CLA-VAL 34 Series Owner's manual

Electronic Actuator for 34 Series Pilot Controls
34 Series
MODEL
INSTALLATION / OPERATION / MAINTENANCE
Electronic Actuator for 34 Series Pilot Controls
Thank you for purchasing a 34 Series Electronic Actuated
Pilto Control. With proper maintenance, the actuator will perform
indefinitely and provide very accurate and reliable valve control. It
is built with the latest technology utilizing the highest quality com-
ponents.
34 Series Controls
The 34 Series Actuated Pilot Controls for 300 Series Valves
consist of a hydraulic pilot subassembly and 130VC-3 Actuator.
The Cla-Val Model CD S-34, CRA-34, CRD-34, CMC-34, and
CRL-34 pilot controls are factory set to full adjustment range of the
pilot subassembly. The 34 Series Actuator accepts a 4 - 20 mA
remote command set point or dry contact closure and positions
spring-loaded hydraulic pilot subassembly as it maintains set point
of pressure or flow rate. The pilot subassembly is automatically lin-
ear between the limit settings.
34 Series Control Operation
A.) The 34 Series actuator allows 34 Series Controls to be
used in valve remote control applications where a simple change
of pilot set-point is needed. SCADA instrumentation provides set-
point control and verification communication based on this scale.
The actuator can also be controlled by simple contact closure.
B.) Other suitable valve remote control applications are
where 4 - 20 mA command input signal is calibrated to specific
high and low range values. SCADA instrumentation provides set-
point control and verification communication based on system
dynamic conditions and valve’s re-ranged scale. Using a laptop
computer, the 34 Series actuator is calibrated in the field to specific
minimum and maximum pressure or flow control settings that are
in direct proportion to 4 - 20 mA command signal. Once values are
established, the valve will be linear between limits and set-point
will not exceed limits throughout the 4 - 20 mA signal range. For
example, when actuator is calibrated to 4 mA = 50 psi to 20 mA =
100 psi, a 12 mA command signal will result in a 75 psi set point.
34 Series Actuator Hardware Set-up
BEFORE running actuator or software program, complete the
following hookup steps:
Use good field wiring practices for low voltage DC analog instrumen-
tation wiring (use 20-gauge twisted pair shielded wire minimum).
Avoid potential ground loops. Avoid over tightening wiring connector
fasteners.
The enclosure is rated IP-68 (similar to NEMA 6P) submersible for
short periods of time. It is not intended for continuous underwater
use. Consult Cla-Val factory technical support if you have questions.
The ten-wire ten meter cable is permanently attached to 34 Series
actuator and should be terminated in suitable junction box or
directly into an above grade RTU or similar device. Care should be
used when attaching to wires to avoid damage. Installation of suit-
able protection from lightning is highly recommended.
There are no user serviceable parts inside the actuator and tam-
pering or opening it will void the warranty. The ten-wire actuator
cable is permanently attached. Internal damage not covered by
warranty will occur if cable is removed.
FIELD WIRING STEPS:
Terminate wires only applicable to your application. For example,
minimal wiring requirements for power and remote set point are:
1.) Attach 12 to 24 VDC power to 34 Series Actuator cable.
Black wire is for (-) negative; Red wire is for (+) positive. Provide
minimum 500 mA supply.
2.) Attach 4 to 20 mA analog Remote Command Input (from
SCADA system or loop calibrator) to 34 Series Actuator cable.
Yellow is positive and Grey is negative.
Download Wiring Diagram from website (www.cla-val.com)
3.) After wiring is complete and actuator is powered, it can be
used with 4 - 20 mA remote command input signal scaled to factory
default pilot control adjustment range (Operation A, above).
Troubleshooting Actuator Set-up
1.) The actuator LED will remain red for approximately 30
seconds after power on, and then will switch to green indicating
actuator is OK and that internal start-up test is complete.
2.) The actuator LED blinks red if there is a problem. After
resolving the problem, reset the actuator by turning power off for
ten seconds then on again.
3.) The actuator blinks red and green if still in the calibration
mode. It will be necessary to finish calibration.
Terminal strip not
supplied for
Illustration
purpose only
*DO NOT WIRE 24 VDC POWER
*

