0
prog. key IROPZKEY* or
PSOPZKEY*
Fig. 3
Electrical connections
230 Vac
Fig. 4
Use copper conductors only
Ref. C614A216/R0
12345 6 7
9 10 118
L
L N
115V~
8(4)A 10(10)A EN60730-1
8A 2FLA 12LRA 12A 10FLA 60LRA UL 873
DEF. T.
DI / NTC
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
250 Vac
12345 6 7
9 10 118
L
L N
Use copper conductors only
Ref. C614A217/R0
8(4)A 10(10)A EN60730-1
8A 2FLA 12LRA 12A 10FLA 60LRA UL 873
DEF. T.
DI / NTC
AMB. T.
NTC
PROBES
SERIAL
CONV
PROG.
KEY
-10T50
250 Vac
230V~
Fig. 5
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
PZD4C0H101
PZD4C0H001
PZD0C0P001
+050004122 - rel. 1.2 - 28.07.2011
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 0499716611 – Fax (+39) 0499716600 – http://www.carel.com – e-mail: [email protected]
Table of parameters
Parameter Min. Max. Def. UOM
PS PASSWORD 0 200 22 -
/ PROBE PARAMETERS
/5 Select °C / °F ( 0 = °C; 1 = °F) 0 1 0 -
/6 Disable decimal point (1 disabled) 0 1 0 -
/C1 Probe calibration -50.0 50.0 0.0 °C/°F
/C2 Probe 2 calibration -50.0 50.0 0.0 °C/°F
r CONTROL PARAMETERS
St Control temperature -50.0 90.0 -18.0 °C/°F
rd Control differential (hysteresis) 0.0 19.0 2.0 °C/°F
c COMPRESSOR PARAMETERS
c0 Comp. and fan start delay after start-up 0 100 0 min
c1 Min. time between successive comp. starts 0 100 1 min
c4 Compressor safety (duty setting) 0 100 15 min
d DEFROST PARAMETERS
d0 Type of defrost (0= heater; 1= hot gas; 2= heater by time;
3= hot gas by time; 4= heater by time with temp. cont.)
04 0-
dI Interval between two defrosts 0 199 6 h/min
dt End defrost temperature 50.0 130.0 8 °C/°F
dP Max. or effective defrost duration 1 199 25 min/s
d4 Defrost when the instrument is switched on (1= activated) 0 1 0 -
d6 Disable temperature display during defrost (1= display disabled) 0 1 1 -
dd Dripping time after defrost 0 15 1 min
d/ Defrost probe reading - - - °C/°F
A ALARM PARAMETERS
A0 Alarm and fan differential -20.0 20.0 -2.0 °C/°F
AL Low temperature alarm threshold/deviation (AL= 0; alarm disabled) -50.0 250.0 -50 °C/°F
AH High temperature alarm threshold/deviation (AH= 0; alarm disabled) -50.0 250.0 50 °C/°F
Ad Low and high temperature alarm delay 0 199 0 min
F FAN PARAMETERS
F0 Fan management: 0= fans on excluding specific phases;
1= fans on according to parameter F1 excluding specific phases
01 1-
F1 Fans shutdown temperature 50.0 130.0 2 °C/°F
F2 Fans OFF when compressor OFF 0 1 1 -
F3 Fans status during defrost: 0= fan ON; 1= fan OFF 0 1 1 -
H OTHER SETTINGS
H2 Enable keypad
0= keypad disabled
1= keypad enabled
2= keypad enabled except for ON/OFF function
02 1-
EZY restore the Default settings 0 1 0 -
Tab. 5
Table of alarms
Alarm
code
buzzer and
alarm relay
LED Description Parameters involved
E0 active ON probe 1 error= control -
E1 inactive ON probe 2 error= defrost [d0 = 0 / 1]
LO active ON low temperature alarm [AL] [Ad]
HI active ON high temperature alarm [AH] [Ad]
EE inactive ON unit parameter error -
EF inactive ON operating parameter error -
Ed inactive ON defrost ended by timeout [dP] [dt] [d4] [A8]
dF inactive OFF defrost running [d6=0]
Tab. 6
How to restore the Default settings (refer to table of parameters in this
sheet)
1) Access parameter EZY (entering password 22 and scroll parameter list).
2) Select the desired configuration:
• EZY = 0 No changes;
• EZY = 1 Restore of default settings (refer to Table of parameters in this sheet);
3) Exit the setting procedure (holding SET button for more than 3 sec).
4) Power off the device and then power it on again while holding SET button.
5) The display shows “CE” to indicate that the configuration has been restored.
Switching the device ON/OFF
Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instrument displays the
message “OFF” alternating with the temperature read by the set probe.
Manual defrost
Press DOWN for more than 3 s (the defrost starts only if the temperature conditions are valid).
