COZY DVCF403C-H User manual

DIRECT VENT
COUNTERFLOW
WALL FURNACE
Installation and Operating Instructions
ENGLISH
Click here for the full manual or
click on the links below to quickly
locate what you’re looking for:
ESPAÑOL
Haga clic aquí para ver el manual
completo o haga clic en los
siguientes enlaces para localizar
rápidamente lo que está buscando:
FRANÇAIS
Cliquez ici pour le manuel complet
ou cliquez sur les liens ci-dessous
pour localiser rapidement ce que
vous recherchez:
1018028-A_webcvr
Antes de la Instalación
Estándares .......................................... 2
Especicaciones y Dimensiones ......... 3
Introducción ........................................ 3
Reglas de Seguridad ...................... 3 - 4
Desfogue ............................................. 4
Espacios Libres .............................. 5 - 6
Ubicaciones ......................................... 7
Instalación
Instrucciones Generales ................. 7 - 8
Ubicar abertura de Ventilación ............ 8
Conexión de Gas ................................. 8
Instalación del Termostato ................... 8
Instrucciones de Encendido ......... 9 - 10
Mantenimiento
Instrucciones de mantenimiento ........ 11
Ajuste piloto ....................................... 11
Eliminación de quemadores .............. 12
Gráco de llamas
y oricios del quemador ..................... 12
Diagramas de cableado .............. 12 - 13
Kits:
14-PEK
Kit de extensión ............................. 14
31300-A
Kit de acabado de gabinete .......... 15
306SR-A y 30SRB-A
Kits de descarga lateral ................ 16
Cuadros de solución
de problemas .............................. 17 - 19
Lista de Piezas ........................... 20 - 23
Garantía ............................................. 24
Avant l’installation
Normes ................................................ 2
Spécications et dimensions ............... 3
Introduction .......................................... 3
Règles de sécurité .......................... 3 - 4
Desfogue ............................................. 4
Espace libre .................................... 5 - 6
Emplacements ..................................... 7
Installation
Instructions générales .................... 7 - 8
Localiser l’ouverture de ventilation ...... 8
Raccordement au gaz ......................... 8
Installation du thermostat .................... 8
Instructions d’allumage ................. 9 - 10
Maintenance
Instructions de maintenance .............. 11
Réglage du pilote ............................... 11
Élimination des brûleurs .................... 12
Tableau de amme
et les trous du brûleur ........................ 12
Schémas de câblage .................. 12 - 13
Kits:
14-PEK
Kit d’extension .............................. 14
31300-A
Kit de nition de l’armoire ............. 15
306SR-A et 30SRB-A
Kits de déchargement latéral ........ 16
Tables de solution
des problèmes ............................ 17 - 19
DVCF Liste des pièces ............... 20 - 23
Garantie ............................................. 24
Before Installation
Standards ............................................ 2
Specications ...................................... 3
Introduction ......................................... 3
Venting ................................................. 4
Safety ............................................. 3 - 4
Clearances ..................................... 5 - 6
Locations ............................................. 7
Installation
Rough-In Instructions ..................... 7 - 8
Locate Vent Opening ........................... 8
Gas Connection ................................... 8
Thermostat Installation ........................ 8
Lighting Instructions ...................... 9 - 10
Maintenance
Maintenance Instructions ................... 11
Pilot Adjustment ................................. 11
Burner Removal ................................. 12
Burner Flame
& Orice Chart ................................... 12
Wiring Diagrams ......................... 12 - 13
Kits:
14-PEK
Extension Kit ................................. 14
31300-A
Cabinet Trim Kit ........................... 15
306SR-A & 30SRB-A:
Side Discharge Kits ..................... 16
Troubleshooting Charts .............. 17 - 19
DVCF Part List ............................ 20 - 23
Warranty ............................................ 24

1018028-A
Page 1
—Donotstoreorusegasolineorotherammablevapors
andliquidsinthevicinityofthisoranyotherappliance.