Page 2
34 Series Software
For Operation A (above) applications, no changes to the 34
Series control preset values are needed. For Operation B (above)
applications, the 34 Series Software kit is used to ONLY change
factory-set values of: 1) range limits (high and low), 2) rotational
speed of actuator, and 3) loss of signal mode. It is used only for
set-up of 34 Series pilot controls during initial valve start-up or
during valve repair.
Cla-Val 34 Series Software is required to communicate between
your Windows laptop computer and the 34 Series Actuator.
Required is the free software program, a special multi-USB con-
nector cable, and these instructions. The software is obtained by
downloading from our website. Only one cable is needed to work
with all 34 Series Actuators. Replacement cables (p/n
20519203A) can be ordered at extra cost. Do not use this soft-
ware for remote control of 34 Series Actuator.
Software Download Instructions
Supported Operating Systems are Windows XP and XP Service Pack 2
1) Go to Cla-Val website (www.cla-val.com) and navigate to
34 Series actuator software download page. Click the
Download 130VC-3 Range Software button to start the
download.
2) Do one of the following:
_ To start the installation immediately, click RUN to run
this program from its current location.
_ To copy the download to your computer for installation
at a later time, click SAVE to save this program.
3) This program will automatically be installed in new e-Drive
folder in C: Program Files/Cla-Val folder on your computer.
A new Cla-Val folder is created in Program Files folder and
an "e-Drive" icon link is created on Desktop to start program.
34 Series Actuator and Software Set-up
Change 34 Series Actuator configuration from factory default set-
tings, by using free download software from website (www.cla-
val.com). To set up a communication link with 34 Series Actuator,
first install software and cable driver and then special USB commu-
nications cable in laptop computer. After installing driver and com-
munication cable, the actuator must be powered for link to work.
Follow hardware set-up and wiring diagram instructions. Your com-
puter must be on before powering the actuator.
ardware set-up steps must be completed before program will
communicate and change 34 Series factory default settings. Until
wiring and power connections are made to the actuator, the soft-
ware program can be opened, but new parameters can not be cre-
ated or stored or sent to actuator. Changes to parameters must be
done "live" and while control valve is operating.
Cla-Val multi- SB Driver Setup
When 34 Series communications cable is installed in your laptop
computer USB port for the first time, Windows will search your
computer for the cable multi-USB driver. If Windows Plug-and-
Play does not automatically find the driver and connect to actuator,
then the cable driver must be set-up manually. Please refer to doc-
ument “N-USB Cable Driver Install” instructions to manually acti-
vate the cable driver.
Download multi-USB software from the Cla-Val web site:
www.cla-val.com
Opening Software
When the “e-Drive” desktop icon is clicked, the Actuator List will be
displayed, which can contain multiple listing of the actuators.
If the actuator is not connected to the laptop, the window will be
empty but can be used to view the software to become familiarized
with the different windows. Click the “cancel “ button to launch the
software
If connected to one or more actuators, click on "View All" and
select the actuator you would like to communicate with from the
list then click once on left mouse button.
Product name, Firmware version and serial number are displayed.
Starting Actuator Software
First, be sure hardware set-up and wiring to actuator is complet-
ed. Connect laptop computer to actuator using special multi-USB
cable. Be sure computer is on and actuator is powered. Check
that Actuator LED is steady green. The first window to appear will
be display.

