CIAT V3000 KNX Use and maintenance manual

V3000
KNX
03 - 2017
EN7515935-00
Control manual


CONTENTS PAGE
1 - USER TERMINAL AND RADIO-FREQUENCY REMOTE CONTROL 2
2 - CLOSE-UP OF DISPLAY TERMINAL SCREENS 3
3 - MEANING OF SYMBOLS 3
4 - INSTALLATION PARAMETERS 4
5 - DIAGNOSTIC 6
6 - AIR TEMPERATURE MEASUREMENT 10
7 - SPECIFICATIONS OF SENSORS USED BY THE V3000 10
8 - WATER TEMPERATURE MEASUREMENT 10
9 - CONTROL ALGORITHM 11
10 - CONNECTING THE FRAME CONTACT 12
11 - FRESH AIR 13
12 - MASTER / SLAVE FUNCTION 13
13 - RADIO-FREQUENCY REMOTE CONTROL (SET-UP) 16
14 - TECHNICAL SPECIFICATIONS 18
15 - WIRING DIAGRAM 20
ORIGINAL TEXT: FRENCH VERSION
EN
EN - 1 EN7515935-00

1 - USER TERMINAL AND RADIO-FREQUENCY REMOTE CONTROL
Display
terminal
Radio-frequency
Remote control
1
2
3
4
Dial terminal
Flush-mounted terminal
10
11
3
5
8
9
7
6
4
3
4
2
1
Display:
- This continuously displays the temperature detected by the sensor, the current operating mode, the chosen ventilation
speed, and any alarm present.
- If you press the buttons
,
scale appears, and you can modify the desired temperature by pressin
or .
The
temperature measured by the sensor is displayed again 8 seconds after the last time button
.
was pressed.
- It also displays error messages, reports windows opened or emergency switch-off activation, thereby enabling an initial
diagnostic.
T
emperature adjustment buttons
:
- These enable you to adjust the temperature setpoint and also access the set-up and diagnostic values
.
Standby button
:
- This enables you to change the operating mode (comfort, standby, economy, frost protection according to the chosen
set-up).
Ventilation button
:
- This enables you to select the ventilation speed (Auto, I, II, III) if the controller is in comfort, or switch to comfort mode if
the controller is in standby (see close-up of display below)
Temperature adjustment dial
Cold indicator. If lit, this indicates refrigeration
Heat indicator. If lit, this indicates heating
Automatic ventilation indicator
Low speed ventilation indicator
Medium speed ventilation indicator
High speed ventilation indicator
Note on Ventilation speed indicator operation:
*
If only
-
or lit =
Current manual speed selected.
* If
+ (
or
or ) =
Current speed given by controller AUTOMATIC position
.
Si un des voyants
à est éclairé, alors le régulateur est en régime confort
Note:
The wall terminals are interchangeabl
e.
EN7515935-00 EN - 2

2 - CLOSE-UP OF DISPLAY TERMINAL SCREENS
Display of temperature measured in
room
Bar graph of setpoint offset
Heating active
Cooling active
Alarm:
Flashing spanner= Alarm switches off the unit
Fixed spanner = Alarm does not switch off the
unit
Displays the parameter values in % from the
controller set-up menu
Temperature unit
Delayed comfort mode
Off for Economy/Standby/or
Frost protection modes,
depending on set-up
Dehumidification mode
or
Condensate pump fault if flashing
3 manual ventilation speeds +
Automatic position
Special display:
---:
Stop on window contact
Fro:
Stop on Frost protection device
Cnf:
KNX Configuration Menu
Add x:
Controller performing automatic Master/Slave configuration
Lrn:
Controller in Configuration mode on a KNX bus (Learning mode for ETS)
del:
Controller performing automatic Master/slave deconfiguration
e
Err:
Error occurred during Master/Slave configuration
3 - MEANING OF SYMBOLS
Symbols Display version Dial version
Heating Heating symbol fixed Heating LED fixed
Refrigeration Air conditioning symbol fixed Air conditioning LED fixed
Delayed comfort Hourglass + ventilation status One ventilation LED lit (according to user
Comfort not delayed Ventilation only status
Reduced (Standby, eco, frost protection) set via KNX
or standby button on terminal
Standby symbol
No ventilation indication
All ventilation LEDs off
Frost protection by window contact Three dashes "---" in place of temperature
No ventilation indication
All ventilation LEDs off
Standby or eco by presence contact or clock contact Standby symbol No ventilation indication All ventilation LEDs off
Setpoint adjustment Depends on set-up
Ventilation 1, 2 or 3 ventilation symbols displayed simultaneously
to indicate LS, MS or HS.
If auto is selected, the AUTO symbol appears in
addition to the ventilation symbols
If AUTO selected, the LED for current speed is lit.
If AUTO is off, the speed indicator gives the manual
speed selected.
Dehumidification function Fixed water drop Air conditioning LED flashing
Indoor environment sensor fault if indoor environment
sensor assigned priority
Adjustable spanner fixed No particular indication
Return sensor fault if return sensor assigned priority Adjustable spanner fixed No particular indication
Simultaneous fault on indoor environment and return
sensors
Adjustable spanner flashing Heating + air conditioning LEDs flashing simultaneously
Safety sensor fault, “anti-condensation” Adjustable spanner flashing Heating + air conditioning LEDs flashing simultaneously
Condensate drain pump alarm Flashing water drop Heating + air conditioning LEDs flashing simultaneously
Fan unit motor assembly alarm Adjustable spanner flashing Heating + air conditioning LEDs flashing simultaneously
General alarm Adjustable spanner flashing Heating + air conditioning LEDs flashing simultaneously
Frost protection alarm in fresh air application
(antifreeze thermostat)
Letters "Fro" in place of temperature Heating + air conditioning LEDs flashing simultaneously
Filter needs replacing Adjustable spanner fixed No particular indication
Device designated as Master or Slave (P00 ≠ 0 ) but
has not yet been configured
Adjustable spanner flashing Heating + air conditioning LEDs flashing simultaneously
Generally speaking:
Alarm not disabling V3000 operation
Alarm stopping V3000 operation
Adjustable spanner fixed
Adjustable spanner flashing
No particular indication
Heating + air conditioning LEDs flashing simultaneously
EN
EN - 3 EN7515935-00