— WHAT TO DO IF YOU SMELL GAS
•Donottrytolightanyappliance.
•Donottouchanyelectricalswitch;donotuseany
phoneinyourbuilding.
•Immediatelycallyourgassupplierfromaneighbor’s
phone.Followthegassupplier’sinstructions.
•Ifyoucannotreachyourgassupplier,callthere
department.
—Installationandservicemustbeperformedbyaqualied
installer,serviceagencyorthegassupplier.
!WARNING:Iftheinformationintheseinstructions
isnotfollowedexactly,areorexplosionmayresult
causingpropertydamage,personalinjuryorlossoflife.
INSTALLER:Leavethismanualwiththeappliance.
CONSUMER:Retainthismanualforfuturereference.
DIRECT VENT
COUNTERFLOW
WALL FURNACE
Installation and OperatingInstructions
Cozy Heating Systems, LLC | cozyheaters.com | 855-589-5380 | 3230 Industrial Pkwy | Jeffersonville, IN 47130
performed by a qualied service agency. DO NOT attempt any of these procedures if you are not qualied as this could expose you to
property damage, personal injury, or loss of life and will invalidate all warranties.
- This unit is for residential use only and is not approved for installation in greenhouses, or environments involving dusty, wet, corrosive,
or explosive conditions. Such conditions will invalidate the warranty and may create unsafe conditions.
- The appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not
prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certied kit is used.
- The coating selected to provide
longer life to the heat exchanger
may smoke slightly upon initial
ring. Please provide adequate
ventilation if this occurs.
- Installation, maintenance, service,
troubleshooting & repairs must be
NATURAL GAS - DVCF403C-H, DVCF553C-H, DVCF407C-H, DVCF557C-H
PROPANE GAS - DVCF404C-H, DVCF554C-H, DVCF408C-H, DVCF558C-H
DVCF55
DVCF40
WARNING: Operation of this furnace without the properly installed, furnished vent system and vent cap could result in Carbon
Monoxide (CO) poisoning and possible death. For your safety, this furnace and the vent system should be inspected at least
annually by a qualified service technician.

1018028-A
Page 2
CONTENTS
BeforeInstallation
Standards ........................................... 2
Specications ..................................... 3
Introduction ........................................ 3
Venting ............................................... 4
Safety ............................................. 3 -4
Clearances ..................................... 5 -5
Locations ............................................ 7
Installation
Rough-In Instructions ...................... 7 -8
Locate Vent Opening .......................... 8
Gas Connection .................................. 8
Thermostat Installation ....................... 8
Lighting Instructions ...................... 9 -10
Maintenance
Maintenance Instructions .................. 11
Pilot Adjustment ................................ 11
Burner Removal ................................ 12
Burner Flame & Orice Chart ............ 12
Wiring Diagrams ......................... 12 -13
Kits:
• 14-PEK Extension Kit ........................ 14
• 31300-A Cabinet Trim Kit ................. 15
• 306SR-A & 30SRB-A:
Side Discharge Kits .......................... 16
Troubleshooting Charts ............... 17 -19
Parts
DVCF Part List ............................ 20 -23
Warranty ............................................. 24
TheStateofMassachusettsrequiresthatinstallation
andserviceofagasappliancebeperformedbya
plumberorgastterlicensedintheCommonwealthof
Massachusetts.
These installation instructions are a general guide and do not
supersede applicable local codes and ordinances. Before planning
or making the installation be sure it complies with all phases of the
local heating code. (Or, in the absence of local codes, with the latest
edition of National Fuel Gas Code, ANSI.Z223.1, or CAN1-B149).
The appliance, when installed, must be electrically grounded in
accordance with local codes, or in the absence of local codes, with
the latest edition of National Electrical Code ANSI / NFPA 70, or
Canadian Electrical Code CSA-C22.1.
