InteliNanoNT MRS 3 Operator Guide, ©ComAp –July 2017
9
3.2.2 Inactive warning
When a warning becomes inactive, O04 Alarm and O15 Common Warning output will open, the red
LED above STOP button will stop blinking, and the warning symbol on main screen will go out.
Figure 3.5
inactive warning –Low Battery
3.3 Shutdowns
3.3.1 Shutdown procedure
The InteliNanoNT controller opens outputs O05 GCB Close/Open, O01 Starter, O08 Prestart and
O02 Fuel Solenoid and closes O03 Stop Solenoid to stop the engine immediately. O04 Alarm and
O16 Common Shutdown outputs are closed. Active or not confirmed shutdowns are blocking next
start of gen-set.
3.3.2 Active unconfirmed shutdown
When a shutdown occurs, the Shutdown procedure will start, the red LED above STOP button
blinks, the shutdown symbol will blink in the upper right corner of LCD, and the proper shutdown
symbol is displayed in history with running hours stamp. The record in history is inversed, see Figure
3.6.For shutdown alarm confirmation press STOP button.
Figure 3.6
active unconfirmed shutdown –Emergency Stop
3.3.3 Active confirmed shutdown
When an active shutdown is confirmed the red LED above the STOP button stops blinking. The record
in history stays inversed with confirmation symbol at the end. O04 Alarm and O16 Common
Shutdown outputs are open.
Figure 3.7
active confirmed shutdown –Emergency Stop
3.3.4 Inactive unconfirmed shutdown
O04 Alarm and O16 Common Shutdowno utputs are closed, red LED above STOP button blinks.
Shutdown symbol is displayed in upper-right corner of the LCD, and proper warning symbol is
displayed in history with running hours stamp. See Figure 3.8.For shutdown alarm confirmation press
STOP button.
Figure 3.8
inactive unconfirmed shutdown –Emergency Stop