To modify the installation parameters, a display terminal is essential (wall-mounted display terminal, ush-mounted display terminal
or radio remote control terminal).
To enter set-up mode, you need to simultaneously press the standby , ventilation and buttons for 5 seconds, then press
the button twice, and finally the standby button for 5 seconds.
The parameter is selected by pressing the and . buttons. To consult a parameter value, you need to press the standby
button . To validate a parameter modification, press the standby button. To exit set-up mode, press the ventilation button .
If a set-up has been changed and you go back to normal operating mode, the terminal display switches off briefly and then
displays its version number (e.g. 101) for around 5 seconds, while it reconfigures the controller before going back to the normal
display.
Parameter Name Explanation Setting range Default value
P00 Master/Slave/Stand-alone
The controller must be informed whether it is a master or a slave,
or whether it is stand-alone.
0 = individual
1 = Master
2 = Slave by hot/cold authorisation
3 = Slave by indoor temperature
4 = Slave by actuator position
0…4 0
P01 Zone number Zone number used for configuring a KNX installation in Push
Button mode. 0…16 0
P02 Heating comfort setpoint Setpoint for heating control in comfort mode 5…40
increments of 0.5 19.0
P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode 5…40
increments of 0.5 26.0
P04 Heating Standby setpoint Setpoint for heating control in Standby mode 5…40
increments of 0.5 17.0
P05 Consigne Stand By
refroidissement Setpoint for heating control in Standby mode 5…40
increments of 0.5 28.0
P06 Heating economy setpoint Setpoint for heating control in economy mode 5…40
increments of 0.5 14.0
P07 Cooling economy setpoint Setpoint for cooling control in economy mode 5…40
increments of 0.5 32.0
P09 Supply air low limit Setpoint below which blown air temperature limiting is activated 5…35 resolution of 0.5 16.0
P10 Supply air upper limit Setpoint above which blown air temperature limiting is activated 20…70 resolution of 0.5 40.0
P11 Comfort setpoint setting range Sets the maximum +/- offset from the setpoint for indoor
environment devices
0.0…9.5 resolution
of 0.5 4.5
P12 Air quality setpoint
If an air quality sensor is present on KONNEX bus, air quality
setpoint expressed in ppm, with fixed hysteresis of 200 ppm:
0 = Function inactive
0.1…5.0 = Setpoint in thousand ppm
0…5.0
increments of 0.1 1.0
P13 Comfort operating option 0 = Inactive
1 = Dehumidification function 0:1 0
P14 Dehumidification setpoint
(if option = dehumidification)
If a humidity sensor is present on KONNEX bus, the
dehumidification function remains active as long as the humidity
value is above the setpoint:
0 = Inactive
1… 100 = Setpoint
0…100 100
4 - INSTALLATION PARAMETERS
EN7515935-00 EN - 4

Parameter Name Explanation Setting range Default value
P24 Temperature sensor selection (if
recycled air application)
Control sensor selection
0 = Return sensor priority
1 = Indoor environment sensor priority
0:1 Depending on
application
P25 Sensor S1 calibration Correction factor for sensor S1 (return or supply air sensor,
depending on applications). -9.9…+9.9 resol. 0.1 0
P26 Indoor environment sensor
calibration Correction factor for indoor environment sensor -9,9…+9,9 résol. 0,1 0
P27 Changeover upper threshold 2-pipe changeover upper threshold for hot water detection in
relation to ambient temperature 0/20 7
P28 Changeover lower threshold 2-pipe changeover lower threshold for cold water detection in
relation to ambient temperature 0/-20 -4
P40 Ventilation in neutral zone
comfort mode
In the comfort mode neutral zone, the fan may run all the time, be
switched off completely, or run periodically:
0 = ventilation off
1 = permanent ventilation, any season
2 = permanent ventilation in summer
3 = ventilation periodically restarted
0:1:2:3 Depending on
application
P41 Ventilation in neutral zone
Standby mode
In the standby mode neutral zone, the fan may run all the time, be
switched off completely, or run periodically:
0 = ventilation off
1 = permanent ventilation, any season
2 = permanent ventilation in summer
3 = ventilation periodically restarted
0:1:2:3 0
P47 Operating mode activated by
standby button on user terminal.
1 = Comfort --> Frost protection
2 = Comfort --> Eco
3 = Comfort --> Standby
1:2:3 1
P48 Comfort override delay
Override to remain in comfort mode after comfort mode activation
from the user terminal. It may be set to run all the time, have a
limited period, or prohibit overrides
0 = Override prohibited
0.5.24 = Override time in h
24.5 = Infinite override time
0.0…24.5 (increments
of 0.5 h) 24.5
P49 Action direction of auxiliary contact
on input D1
The auxiliary contact on input DI1 may be normally closed or
normally open:
0 = Normally open
1 = Normally closed
0:1 1
P50 Action direction of auxiliary contact
on input D2
The auxiliary contact on input DI2 may be normally closed or
normally open:
0 = Normally open
1 = Normally closed
0:1 1
P51 Input D1 function
This parameter enables this input to have
several functions
0 = Inactive
1 = Window contact (= Frost protection)
2 = Presence contact (Max Eco)
3 = Presence contact (Max Standby)
4 = Condensate drain pump
5 = Fan unit motor alarm
6 = General alarm
7 = Air quality sensor
8 = Clock (comfort --> Eco)
9 = Clock (comfort --> Standby)
0…9
4
(or 5)
(or 6)
P52 Input D2 function
This parameter enables this input
to have several functions:
0 = Inactive
1 = Window contact (= Frost protection)
2 = Presence contact (Max Eco)
3 = Presence contact (Max Standby)
4 = Condensate drain pump
5 = Fan unit motor alarm
6 = General alarm
7 = Air quality sensor
8 = Clock (comfort --> Eco)
9 = Clock (comfort --> Standby)
10 = Frost protection for "Fresh air"
0…10 1
(or 10)
EN
EN - 5 EN7515935-00

