Remarks:
Please note that devices inside the power supply might fail when
voltage of more than rated output voltage is applied to output ter-
minal of the power supply. This could happen when the customer
tests the overvoltage performance of the unit.
4.5 Thermal protection
¡When it exceeds the Derating (Section 6.5), the thermal protection
will be activated and simultaneously shut down the output.
When the thermal protection is activated, shut off the input voltage
and eliminate all the overheating conditions. To recover the output
voltage, keep enough time to cool down the power supply before
turning on the input voltage again.
4.6 Remote ON/OFF
¿-R1
¡Remote ON/OFF is possible by applying a voltage between RC1
and RC2 pin. External DC power source is necessary to operate
remote control.
External current limiting resistor Rrc is necessary.
¡When power supply shut off by over voltage protection or
overheating protection, it can be recovered by toggling Remote
ON/OFF signal.
No. ITEM RC1, RC2
1 Function Output is OFF in ”L”
2 Base pin RC2
3 Output ON SW OPEN
(0.5V max, 0.1mA max)
4 Output OFF SW SHORT
(5mA typ, 3mA min)
¡Sink current of RC1 must be kept up to 12mA.
RC1150
RC2
12mA max
Rrc
OUTSIDE OF TUNS INSIDE OF TUNS
Vrc
SW
VfN1.0V
Fig .4.1 RC Connection Example
*Please be careful not to connect RC1 and RC2 opposite.
It may cause a failure of power supply.
¡Remote ON/OFF circuit (RC1, RC2) is isolated from the input and
output and FG.
¿-R2
¡”-R2” can reduce standby power than “-R1”.
¡The usage is same as option “-R1”.
Please refer to option “-R1”
0.5Wtyp (AC100V), 1.2Wtyp (AC200V)
(3) TFR1 : Inrush current limiting resistor 4.7ohm - 22ohm
¡Connect a resistor between R pin and +BC pin for inrush cur-
rent protection. The surge capacity is required for TFR1, please
contact component mfg. Wirewound resistor with thermal cut-offs
type is required.
4 Function
4.1 Input voltage range
¡The input voltage range is from 85 VAC to 264 VAC.
¡In cases that conform with safety standard, input voltage range is
AC100-AC240V(50/60Hz).
¡Be aware that use of voltages other than those listed above may
cause damage. Avoid square waveform input voltage, commonly
used in UPS units and inverters.
4.2 Overcurrent protection
¿TUNS300F/TUNS700F
¡Overcurrent protection is built-in and comes into effect at over
105% of the rated current.
Overcurrent protection prevents the unit from short circuit and
overcurrent condition. The unit automatically recovers when the
fault condition is cleared.
¡When the output voltage drops at overcurrent, the average output
current is reduced by intermittent operation of power supply.
¿TUNS500F
¡Overcurrent protection is built-in and comes into effect at over
101% of the peak current.
Overcurrent protection prevents the unit from short circuit and
overcurrent condition. The unit automatically recovers when the
fault condition is cleared.
¡When the output voltage drops at overcurrent, the average output
current is reduced by intermittent operation of power supply.
4.3 Peak current protection
¿TUNS500F
¡Peak current protection is built-in. When the power supply is op-
erated at over peak load based on section 7 (Peak current), this
function comes into effect and reduce the output.
¡A few seconds later, a unit automatically recovers. But if the over-
current condition has not been released, the output will reduced
again (intermittent operation mode).
4.4 Overvoltage protection
¡Overvoltage protection circuit is built-in. If the overvoltage protec-
tion circuit is activated, shut down the input voltage, wait more
than 3 minutes and turn on the AC input again to recover the out-
put voltage. Recovery time varies depending on such factors as
input voltage value at the time of the operation.
TUNS300F, TUNS500F, TUNS700F
AC-DC Power Supplies Bus Converter.Power Module Type
Instruction Manual
TUNS-23
TUNS