CLA-VAL 90G-21 Instruction manual

UL Listed Pilot-Operated Pressure Control
INSTALLATION / OPERATION / MAINTENANCE
90G-21/90A-21 UL
MODEL
The Cla-Val 90-21 Pressure Reducing Valve is a pilot-operated regulator,
capable of holding downstream pressure to a predetermined pressure.
1. SPECIAL NOTE:For system protection, on valve sizes 1-1/2" thru 8" a
UL Listed minimum 1/2" pressure relief valve shall be installed down-
stream (system side) of the 90-21 Pressure Reducing Valve. For valve
sizes 10" and 12" a UL Listed 3" or larger relief valve shall be installed
downstream side of the 90-21. Adequate drainage of the relief valve dis-
charge must be provided. The relief valve should be set above the “no
flow” or “dead end” shutoff pressure which is at 2 to 8 psi higher than the
90-21 set pressure for 1-1/2" thru 8" valve sizes and 2 psi for 10" and 12"
valve sizes.
2. Allow sufficient room around the valve assembly to make adjustments
and for disassembly.
3. It is recommended that isolation valves be installed on both ends of the
90-21 valve to facilitate isolating the valve for start-up, testing and preven-
tative maintenance.
4. BEFORE THE VALVE IS INSTALLED, PIPE LINES SHOULD BE
FLUSHED OF ALL CHIPS, SCALE, AND FOREIGN MATTER.
5. Place the 90-21 valve in line with flow through the valve in the direction
indicated on the nameplate. Check all fittings and hardware for proper
makeup and that no apparent damage is evident.
6. Cla-Val valves operate with maximum efficiency when mounted in hori-
zontal piping with the cover UP; however, other positions are acceptable.
Due to size and weight of cover and internal components of six inch and
larger valves, installation with the cover up is advisable. This makes peri-
odic inspection of internal parts readily accessible.
7. Installation, testing, inspection and maintenance shall be in accordance
with NFPA 13, 14 and 25.
Start-Up and Adjustment
1. Upon initial start-up and after any valve servicing, it is necessary to fol-
low these steps.
2. Prior to pressurizing the valve make sure the necessary gauges to
measure pressure are installed. Gauges should be installed upstream
(inlet) and downstream (outlet) of the valve. Unused ports on main valve
body can be used for this purpose.
CAUTION: During start-up and test procedures a large volume of water
may be discharged downstream. Check to make sure that the downstream
venting is adequate to prevent damage to personnel and equipment.
3. Close upstream and downstream isolation valves.
4. Slowly open the upstream isolation valve enough to allow the valve and
pilot control system to fill with liquid.
5. Bleed air from the main valve (1) cover and pilot system by slightly loos-
ening fittings or plugs at all high points until a steady flow of water is
observed retighten. It may be necessary to do this more than once.
6. Open fully the upstream isolation valve.
7. Slowly open the downstream isolation valve part way to establish a low
flow rate.
There must be liquid flowing through the valve during pressure
adjustments.
Optimum valve performance occurs when pressure setting is done with
flow rate as low as practical.
8.
Adjust the CRD Control (3) to desired pressure. To change pressure setting,
turn the adjusting screw in (clockwise) to increase outlet pressure. Turn the
adjusting screw out (counterclockwise) to decrease outlet pressure.
The pres-
sure should change approximately 27 psi per turn. Only slight changes in
adjustment should be made to avoid damage to equipment. When the
desired setting has been made, tighten jam nut and replace cover.
9. To fine tune the operation of the main valve, an oscillation control device
is included but may not be necessary. Adjust screw clockwise/counter-
clockwise until system pressures stabilize.
10. For 1-1/2" thru 8" 90-21 Pressure Reducing Valves the downstream
pressure relief control recommended set point is 2-8 psi above the CRD
(3) set point. For 10" and 12" 90-21 Pressure Reducing Valves the set
point is 2 psi above the CRD (3) set point. The relief valve for the 10" and
12" 90-21 shall be installed a recommended minimum 6 pipe diameters
downstream of the 90-21
11. Pressure ratings of components installed downstream of the Model 90-21