Note:
T
o perform a diagnostic, you must use a display terminal.
T
o enter diagnostic mode, you need to press the ventilation
and
buttons simultaneously for 5 seconds
.
The parameter is selected by pressing the
and .
buttons. To consult a parameter value, you need to press the standby
button
.
To exit diagnostic mode, press the ventilation button
Diagnostic Name Explanation
d01 Individual address
d02 Master address Only valid for configuration in Push Button mode (see KNX Bus manual NA 08.51)
d03 Zone number
d04 Application type
1 = 2-Wire
2 = 2-pipe
21 = 2-Pipe/2-Wire
22 = 2 Tubes Froid + radiateur
23 = 2 tubes + convecteur élec.
4 = 4-pipe
41 = 4-Pipe/2-Wire
Parameter Name Explanation Setting range Default value
P55 Heating electrical power (based
on 230 V)
If an electric heater is used, the power (in kW) must be indicated
in this parameter, rounded up to the nearest 100W. Used for
certain energy consuming applications
0…20,0 résolution de 0,1 2.0
P56 LS power
The low speed ventilation power must be indicated in this
parameter, rounded up to the nearest 5W.
Used for certain energy consuming applications
5…990
increments of 5 50
P57 MS power
The medium speed ventilation power must be indicated in this
parameter, rounded up to the nearest 5W.
Used for certain energy consuming applications
5…990
increments of 5 75
P58 HS power
The high speed ventilation power must be indicated in this
parameter, rounded up to the nearest 5W. Used for certain energy
consuming applications
5…990
increments of 5 75
P59 Hot water coil nominal capacity Nominal capacity (in kW) of the hot water coil, rounded up to the
nearest 100W. Used for certain energy consuming applications
0…99.0 resolution
of 0.1 100
P60 Cold water coil nominal capacity Nominal capacity (in kW) of the cold water coil, rounded up to the
nearest 100W. Used for certain energy consuming applications
0…99.0 resolution
of 0.1 2.0
P62 Base outdoor temperature Lowest outdoor temperature for electric heater power limiting -35…+5 -10
P64 Setpoint deviation from outdoor
temperature
Max difference between cold setpoint and outdoor temperature
0 = Inactive 0…20 6
P67 Battery/coil use authorisation
1 = hydraulic + electric
2 = hydraulic only
3 = electric only
1:2:3 Depending on
application
P93 Period for filter maintenance
At the end of this ventilation time, the maintenance pictogram
appears on the screen for filter replacement. This pictogram does
not stop control:
0 = Inactive
1…200 = time in days (in HS equivalent)
0…200 0
P94 Temperature displayed in °C or °F 1 = Temperature displayed in °C
2 = Temperature displayed in °F 1:2 1
P95 Temperature displayed on terminal
Actual temperature display on the indoor environment device
LCD:
1 = Setpoint
2 = Measurement
1:2 2
P96 Setpoint offset value display
Display of actual temperature offset value:
1 = Not displayed (bar graph)
2 = Display offset + bar graph
3 = Display setpoint + bar graph*
1:2:3 1
(*) The absolute setpoint displayed corresponds to the heating requirements calculated by the V3000:
- if the room temperature (°C) > current cooling setpoint: the cooling setpoint is displayed
- if the room temperature (°C) > current heating setpoint: the heating setpoint is displayed.
5 - DIAGNOSTIC
EN7515935-00 EN - 6

Diagnostic Name Explanation
d05 Application type 1 = Recycled air sequence
2 = Fresh air sequence
d06 Function to limit the temperature of
blown air.
1 = Room control without supply air limiting
2 = Room control with supply air limiting
3 = Control at constant supply air temperature
d07 Type of valve motor, fan coil
1 = 3 points
2 = On/off
3 = Thermal
4 = 0/10 V
d08 Ambient temperature Ambient temperature display
d09 Return or supply air temperature Return or supply air temperature display
d10 Setpoint in progress Temperature setpoint corresponding to the last regulation sequence made by the controlle
d11 C/O Temperature if room C/O or central C/O status
d12 Heating/cooling authorisation
CO = Cold
HE = Hot
0 = No
AU = Auto
d13 Electric/hydraulic authorisation
1 = hydraulic + electric
2 = hydraulic only
3 = electric only
d14 Communication mode
InI = Initialisation
BUS = Bus switched on, no central unit
BMS = Dialogue with central unit
--- = Bus switched off
d15 Fan electrical consumption Calculated fan consumption (display unit = kWh)
d16 Electric heater electrical consumption Calculated electric heater consumption (display unit = hundred kWh)
d17 Heating heat consumption Calculated heat consumption of heating coil (display unit = hundred kWh)
d18 Air conditioning heat consumption Calculated heat consumption of air conditioning coil (display unit = hundred kWh)
d19 Filter maintenance time meter Number of hours' ventilation (in high speed equivalent) since last filter replacement
d20 Controller software version 10 (example)
d21 Terminal software version 10 (example)
d22 Current error
Alarm code Alarme description
E07 Replace filter
E08 Supply air sensor fault
E09 Return air sensor fault
E10 Indoor environment sensor fault
E11 Centralised changeover not received
E12 Fresh air frost protection alarm (supply air safety device)
E13 Fresh air frost protection alarm (safety thermostat)
E14 Condensation alarm
E15 Slave cut off from master
E16 Condensate drain pump alarm
E17 General alarm
E18 Fan unit alarm
E19 Active temperature sensor fault
E20 Condensation sensor S3 fault
E21 Master or Slave not configured
E22 No other Push button product selected on the bus
E23 Impossible to connect to selected push button product
d23 Last error message As d22
d24 Outdoor temperature Outdoor temperature display
With:
E00: alarm does not switch off the terminal unit, xed key (E07 to E15)
E00: alarm locks the terminal unit off, ashing key (E16 to E23)
EN
EN - 7 EN7515935-00