.
Page 3
Display
1 Start the e-Drive / CPC CLA-VAL software.
2 Select the e-Drive in the e-Line list.
3 Select language and click "Read parameters".
4 The right side will display specific configuration information. Also general information including the date of
latest calibration, the average & total working time since the first power up, the number of starts, the serial
number, the firmware version and the maximum and minimum recorded temperature is displayed.
5 Click on continuous reading to see the position of e-Drive, set point (mA) and, if used feedback position
(mA and units).
6 To manually change the setting, write the setting and click on "Override Set point".
CA TION: Improper use of "Override Set point" may cause damage to your system

Calibration - Static and Dynamic
Before beginning the calibration process, determine if it is actual-
ly necessary! The actuator, if new, has been factory calibrated to
the spring range shown on the pilot and may not require further
calibration (30-300 spring range is calibrated from 40 to 140 psi).
Static calibration
Static calibration is a fast and convenient method of calibrating
the actuator by calculating the 4 and 20 mA values rather than
raise or lower the actual system pressure. Dynamic Calibration
requires that the system pressure is actually raised and lowered
to the system values desired.
The “Set Range” window will launch either Static or Dynamic cali-
bration. When the "Set Range" is activated, the following mes-
sage will be displayed. To continue with calibration, click "OK”, if
not click "Cancel".
1 Select "Static Calibration" Mode. The "CPC Motor"
check box should unchecked (Disabled).
2 Use increase and decrease buttons to put valve in control
of system. This will establish the reference set point.
3 Determine the pilot spring range. (Check nameplate label
on pilot). Get the pressure change per turn per pilot revolu
tion from the spring chart. Calculate the number of turns
between the reference set point and desired low and high
pressures.
4 These numbers are the "Value at 4 mA" and the Value at
20 mA". Numbers must be positive and can have up to 2
decimal places.
5 Enter the low value in set-point window (1).
6 Enter the high value in set-point window (2).
7 Click "Write Set Range" tab to complete actuator to
complete calibration.
Page 4
e-line list
OK
You are going to put the e-Drive / CPC in calibration Mode (Led Blinks Red/Green
X
Cancel
Example:
Valve is in control operating at 45 psi (3 bar).
The desired pressure at 4 mA is 30 psi (2 bar).
The desired pressure at 20 mA is 70 psi (4.8 bar).
From the spring chart, using a 15-75 spring, the pressure per turn is 10.2 psi (0.7 bar). The number of turns to Low set
point is equal to 45 psi (3 bar) minus 30 psi (2 bar) divided by 10.2 psi (0.7 bar) = 1.47 turns. The number of turns to
igh set point is equal to 70 psi (4.82 bar) minus 45 psi (3 bar) divided by 10.2 psi (0.6 bar) = 2.45 turns.
(1)
(2)

1 Press the Set Range tab and select the Dynamic Calibration mode. Uncheck the "CPC Motor".
2 Select Units.
3 Enter the pressure/flow value at 4 mA and at 20 mA.
4 "Low point setting" - Look at the pressure/flow gauge/display and use the " Decrease
5 actuator" button until the low pressure/flow setting is attained.
6 Click on "Low point setting" button to store the value.
7 " igh point setting". Look at the pressure/flow on the gauge/display and use the "Increase actuator" button until the high
pressure/flow setting is attained.
8 Click on the " igh point setting" tab to store value.
9 When all values have been entered, click on "Write Set Range". Dynamic calibration is done.
Configuration
Use the configuration mode to set the rotation speed, dead band and loss of signal values.
1 Rotation speed affects the response time of the valve between set-points. The default condition is 1 second on-time, 5
seconds off-time achieving at rotation speed of 1.2 rpm. Entering a ‘0’ (zero) on time and ‘0’ (zero) off time will achieve a
continuous rotation speed of 6 rpm (maximum speed).
Make sure that the values entered are appropriate to your system to minimize the potential for surge.
2 Dead band - The default value is 0.1 mA. This value can be increased depending on the stability of the of the set point
signal. The actuator is internally isolated however, If the set point is inherently unstable, the actuator can dither. If this
happens, improve the signal or increase the dead band.
3 Choose the loss of set point signal mode:
a. Go to 4 mA: Actuator will default to the 4 mA position (low set point).
b. Last position: Actuator will maintain the last position.
c. Go to 20 mA: Actuator will default to the 20 mA position (high set point).
4 Click on "Write Configuration" button to complete configuration.
Dynamic Calibration
Page 5
When using this method, the system pressures must be changed from the actual minimum to maximum set-point values. If this is not
possible, use "Static Calibration" mode.