pilot operated pressure control valve shall not be exceeded.
12. Valves shall be tested after installation in accordance with NFPA 13 or
NFPA 14 or both NFPA 13 and 14, whichever is applicable, and tested peri-
odically thereafter in accordance with NFPA 25.
Maintenance
1. The Cla-Val 90-21 Pressure Reducing Valve requires no lubrication or
packing and a minimum of maintenance. However, a periodic inspection
schedule should be established to determine how the fluid handled is
affecting the efficiency of the valve. Minimum of once per year.
2. When servicing the pilot control system, use care to prevent damage. If
it is necessary to remove fittings or components, be sure they are kept
clean and replaced exactly as they were.
3. Repair and maintenance procedures of the Cla-Val Hytrol Main Valve
and pilot control components are included in a more detailed IOM manual.
It can be downloaded from our web site (www.cla-val.com) or obtained by
contacting a Cla-Val Regional Sales Office.
4. When ordering parts always refer to the catalog number and stock
number on the valve nameplate.
Main valve
fails to open
Main valve
fails to close
Fails to
Regulate
No pressure at valve inlet
Main valve diaphragm assembly
inoperative
Pilot Valve (CRD) not opening:
1. No. spring compression
2. Damaged spring
3. Spring guide not in place
4. Yoke dragging on inlet nozzle
Foreign matter between disc
and seat or worn disc. Scale on
stem or Diaphragm ruptured
Flow Clean Strainer plugged
Pilot Valve (CRD) remain open:
1. Spring compressed solid
2. Mechanical obstruction
3. Worn disc
4. Yoke dragging on inlet nozzle
5. Diaphragm damaged or loose
diaphragm nut. Leakage from
vent hole in cover
Air in main valve cover and/or
tubing
Pilot Valve (CRD) yoke dragging
on inlet nozzle
Check inlet pressure
Disassemble, clean and polish
stem, replace detective parts
1. Tighten adjusting screw
2. Disassemble and replace
3. Assemble properly.
4. Assemble properly
Disassemble main valve,
remove matter, clean parts and
replace defective parts
Remove and clean or replace
1. Back off adjusting screw
2. Disassemble and remove
obstruction
3. Disassemble remove and
replace disc retainer assembly
4. Assemble properly
5. Disassemble. replace
diaphragm and/or tighten nut
Loosen top cover plug and fit-
tings and bleed air
Assemble properly
SYMPTOM PROBABLE CAUSE REMEDY
LISTED
Valve Size Minimum Differential Pressure
1-1/2" 20 psid
2" - 8" 10 psid
10" 20 psid
12" 45 psid
X58C (2) X46A (4)
5
6
*SUGGESTED
REPAIR PARTS
For a more detailed IOM Manual go to www.cla-val.com or contact a Cla-Val Regional Sales Office.
CLA-VAL
Copyright Cla-Val 2021 Printed in USA Specifications subject to change without notice.
1701 Placentia Ave •Costa Mesa CA 92627 Phone: 949-722-4800 •E-mail: [email protected] •www.cla-val.com
©
N-90-21 UL (R-10/2020)
90-21 UL SCHEMATIC
CRD (3)
COVER
PIPE PLU
G
COVER BEARING
SPRING
STEM NUT
DIAPHRAGM WASHER
DISCRETAINER
BODY
*
SPACER WASHERS
DISCGUIDE
SEAT
PIPE PLUG
STEM
SEAT O-RING
STUD
8" and Larger
*
DIAPHRAGM
*
DISC
*
RepairParts
SeatScrew
8" and Larger
(Globe
or
Angle)
PIPE PLUG
HEX NUT
8" and Larger
Cover Bolt
6" and Smaller
FLAT WASHER
FLAT WASHER
HYTROL MAIN VALVE (1)
inlet
Cover vent
(3/8" NPT)
Cap
Adjusting Screw
Jam Nut
Cover
Spring
Hex Nut
Belleville Washer
Diaphragm Washer
Diaphragm*
Yoke
Body and Seat Assy
Disc Retainer Assy
Gasket*
Plug, Body
*Machine Screw
(Fil.Hd) 8 Req’d
Spring Guide
Pressure Setting
Adjusting Screw
(Turn Clockwise to
Increase Setting)
Tube Connector
(NPT)
Restriction
Plug
Orifice
Minimum Recommended Flow When Setting Pressure
*Maximum obtainable flow for UL LLC Operational testing was
1600 gpm for the 10" Valve and 1200 gpm for the 12" Valve
X140-1
Security Cap
Option
BASIC COMPONENTS
1 100-01 Hytrol (Main Valve)
2 X58C Restriction Fitting
3 CRD Pressure Reducing Control
4 X46A Flow Clean Strainer
5 CV Flow Control (opening)
6 Relief Valve
OPTIONAL FEATURES
P X141 Pressure Gauge
D CDC Check Valve
P1 & P2
CV
X58C (2)
Valve Size Orifice Dia.
1-1/2" - 3" .094"
4" - 8" .125"
10" .156"
12" .188"
Valve Size (inch) Min. Flow (GPM)
Max. Intended Flow (GPM)
1-1/2 40 110
2 45 196
2-1/2 50 306
3 57 441
4 100 783
6 220 1763
8 390 3133
10 620 4896*
12 880 7050*