Certain problems may be resolved by checking some fundamental points. Check using the list below before requesting servicing.
N.B.:
When the controller is switched on, control will only take effect after a few minutes of system initialisation.
If you have a display terminal, this displays its version number (e.g. 101) for around 5 seconds after switching on.
Upon a mains power cut:
1. when power is restored, the controller restarts automatically in the mode operating before the cut, with:
if Comfort Mode, it restarts in Comfort mode, but it is not store:
- The setpoint override returns to the middle point
- The ventilation speed returns to Auto
2. All information from the KNX bus is lost.
3. Error message: diagnostic d23 saves the last error message. d23 is saved even in case of a power cut.
Irregularity Solution
User terminal
Terminal off or no Led is lit on the terminal in comfort mode
- No 230V supply (check fuse, fused isolator, controller connection)
- Check the electrical connection between the terminal and the controller (refer to
wiring diagram)
Flashing water drop - Check the condensate pump, the condition of the condensate pan.
Display '_ _ _' Window open
Symbol on display See diagnostic d22
Fan coil unit
The valves close instead of opening and vice-versa - If the controller has just been supplied, wait for system initiation (6 mins)
- Check the electrical connection of the valves (refer to wiring diagram).
No heating
- Check that:
- The hot setpoint T°C is greater than the measured and displayed
temperature
- Any shunt in case of a 2-pipe (hot water coil only) is present between
terminals S2 and C (refer to wiring diagram).
- Any room changeover sensor, in case of a reversible 2-pipe coil, is
correctly electrically connected and that the sensing element is in contact
with the water inlet pipe
- The controller is correctly set up (refer to the Installation parameters
procedure)
- If operating with an electric heater, check that the T°C limiters are
activated.
No refrigeration
- Check that:
- The cold setpoint T°C is less than the measured and displayed
temperature
- Terminals S2 and C are not connected by a shunt in case of a 2 cold
pipes only, with or without electric heater
- Any room changeover sensor, in case of a reversible 2-pipe coil, is
correctly electrically connected and that the sensing element is in contact
with the water inlet pipe
- The controller is correctly set up (refer to the Installation parameters
procedure)
The fan always remains at high speed.
- Check that:
- The water inlet T° is correct
- The water flow is sufficient
- The installation has been correctly bled
- The control parameters are suitable (proportional band, integration time)
- The ventilation is not in manual position III
EN7515935-00 EN - 8

Faults are automatically released once the problem related to the fault is resolved (sensor replaced…).
*Only the "Filter" fault requires manual release - to do so:
- replace or clean the filter
- In the Diagnostic menu, access d19 "Filter maintenance time meter"
- Set this meter to 0 by pressing and holding the button for 5 seconds.
- Go back out of the diagnostic menu
- The alarm is released.
Alarm code Diagnostic Solutions
E07 Replace filter The triggering time for this alarm can be set under P93
It is released in D19 by setting this meter to O*
E08 Supply air sensor fault or absent (P78=2) Check the sensor, its wiring at S1 and the corresponding parameter
E09 return sensor fault (P24=0) Check the sensor, its wiring at S1
E10 indoor environment sensor fault (P24=1) Check the condition and wiring of the room terminal
E11 Centralised changeover via KNX not received Check the bus wiring, its supply, the KNX links with the Building Management System
supplier
E12 fresh air frost protection alarm (supply air safety
device) Check the hot water temperature, the hot valve
E13 fresh air frost protection alarm (safety thermostat) Check the hot water temperature, the hot valve, the condition of the antifreeze thermostat
E14 condensation alarm
The terminal unit is in anti-condensation operating sequence following the appearance of
condensates on the cooling coil. This alarm is present as long as there is condensation
present on the cooling coil. Check the water temperature
E15 Slave cut off from master No dialogue between a master and a slave.
Check the bus (connections, supply)
Check the Master controller supply
E16 condensate drain pump alarm Check the condensate pump
E17 general alarm Check the condition of the contacts on D1-C and D2-C
E18 Fan unit alarm Check the condition of the fan unit
Check the condition of the contacts on D1-C and D2-C
E19 active temperature sensor fault
the 2 possible control sensors are faulty
Check the condition and wiring of the temperature sensors wired to the controller
Check the condition and wiring of the wall-mounted room terminal
E20 condensation sensor S3 fault Check the condition and wiring of the anti-condensation sensor at S3-C
E21 Master or Slave not configured Appears when configuring Master/Slave using push button until the master or slave is
configured
E22 no other Push button product selected on the bus Configure all products that need to be interlinked to create a Master/slave cluster
E23 impossible to connect to selected push button product Check that the products in push button configuration are mutually compatible
Check the bus, its supply, its wiring and the master/slave parameter (P00) on each product
to be configured
-- No Alarm
With:
E00: alarm does not switch off the terminal unit. (E07 to E15)
E00: alarm locks the terminal unit off. (E16 to E23)
EN
EN - 9 EN7515935-00