Continuous cycle
Press UP and DOWN together for more than 3 s.
Technical specifications
power supply 115 Vac +10 / -15% 50/60 Hz
230 Vac -10% +15% 50/60 Hz
rated power 3,5 VA
inputs NTC probes
relay outputs 16 A relay UL: 12 A Res. 5 FLA 30 LRA - 240 Vac C300,
EN60730-1: 12(2) A NO/NC, 10(4) A up to 60 °C NO,
2(2) A CO - 250 Vac
2HP ralay UL: 12 A Res. 5 FLA 60 LRA - 240 Vac,
EN60730-1: 10(10) A - 250 Vac,
8 A relay UL: 8 A Res. 2 FLA 12 LRA - 240 Vac C300,
EN60730-1: 8(4) A NO, 6(4) A NC, 2(2) A CO - 250 Vac
type of probe Std CAREL NTC 10 Kat 25 °C
connections Screw terminals for cables with cross-sect. from 0.5 mm2 to 1.5 mm2
Rated maximum current per terminal 12 A
assembly Terminal: using screws from the front panel or with rear brackets
Interface: wall mounting, 4 screws, spacing 101x151 mm
display 3 digit LED display with sign (-199 to 999) and decimal point; six status LEDs
operating conditions -10T50 °C - humidity <90% rH non-condensing
storage conditions -20T70 °C - humidity <90% rH non-condensing
range of measurement -50T90 °C (-58T194 °F) - resolution 0.1 °C/°F
front panel index of protection panel installation with IP65 type 1 gasket
case plastic terminal, 81x36x65 mm
classification according to protection
against electric shock
Class II when suitably integrated
environmental pollution normal
PTI of the insulating material 250 V
period of stress across the insulating parts long
category of resistance to heat and fire category D (UL94 - V0)
immunity against voltage surges category 1
type of action and disconnection 1C relay contacts
no. of relay automatic operating cycles EN60730-1: 100,000 operations
UL: 30,000 operations (250 Vac)
software class and structure Class A
cleaning the instrument Only use neutral detergents and water.
cable max. lenght serial: 1 km
probes: 30 m
relay: 10 m
Tab. 7
Note: do not run the power cable less than 3 cm from the bottom part of the device or from the probes;
for the connections only use copper wires.
Safety standards
compliant with the relevant European standards. Installation precautions:
• the connection cables must guarantee insulation up to 90 °C;
• ensure a space of at least 10 mm between the case and the nearby conductive parts;
• digital and analogue input connections less than 30 m away; adopt suitable measures for separating the
cables so as to ensure compliance with the immunity standards;
Secure the connection cables of the outputs so as to avoid contact with very low voltage parts.
IMPORTANT WARNINGS
The CAREL product is a state-of-the-art device, whose operation is specified in the technical documentation
supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating
to the configuration of the product in order to reach the expected results in relation to the specific final instal-
lation and/or equipment. The failure to complete such phase, which is required/indicated in the user manual,
may cause the final product to malfunction; CAREL accepts no liability in such cases. The customer must use
the product only in the manner described in the documentation relating to the product. The liability of CAREL
in relation to its products is specified in the CAREL general contract conditions, available on the website www.
carel.com and/or by specific agreements with customers.
CAREL reserves the right to modify the features of its products without prior notice.
Disposal of the product
The appliance (or the product) must be disposed of separately in accordance with the local waste disposal
legislation in force.
WARNING: separate as much as possible the probe and digital input signal cables from the cables carrying
inductive loads and power cables to avoid possible electromagnetic disturbance. Never run power cables
(including the electrical panel wiring) and signal cables in the same conduits.
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!