“Low Level”
alarm range
“Low Level”
hysteresis alarm value
“Low Level”
alarm value
“ igh Level”
hysteresis alarm value
“ igh Level”
alarm range
“ igh Level”
alarm value
(1)
}
Adjustment of alarms
high and low level and
hysteresis alarm level
Alarms
The actuator has a Low and igh Alarm with an adjustable hysteresis and is activated as shown in the lower window:
Example: 10% Löw alarm = 4 mA + (10% x 16 mA) = 5.6 mA. 90% igh alarm = 4mA + (90% x 16 mA) = 18.4 mA.
Hysteresis
1 ysteresis prevents chattering of the alarms when the set point is very close to the alarm status. It is calculated as follows:
4 mA + (2% x 16 mA) = 0.32 mA. Low alarm hysteresis therefore equals 5.6 mA + 0.32 mA = 5.92 mA. igh alarm
hysteresis equals 18.4 mA - 0.32 mA = 18.08 mA.
2 Enter the requested percentage, for the alarms and hysteresis.
3 Click on "Test" to close or open your contact relay.
4 Click on "Write Alarms" button to complete.
/ CPC
Connect
Information
Firmware Version
Series N
Last Modification
Number of Starts
Complete working time (s)
Average working Time (s)
°C/°F Max
°C/°F Min
Deadband (mA)
Nb. EoC (L/H)
(6) 1.97
30603001
10.09.2010
20
273
14
28 / 83
24 / 75
0.10
0 / 0
Selected Language--> English
Display
Continuous Reading--> No
Override Setpoint Activated (mA)> No
Set Range
CPC Motor--> No
Selected Units--> PSI - bar
4 mA Output in PSI--> 14.5
4 mA Output in bar--> 1.00
20 mA Output in PSI--> 76.9
20 mA Output in bar--> 5.30
Configuration
Rotation speed On Time (s)--> 1
Rotation speed Off Time (s)--> 5
Deadband (mA)--> 0.10
Loss of signal mode--> Last position
Alarms
High Alarm Active Above (%)--> 90
High Alarm Hysteresys (%)--> 2
Low Alarm Active Below (%)--> 10
Low Alarm Hysteresys (%)--> 2
Configuration
Display AlarmSet Range
Write Configuration
Rotation Speed
On time (S)
Off time (S)
Deadband (mA)
0-3600 secs.
0-3600 secs.
(0.1-20 mA)
1
5
0.10
Rotation Speed
Go to 4 mA
Last position
Go to 20 mA
Message
The rotation speed affects the responce time of the valve
between set-points.
The default conditions is 1 second on-time, 5 seconds off-time
achieving at rotation speed of 1.2 RPM
Warning - Make sure that the values entered are appropriate
to your system to minimise potential for surge
Entering a “0” (zero) ON-TIME and “0” (zero) OFF-TIME
will achieve a continuous rotation speed of 6 RPM
(The maximum speed)
Deadband - The default value is 0.1 mA which may need to be
increased depending on the stability of the electrical signal
Page 6