●Parameter P24
Diagnostics d08, d09
The V3000 offers the possibility of controlling the air temperature via a return sensor or an indoor environment sensor (P24).
If you can choose between the two, it is preferable to opt for the indoor environment sensor, since it provides a better picture of
the room temperature.
The indoor environment sensor is situated inside the user terminal unit. When it is used, particular care must be taken in choosing
the location of the user terminal in the room (do not expose it to sunlight, or place it on top of a device giving off heat - put it on
an inside partition).
The end of the wiring conduit must be heat insulated.
20 cm
mini
150 cm
~ 150 cm
The choice of sensor is made using parameter P24 (=0: return sensor; =1: indoor environment sensor).
If the selected sensor is faulty, the other sensor immediately takes over. A symbol is displayed on the screen and the fault can
also be looked up in the variable of diagnostic d22.
In case of doubt about the origin of the displayed temperature value, the value measured by the return sensor can be read in d09.
The value measured by the indoor environment sensor can be read in d08. If the sensor is absent, the value displayed is equal to 0.0°C.
The sensor measurement can be corrected by means of parameter P25 (return sensor) or P26 (indoor environment sensor).
6 - AIR TEMPERATURE MEASUREMENT
●Parameters P27, P28
Diagnostic d11, d12
The 2-pipe hot/cold fan-coil units may be tted with a water temperature sensor (or changeover sensor). It must be positioned
using a conduit clip by the installer upline of the four-way valve (water piping end). It is fastened to the pipe by means of
electrician's clamps.
Position and use of the changeover sensor
Water inlet
pipe
Insulation
Clamp
Sensor adapter
Sensor
Valve motor
3-way valve with
built-in bypass
(often called a
4-way valve)
Sensor
●Changeover operating algorithm:
- If the changeover sensor measures water temperature greater than 7°C (adjustable in P27) at ambient temperature, the
water is deemed to be hot.
- If the changeover sensor measures water temperature less than 4°C (adjustable in P28) at ambient temperature, the water
is deemed to be cold.
- If the changeover sensor measures water temperature between these 2 values, the water is deemed neutral.
●Changeover operation with water at neutral temperature:
In this scenario, and when there is an established need from the controller, the V3000 launches a test cycle on the valve every 45
mins so as to check the network's available water temperature (valve 100 % opened to authorise water circulation in the terminal
unit coil).
- If this temperature does not vary, the V3000 keeps the same status
- If this temperature varies and returns to the conditions described above, the V3000 re-authorises its control cycle
Important
:
the changeover sensor measures the surface temperature of the piping. There is an obvious difference between the
actual water temperature and the surface temperature. The water speed will therefore be selected so as to guarantee changeover
switching
.
- For P31 = 1, if nothing is connected between terminals S2 and C, the controller deduces that the water circulating in the coil is
still cold. If there is a bridge between these terminals, the controller deduces that the water is still hot.
- For P31 = 2, the controller waits to receive the water temperature from the central management unit before starting in heating or
cooling mode (if it does not receive a temperature value, it will not start its heating or cooling control sequence and will indicate
alarm E11)
7 - SPECIFICATIONS OF SENSORS USED BY THE V3000
All the sensors used by the V3000 (return, changeover) have the same specications
Temperature °C 5 10 15 20 25 30 35
Resistance Ohms 22 050 17 960 14 690 12 090 10 000 8 313 6 940
8 - WATER TEMPERATURE MEASUREMENT
EN7515935-00 EN - 10

Parameters P40, P41, P47, P48, P49, P50, P51, P52, P62, P67.
●PID setting
The Proportional Integral Derivative control parameters are set in the factory.
The values are:
- Hot Proportional Band: 4 K
- Hot Integration Time: 5 min
- Hot derivative time: 1 min
- Cold Proportional Band: 2 K
- Cold Integration Time: 10 min
- Cold derivative time: 1 min
These values, validated in the laboratory, enable “Comfort” operation in most terminal unit applications.
●Neutral zone ventilation
According to the operating mode, the neutral zone ventilation is set in the factory as follows:
- Comfort mode (P40): 0 Ventilation off (if controller with indoor environment sensor) or 3: periodic restarts (if control with
return sensor)
- Standby mode (P41): 0 Ventilation off
- Economy mode: 0 Ventilation off
- Frost protection mode: 0 Ventilation off
- Neutral zone ventilation is adjustable via P40 and P41, to comfort and standby mode
It is possible either to cut off the ventilation after 2 mins post-ventilation (parameter = 0), or have constant low speed ventilation
(parameter = 1), or have constant ventilation in the summer and cut off in the winter (parameter = 2), i.e. ventilation on every 30
mins for 30 seconds.
If control is applied using the return sensor, it is strongly recommended to have continuous low speed ventilation.
The setting of these parameters is derived from a compromise between control precision, physiological comfort and energy saving.
- When the V3000 is powered up, the deadband ventilation process will be effective as soon as the rst heating or cooling request
is made for a room.
●Minimum ventilation time
In automatic ventilation, the controller automatically engages the ventilation speeds. To limit the number of ventilation speed
changes, there is a stipulated minimum ventilation run time of 2 minutes at each speed.
●Comfort override delay
To control energy consumption, the controller may limit the operating time in comfort mode following a user override. This delay
is not applied when the order to enter comfort mode comes from the central management unit. Parameter P48 enables you to
set a timer between 30 mins and 24 h, or to prohibit any comfort override (P48 = 0). This function may be disabled (P48 = 24.5).
- If P48 = 24: the setpoint overrides are not stored upon return to standby mode. The current fan speed is not memorized and
returns to AUTO.
- If P48 = 24.5: the setpoint overrides are stored in all operating scenarios. The current fan speed is not memorized and returns
to AUTO.
●Operating mode activated by standby button
According to parameter P47, pressing the standby button switches between comfort and frost protection, or between comfort and
economy, or between comfort and standby.
In all cases, the central management unit maintains the option of selecting each of these operating modes.
●Electric heater operation limiting according to outdoor temperature
The controller can limit operation of the electric heater according to the outdoor temperature, once the comfort temperature has
been reached.
To do so, the base outdoor temperature must be defined (P62), the minimum temperature reachable at least 5 times in the course
of a normal winter.
The outdoor temperature information must come from the BMS via the KNX bus.
●Management of heat exchanger coils
Parameter P67 indicates to the controller whether it has at its disposal a hydraulic coil and electric heater, one of the hydraulic
coils only or an electric heater only.
Certain central management units modify this parameter to temporarily prohibit use of certain coils according to external events
(thermodynamic unit switched off, need to limit electrical energy consumption…).
To get a better understanding of what is going on, diagnostic d13 recalls the value of P67 and d12 indicates the current status
following any action by the central management unit. Depending on what is defined in P67 and what the central management
unit requests (see d12), the regulator determines whether it can have hydraulic coils and electric heaters.
Diagnostic d11:
- If the controller is working based on its changeover sensor wired to S2 and C, d11 indicates the temperature read by this sensor.
- If the controller is working based on an On-off contact wired to S2 and C, or based on information from the centralised changeover
- d11 indicates 127°C if D2/C is shunted or centralised changeover = hot water.
- d11 indicates -72°C if D2/C is not shunted or centralised changeover = cold water.
Diagnostic d12:
Certain central management units may temporarily prohibit heating or air conditioning operation.
Diagnostic d12 will tell you the current authorisations.
Frost protection is enabled even if no heating authorisation has been activated by the supervision.
Very important: the sensor should be placed on the water inlet pipe. It must be installed on the pipe before being insulated
.
9 - CONTROL ALGORITHM
EN
EN - 11 EN7515935-00