This manual suits for next models

3

Other Carel Controllers manuals

Carel pCO2 Series User manual

Carel

Carel pCO2 Series User manual

Carel ir33+wide User manual

Carel

Carel ir33+wide User manual

Carel IR32 Series User manual

Carel

Carel IR32 Series User manual

Carel supernode Manual

Carel

Carel supernode Manual

Carel EASY COOL User manual

Carel

Carel EASY COOL User manual

Carel boss User manual

Carel

Carel boss User manual

Carel IRMPX00000 User manual

Carel

Carel IRMPX00000 User manual

Carel ADP 30 pAD Series User manual

Carel

Carel ADP 30 pAD Series User manual

Carel DN33 Universale Series Guide

Carel

Carel DN33 Universale Series Guide

Carel FCM series User manual

Carel

Carel FCM series User manual

Carel pCO3 series Manual

Carel

Carel pCO3 series Manual

Carel universal infrared series User manual

Carel

Carel universal infrared series User manual

Carel mastercella Manual

Carel

Carel mastercella Manual

Carel HYVC000R0 Series User manual

Carel

Carel HYVC000R0 Series User manual

Carel ir33+ User manual

Carel

Carel ir33+ User manual

Carel EVD4 User manual

Carel

Carel EVD4 User manual

Carel ADCD000110 User manual

Carel

Carel ADCD000110 User manual

Carel P+E c.pCOe User manual

Carel

Carel P+E c.pCOe User manual

Carel Rsf077 User manual

Carel

Carel Rsf077 User manual

Carel pCO Series User manual

Carel

Carel pCO Series User manual

Carel AT th Tune Series User manual

Carel

Carel AT th Tune Series User manual

Carel pCO User manual

Carel

Carel pCO User manual

Carel uChiller UCHBP00000190 User manual

Carel

Carel uChiller UCHBP00000190 User manual

Carel pCO1 series User manual

Carel

Carel pCO1 series User manual

Popular Controllers manuals by other brands

LumaSense LumaSMART user manual

LumaSense

LumaSense LumaSMART user manual

ATI Technologies MetriNet Q52 O & M Manual

ATI Technologies

ATI Technologies MetriNet Q52 O & M Manual

Pixsys ATR620 user manual

Pixsys

Pixsys ATR620 user manual

Apollo Seiko OMEGA instruction manual

Apollo Seiko

Apollo Seiko OMEGA instruction manual

Magnetek 2001-G+M instruction manual

Magnetek

Magnetek 2001-G+M instruction manual

Omron G3PW user manual

Omron

Omron G3PW user manual

IAI ROBO Cylinder RCS4- SA4C instruction manual

IAI

IAI ROBO Cylinder RCS4- SA4C instruction manual

Dantherm CC 3000 Service manual

Dantherm

Dantherm CC 3000 Service manual

Telemark 861 Quick setup

Telemark

Telemark 861 Quick setup

Emulex MD01 Technical manual

Emulex

Emulex MD01 Technical manual

Emerson Bettis Q series Installation, operation & maintenance manual

Emerson

Emerson Bettis Q series Installation, operation & maintenance manual

Nelson EZ Pro Jr Installation and programming guide

Nelson

Nelson EZ Pro Jr Installation and programming guide

SyxthSense SRC-131 user manual

SyxthSense

SyxthSense SRC-131 user manual

Seneca S6001 user manual

Seneca

Seneca S6001 user manual

Johnson Controls PCA3613 installation instructions

Johnson Controls

Johnson Controls PCA3613 installation instructions

Haiwell PLC user manual

Haiwell

Haiwell PLC user manual

Orion OPM-4260 user manual

Orion

Orion OPM-4260 user manual

Calian SatService sat-nms ACU-ODM user manual

Calian

Calian SatService sat-nms ACU-ODM user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.