Troubleshooting FAQ
LED Diagnostics
When power is applied to the actuator, the LED will be red for
approximately 5-30 seconds, and then will change to solid green.
Green
OK.
No light
Check power supply.
Red
igh torque limit has been exceeded - Power down and power up
again
Excessive Voltage has been applied (Above 32 Volts).
Blinking red/green
Calibration was not completed - recalibrate
Changing set-point without a 4-20 mA command signal
with the SB cable connected to
Go to ‘Display’ tab and select Milliamp value and check the box to
activate.
Changing set-point without a command signal without
an e-Drive - SB cable.
Refer to wiring diagram.
To Increase Actuator connect the Purple Wire with the Pink.
To Decrease Actuator connect the turquoise Wire with the Pink.
To Increase or Decrease the actuator without 4-20 mA
signal.
Refer to wiring diagram in the this manual. To increase actuator
connect the purple wire to the pink. To decrease actuator, connect
the turquoise wire to the pink.
What are the default settings for the 34 Series actuator?
Factory default setting for 34 Series Actuator range parameter is
the full pilot spring range scaled to match the 4 to 20 mA Remote
Command Input analog signal. Factory default setting for 34 Series
Actuator rotation speed is one rpm with 24 VDC power.
How do I get the software to work with the actuator?
To set up a link with 34 Series Actuator, first install cable driver and
then the special multi-USB communications cable. After installing
driver and communication cable, the Actuator must be powered for
link to work. Follow wiring diagram and hardware hookup instruc-
tions. Download Wiring Diagram from website (www.cla-val.com).
How do I install Special SB Communication Cable?
When communications cable is installed in your laptop computer
USB port for the first time, Windows will search your computer for
the cable USB driver. If Windows Plug and Play does not automat-
ically find the driver and connect to actuator, then the cable driver
must be set up manually. Windows will take you step-by-step
through the manual set up process. The cable USB driver is
installed during software download. You will have to browse to the
Cla-Val folder created during download where the driver file is
located. Details are in this manual.
My computer does not have a SB port
Older laptop computers with only Serial port may have a problem
using USB to Serial adapter with special USB connector cable and
communicating with 34 Series actuator. Make sure the USB to
Serial adapter cable is less than 18 inches long. Also, USB exten-
sion cables should not be used because they will degrade signals
and cause problems. If problem persists, consult Cla-Val factory
technical support.
Why is actuator LED still blinking red/green after I
downloaded the settings?
Once the calibration mode button is activated, all steps must be
done before downloading is begun. Actuator LED will show green
when downloading is successful and complete.
Can I make a file ahead of time and download it to
34 Series later?
All hardware hookup steps must be completed before program will
communicate and change 34 Series parameters. Until wiring and
power connections are made to the actuator, this program can be
opened, but new parameters can not be created or stored or sent
to the actuator. Changes to parameters must be done "live" and
while control valve is operating. Actuator LED will show green
when downloading is successful and complete.
-
GENERAL DISCLAIMER
In accordance with our policy of continuous development and
improvement, CLA-VAL reserves the right to modify or improve its
products at any time without prior notice. CLA-VAL assumes no lia-
bility or responsibility for any errors or omissions in the content of
this document.
Page 7

CLA-VAL EUROPE
Chemin des Mésanges 1
CH-1032 Romanel/
Lausanne, Switzerland
Phone: 41-21-643-15-55
Fax: 41-21-643-15-50
E-mail: [email protected]
CLA-VAL FRANCE
Porte du Grand Lyon 1
ZAC du Champ du Périer
France - 01700 Neyron
Phone: 33-4-72-25-92-93
Fax: 33-4-72-25-04-17
E-mail: [email protected]
CLA-VAL
1701 Placentia Avenue •Costa Mesa, CA 92627
800-942-6326 Fax: 949-548-5441 Web Site: cla-val.com E-mail: [email protected]
©COPYRIGHT CLA-VAL 2017 Printed in USA Specifications subject to change without notice.
CLA-VAL CANADA
4687 Christie Drive
Beamsville, Ontario
Canada L0R 1B4
Phone: 905-563-4963
Fax: 905-563-4040
CLA-VAL UK
Dainton House, Goods Station Road
Tunbridge Wells
Kent TN1 2 DH England
Phone: 44-1892-514-400
Fax: 44-1892-543-423
E-mail: [email protected]
N-34 Series (R-10/2017)
Other manuals for 34 Series
1
This manual suits for next models
5
Table of contents
Other CLA-VAL Controllers manuals

CLA-VAL
CLA-VAL CF1 Series Owner's manual

CLA-VAL
CLA-VAL CDS7-DO Instruction manual

CLA-VAL
CLA-VAL CF1-C1 User manual

CLA-VAL
CLA-VAL e-Drive-34 User manual

CLA-VAL
CLA-VAL CDS6 Owner's manual

CLA-VAL
CLA-VAL VC12 User manual

CLA-VAL
CLA-VAL CRL Instruction manual

CLA-VAL
CLA-VAL D35 User manual

CLA-VAL
CLA-VAL VC-22D User manual

CLA-VAL
CLA-VAL CRL-60 Instruction manual