●Universal inputs
The V3000 controller is equipped with 2 congurable potential free inputs. These 2 inputs D1-C and D2-C are delivered from the
factory with a bridge. If you want to connect contacts to the inputs (frame contact for example), the bridges must be removed.
- Universal input D1
This input can be congured using parameters P49 and P51
- P49: Action direction of contact, NO or NC
- P51: Enables you to slave controller operation to contact opening or closure, with the possible set-up below:
- 0: Inactive
- 1: Window contact comfort → Frost protection (local override impossible)
- 2: Presence contact comfort → Eco (local override impossible)
- 3: Presence contact comfort → Standby (local override impossible)
- 4: Condensate pump alarm: fan coil unit switched off and cold valve closed
- 5: Fan unit motor alarm: Complete fan coil unit shutdown
- 6: General alarm: Complete fan coil unit shutdown
- 7: Air quality information: enables you to send via the bus a "low air quality" signal to the room. An On-Off controller output
may be synchronised with this information.
- 8: Clock for switching Comfort → Eco (local override authorised)
- 9: Clock for switching Comfort → Standby (local override authorised)
- Universal input D2
This input can be congured using parameters P50 and P52
- P50: Action direction of contact, NO or NC
- P52: Enables you to slave controller operation to contact opening or closure, with the possible set-up below
- 0: Inactive
- 1: Window contact comfort → Frost protection (local override impossible)
- 2: Presence contact comfort → Eco (local override impossible)
- 3: Presence contact comfort → Standby (local override impossible)
- 4: Condensate pump alarm: fan coil unit switched off and cold valve closed
- 5: Fan unit motor alarm: Complete fan coil unit shutdown
- 6: General alarm: Complete fan coil unit shutdown
- 7: Clock for switching Comfort → Eco (local override authorised)
- 8: Clock for switching Comfort → Standby (local override authorised)
- 9: Air quality information: enables you to send via the bus a "low air quality" signal to the room. An On-Off controller output
may be synchronised with this information.
- 10: Frost protection for "Fresh air": fan coil unit switched off, with hot valve 100 % opened
Note regarding D1 and D2:
- Make sure that the settings of inputs D1 and D2 are always different (to avoid any risk of conict between identical values on
two different inputs).
Parameters P51 or P52
Frame contact to be wired to input D1-C or D2-C, according to your device's conguration (refer to the corresponding wiring
diagram).
C
D1
Regulator
Window
contact
The cable used has a maximum length of 10 m, and minimum section of 0.9 mm². It is recommended to use a twisted and shielded
cable.
Note: the window contact must be insulated from earth. If there is shielding present, it must be connected to the fan coil unit earth
- Direction of window contact
- If the window is open and the controller has a display terminal, this will display "_ _ _" instead of the temperature.
N.B: - When the window re-closes, the unit restarts automatically
- The terminal display will return to "normal" after 10 seconds, the synchronisation time between it and the controller
10 - CONNECTING THE FRAME CONTACT
EN7515935-00 EN - 12