This manual suits for next models

1

Other CLA-VAL Controllers manuals

CLA-VAL CRL-60 Instruction manual

CLA-VAL

CLA-VAL CRL-60 Instruction manual

CLA-VAL PC-22D Instruction manual

CLA-VAL

CLA-VAL PC-22D Instruction manual

CLA-VAL 130VC-2 Owner's manual

CLA-VAL

CLA-VAL 130VC-2 Owner's manual

CLA-VAL CDS7-DO Instruction manual

CLA-VAL

CLA-VAL CDS7-DO Instruction manual

CLA-VAL CPC Owner's manual

CLA-VAL

CLA-VAL CPC Owner's manual

CLA-VAL CRD-34 User manual

CLA-VAL

CLA-VAL CRD-34 User manual

CLA-VAL VC-22D User manual

CLA-VAL

CLA-VAL VC-22D User manual

CLA-VAL D35 User manual

CLA-VAL

CLA-VAL D35 User manual

CLA-VAL CF1-C1 User manual

CLA-VAL

CLA-VAL CF1-C1 User manual

CLA-VAL VC-22D User manual

CLA-VAL

CLA-VAL VC-22D User manual

CLA-VAL CRL Instruction manual

CLA-VAL

CLA-VAL CRL Instruction manual

CLA-VAL VC12 User manual

CLA-VAL

CLA-VAL VC12 User manual

CLA-VAL CF1 Series Owner's manual

CLA-VAL

CLA-VAL CF1 Series Owner's manual

CLA-VAL 34 Series Owner's manual

CLA-VAL

CLA-VAL 34 Series Owner's manual

CLA-VAL e-Drive-34 User manual

CLA-VAL

CLA-VAL e-Drive-34 User manual

CLA-VAL CDS6 Owner's manual

CLA-VAL

CLA-VAL CDS6 Owner's manual

Popular Controllers manuals by other brands

Tekmar Mixing Control 354 Data brochure

Tekmar

Tekmar Mixing Control 354 Data brochure

Osram SLC manual

Osram

Osram SLC manual

Swagelok KHF Series Maintenance instructions

Swagelok

Swagelok KHF Series Maintenance instructions

Centurion D3 quick guide

Centurion

Centurion D3 quick guide

Linear Technology Analog Devices LTM4622A datasheet

Linear Technology

Linear Technology Analog Devices LTM4622A datasheet

Evco EVD HP Installer manual

Evco

Evco EVD HP Installer manual

Siemens RWF 50.2 Installation, use and maintenance instructions

Siemens

Siemens RWF 50.2 Installation, use and maintenance instructions

ELREHA TAR 1380 quick start guide

ELREHA

ELREHA TAR 1380 quick start guide

Conrad SPC-1 operating instructions

Conrad

Conrad SPC-1 operating instructions

Zero Zone Carel Programming instructions

Zero Zone

Zero Zone Carel Programming instructions

Shibaura COMPO ARM BA-III Series instruction manual

Shibaura

Shibaura COMPO ARM BA-III Series instruction manual

nekos SKY 450 instruction manual

nekos

nekos SKY 450 instruction manual

Regada Rematic UMR 1PA-Ex Installation, service and maintenance instructions

Regada

Regada Rematic UMR 1PA-Ex Installation, service and maintenance instructions

Elvox EA20 instruction manual

Elvox

Elvox EA20 instruction manual

MOTECK CIS3 user guide

MOTECK

MOTECK CIS3 user guide

ascon G2 Series user manual

ascon

ascon G2 Series user manual

Linear Technology LT8391EFE Demo Manual

Linear Technology

Linear Technology LT8391EFE Demo Manual

TMK SP 100CW Installation and operation manual

TMK

TMK SP 100CW Installation and operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.