●Diagnostic d05, d06
The fresh air function can be carried out in various ways:
- Ambient temperature control with supply air series (all fresh air):
The room temperature measurement must be taken with the sensor of a terminal located in the room.
In Comfort mode, the controller applies PID room control with all fresh air; but if the supply air temperature drops below the supply
air setpoint (set via parameter P09) while the room control is in neutral zone or heating sequence, then the control switches to
supply air control cycle with a proportional algorithm.
In winter, this function prevents the cold shower effect, a source of discomfort, by supplying preheated fresh air even if no heat
gain is required in the room. In cooling mode, the supply air control is locked.
If the hot valve opens fully, or if the frost protection thermostat is triggered (given by P52 = 10), the valve closes and the fan is
switched off immediately.
If the unit has a display terminal, the "Fro" information is displayed when the Frost protection is triggered by the safety thermostat.
An adjustable spanner appears upon the "hot valve 100 % open" safety mechanism being triggered.
- Supply air temperature control (all fresh air):
The V3000 regulates with a Proportional algorithm so that the measured supply air temperature tends towards the setpoints
(P02 or P03).
If the hot valve opens fully, or if the frost protection thermostat (given by P52 = 10), the valve closes and the fan is switched off
immediately.
If the unit has a display terminal, the "Fro" information is displayed upon the Frost protection being triggered by the safety
thermostat. An adjustable spanner appears upon the "cold valve 100 % open" safety mechanism being triggered.
11 - FRESH AIR
Parameters P00 and conguration procedure:
●Diagnostic d01 and d02
The V3000 may perform the master/slave function via 3 different ways:
M
aster/slave by hot/cold authorisation (P00 =1 on master, P00 = 2 on slaves). Each controller works according to its own
temperature measurement. A slave can only heat if the master is heating. A slave can only cool if the master is cooling.
This function can take into account local temperature variations inside the same room.
Master/slave by measured T°C mirror effect (P00 = 1 on the master, P00 = 3 on the slaves) The master sends its own
temperature measurement to all slaves. All the devices in the room therefore work with an identical measurement.
Master/slave by actuator position mirror effect (P00 = 1 on the master, P00 = 4 on the slaves), the master sends the position of
its outputs to all the slaves. All the devices in the room therefore work with the same outputs position (valves, electric heater,
fan).
NOTE:
Do not use this configuration when there are units in the same room which are
:
- A different size, and
- Equipped with HEE motors (and therefore have different speed thresholds)
- In this case, use the configuration P00=3 on the slaves.
In these 3 cases, the temperature setpoints, and the operating mode are the same on all the devices of the same master/slave
function.
With regards to the ventilation speeds, the first 2 authorise different speeds on the master and corresponding slaves if the
Auto position is selected on the master.
The master/slave function is performed directly, with no need for the presence of a central management unit. It is sufficient to
have a KNX supply and a bus meeting the KNX specifications (see Manual NA 08.51):
- The bus must be fed by a standardised KNX supply.
- Use KNX certified cables
- Wiring diagram (see manual NA 08.34)
12 - MASTER / SLAVE FUNCTION
EN
EN - 13 EN7515935-00

●Configuration method for Master/Slave operation
The connection bus between the controllers must meet the KNX specifications and be fed by a KNX supply.
This configuration is performed using a wall-mounted display terminal (using 2 display terminals is advised).
Before configuring, all controllers connected to the KNX bus must be switched on (even if they are not affected by the master/
slave).
1 - Case of a Master unit with 1 slave:
a) Start with the master
- Set parameter P00 to 1.
- To switch to configurator mode press buttons for 5 seconds, and the CnF menu will be displayed.
- Press for 5 seconds until the display "Add 1" flashes.
b) Go on to the slave
- Perform the same operation as above, setting parameter P00 to 2, 3 or 4 beforehand, according to the chosen slave type.
c) The configuration takes around 1 min to 1.5 mins. It is completely finished when the fixed display "Add 0" appears
d) To return to normal display, press
e)
If the display "Err" appears, an error has occurred
Check:
- The bus wiring
- Its supply
- Parameter P00 on the master and slave
and restart the operation
Configuration on SLAVE on MASTER
Step 1
Set P00 on the master via the
3 buttons
(see ccessing Parameters paragraph)
Pco = 1
Step 2 Access the "CnF" menu on the Maste
/ for 5 s
Switch the Master to configuration
- for 5 s
- "Add x" flashes
Step 3
Set P00 on the slave via the
3 buttons
(see "Accessing Parameters" paragraph)
P00 = 2 – 3 or 4
depending on the chosen
slave type
Step 4 Access the "CnF" menu on the Slavee
/ for 5 s
Switch the Slave to configuration
- for 5 s
- "Add x" flashes
Step 5 Wait 1 min to 1.5 mins Configuration step displayed,
from Add 1to Add 6
Configuration step displayed,
from Add 1to Add 6.
Step 6 End of configuration if: "Add 0"
Fixed display
"Add 0"
Fixed display
Step 7 Configuration successful Button to exit CnF menu
EN7515935-00 EN - 14

2 - Case of a Master unit with several slaves:
- 1 master must be associated with 1 slave only
- This must therefore be repeated as many times as there are slaves
- Perform the same operation as in
paragraph 1
with the first slave
.
- Do the same operation as in paragraph 1 with all other slaves associated with this mastere.
- Starting from the 2nd slave configuration lasts 30 seconds to 1 minute
Note: Allow a maximum of 15 slaves for 1 master unit.
3 - Verify configuration via diagnostics d01 and d02
- d01 relates to the master
- d01 gives the address of the master on the bus, for instance: 1
- d02 relates to the slave
- d02 enables you to check which master is associated with the queried slave. All slaves with their d02 at 1 are associated
with master no.1.
Deconfiguring a Master/Slave loop
a)
Start with the slave
- To switch to configurator mode, press buttons for 5 seconds.
- Press for 5 seconds until the display "dEL" flashes.
b)
Go on to the master
- Perform the same operation as above
c) Configuration takes between 30 seconds and 1 min (approximately). It is completely finished when "dEL 0" goes back to
being fixed.
d) To return to normal display, press
e) If the display "Err" appears, an error has occurred
Check:
- The bus wiring
- Its power supply
- Parameter P00 on the master and slave
and restart the operation
Configuration on SLAVE on MASTER
Step 1 - Access the "CnF" menu on the Slave
/ for 5 s
witch the Slave to deconfiguration
- for 5 s
- "dEL" flashes
Step 2 - Access the "CnF" menu on the Master
/ for 5 s
Switch the Master to deconfiguration
- for 5 s
- "dEL" flashes
Step 3 Wait 30 s to 1 min "dEL 6"
flashes
"dEL 4"
flashes
Step 4 End of deconfiguration if: "dEL 0"
Fixed display
"dEL 0"
Fixed display
Step 5 Deconfiguration successful Button to exit CnF menu
EN
EN - 15 EN7515935-00

25
49
150.4
LR3 batteries
compartment
Label
The radio-frequency remote control can only be used with a radio receiver built into the terminal unit.
This remote control enables you to remote control (up to 10 m range) a fan coil unit equipped with a radio-frequency receiver.
This radio-frequency receiver is tted in the factory on the terminal unit. Its design enables it to be put in the room itself, if
necessary.
The features and use of this remote control are the same as for the user display terminal.
The receiver and remote control periodically exchange information (return air temperature value, setpoint value, ventilation
speed…).
These exchanges may take longer than with a wire terminal and need a few seconds.
Batteries: the V3000 system CIAT remote control operates with 2 LR03 alkaline batteries (provided). It is advised that these
batteries are replaced once a year. (depending on the use).
●Configuration of the remote control with its radio-frequency receiver
If the remote control is not associated with its radio receiver (in this case the remote control displays CF1):
- Upon switching on, the radio-frequency receiver LED ashes rapidly.
- If this is not the case, the radio-frequency receiver has already been congured. In this case, refer beforehand to paragraph
“Removing links” below.
- Switch the radio receiver to conguration mode, pressing its button for 3 seconds until the green LED starts ashing more
slowly.
- On the remote control:
- Remove the insulation tab on the batteries to switch it on.
- The display will then be "CF1" (Configuration Menu).
- If "CF1" does not appear, enter the configuration menu, holding the 2 buttons and or 5 seconds.
- "CF1" means that no radio receiver is associated with the remote control.
- Then on the remote control press the button until "Add 1" appears on the screen.
- The rest of the conguration is performed automatically (around 5 seconds).
- When conguration is complete, the remote control display returns to its normal screen (temperature display…).
- The LED on the radio receiver goes out.
Note 1:
The remote control may not return to its normal display, but may return to the "CF" conguration menu:
- If CF2 is displayed, the pairing process has been completed correctly. Allow the remote control to go to standby before
using it.
- If CF1 is displayed, the pairing process has failed; it is therefore necessary to restart the pairing process by clearing any links
created previously (see the paragraph entitled "deleting links between the remote control and the receiver").
Note 2:
* The LED on the radio receiver is lit once it receives an order from its associated remote control.
* Once congured, the button on the radio receiver enables you to start/stop the fan coil unit on which it is tted.
13 - RADIO-FREQUENCY REMOTE CONTROL (SET-UP)
EN7515935-00 EN - 16

In parallel, the symbol displayed on the remote control reacts according to the fan coil unit status. This enables you to check
that the receiver and its remote control have been "coupled".
To remove links between a remote control and a receiver already associated.
Switch the radio receiver to conguration mode, pressing and holding its button for around 10 s, until the LED starts ashing
rapidly. "Decoupling" is executed automatically
Then on the remote control, enter "cong" mode by pressing the ventilation , and standby , buttons simultaneously, until
"CF2" is displayed on the screen.
Press the button until the remote control displays "del".
The rest of deconguration is executed automatically.
When deconguration is complete, the display will return to "CF1".
●Using the radio remote control
After 30 seconds without use, the remote control will go into standby (display switches off) so as to save the batteries.
To "wake" the remote control, press any button.
A horizontal dotted line (-----) ashes on the screen while the remote control synchronises with its receiver (this will take a few
seconds).
●Battery replacement message
If the message "bAt" appears for a few seconds (instead of the ashing dotted line mentioned above) when the remote control is
woken up from standby mode, replace the batteries.
●Master/Slave configuration with the radio-frequency remote control::
1) The KNX bus is present between the Master and Slaves, in this case the configuration procedure is the same as that
described on page 13.
2) No bus is wired between the Master and Slave, in this case it is possible to control up to 8 terminal units with a single remote
control (each terminal unit must be equipped with a radio-frequency receiver).
To configure
- Set P00 to 0 on all the controllers in the master/slave loop (default factory setting).
- Initially, congure the remote control with the 1st radio receiver, as per the procedure described above.
- This radio receiver thereby becomes the "master", and it will indicate to the remote control all information necessary for its
operation.
- Switch receiver no.2 (slave) to "coupling", making it ash slowly using button (hold for around 3 seconds).
- Enter the remote control Conguration menu (button or ) for 6 seconds)
- The display turns to CF2: this means that the master is correctly congured and that you can congure a slave.
- Press : "Add 2"
- The conguration is executed automatically.
- At the end of the conguration: the remote control returns to its normal display and the receiver LED goes off.
- Restart the operation for the other slaves, up to a maximum of 6 terminal units.
Removing links between a remote control and several receivers:
- Start by "decoupling" all the radio receivers by pressing their respective buttons for more than 10 seconds (LED ashing
rapidly). Deconguration is automatic.
- On the remote control enter the conguration menu ( and for 5 seconds) until "CF2" is displayed.
Press , "dEL" appears.
- Wait until the display turns to "CF1"
- All of the receivers and the remote control are "decongured"
Wiring of window contacts (CF), presence contacts on inputs D1/C to D2/C in case of Master/Slave configuration without
KNX bus.
V3000
D1 C
V3000
D1 CD1 C
CF
1
CF
2
V3000 V3000
D1 C
V3000
D1 CD1 C
CF
1
CF
2
Radio receiver Radio receiver Radio receiver
MASTER SLAVE SLAVE
Important: he correct polarities (D1 to D1 and C to C for all controllers)
EN
EN - 17 EN7515935-00

a) Blank terminal
b) Wall-mounted dial terminal
14 - TECHNICAL SPECIFICATIONS
EN7515935-00 EN - 18
Table of contents
Other CIAT Control Unit manuals
Popular Control Unit manuals by other brands

Conductrix Wampfler
Conductrix Wampfler 0832 installation instructions

Trenz Electronic
Trenz Electronic TE0790 manual

AVR
AVR AT90USB162 manual

Honeywell
Honeywell Esser 8044 Series Installation instruction

Roger Technology
Roger Technology H70/101AC Instructions and Recomendations for the Installer

Sundance Spas
Sundance Spas SMT351 user manual