All of the ANSI and NFPA standards referred to in these installation
instructions are the ones that were applicable at the time the design
of this appliance was certified.
The design of this appliance was certified to comply with the latest
edition of ANSI Z21.86 and CSA 2.32.
Installer must leave these instructions with the consumer, have
them complete, and return the warranty card.
READ CAREFULLY BEFORE INSTALLING UNIT
NFPA Standards:
NATIONAL FIRE PROTECTION
ASSOCIATION
1 Batterymarch Park
Quincy, Massachusetts | USA 02169-7471
ANSI & Canadian Standards:
CSA GROUP
178 Rexdale Boulevard,
Toronto, Ontario | Canada M9W 1R3

1018028-A
Page 3
Your Direct Vent Counterow Wall Furnace is shipped in two cartons. One carton contains the furnace, thermostat, thermostat
wire and insulated staples. The second carton will have the vent tube, air intake tube and vent cap assembly. After the
furnace has been removed from the carton check the rating plate to verify that the model number is correct and that the wall
furnace is equipped with the type gas you intend to use.
SPECIFICATIONS & DIMENSIONS
MODEL NUMBERS
DVCF403C-H DVCF407C-H
DVCF553C-H
DVCF557C-H
DVCF404C-H
DVCF408C-H
DVCF554C-H
DVCF558C-H
Gas Type Natural Propane
Height 78 - 5/8” 87 - 5/16” 78 - 5/8” 87 - 5/16”
Width 14 - 5/16” 14 - 5/16” 14 - 5/16” 14 - 5/16”
Depth 11 - 3/4” 11 - 3/4” 11 - 3/4” 11 - 3/4”
Input (BTU / HR) 40,000 55,000 40,000 55,000
Gas Inlet 1/2” 1/2” 1/2” 1/2”
CFM 320 440 320 440
Type Control 24 Volt 24 Volt 24 Volt 24 Volt
Blower Speed 1 1 1 1
Approx. Shipping Weight 130 lbs 144 lbs 130 lbs 144 lbs
Amps 1.95 2.2 3.05 3.3 1.95 2.25 3.05 3.35
Intermittent Ignition (IID) - IID - IID - IID - IID
READ THESE INSTALLATION AND OPERATING INSTRUCTIONS CAREFULLY BEFORE YOU INSTALL OR ATTEMPT TO USE
THIS DIRECT VENT COUNTERFLOW WALL FURNACE. IF YOU DO NOT UNDERSTAND ANY PART OF THE INSTRUCTIONS,
CONSULT LOCAL AUTHORITIES, A QUALIFIED INSTALLER, SERVICE TECHNICIAN OR THE GAS SUPPLIER. FAILURE TO
READ OR UNDERSTAND THESE INSTRUCTIONS CAN RESULT IN MALFUNCTION, INEFFICIENT OPERATION, PROPERTY
DAMAGE, SERIOUS INJURY OR DEATH.
1. This appliance must be installed in accordance with local
codes, if any; if not, follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or the Natural Gas and Propane Installation
Code, CSA-B149.1.
2. Follow all applicable local codes and ordinances. If there are
none, follow the latest edition of the National Fuel Gas Code,
ANSI Z21.86. A copy may be obtained from the National Fire
ProtectionAssociation;1 Batterymarch Park; Quincy, MA,
02269. In Canada, see the current CAN1-B149 installation
code, available from the CSA Group; 178 Rexdale Boulevard;
Toronto, Ontario; Canada M9W 1R3.
3. The appliance, when installed, must be electrically grounded
in accordance with local codes or, in the absence of local codes,
with the latest edition of National Electrical Code, ANSI/NFPA70.
In Canada, see the current CSA C22.2 Canadian Electrical Code,
available from International Approval Services, 178 Rexdale
Boulevard, Etobicoke, Ontario, Canada M9W 1R3.
4. Do not install this furnace in a recreational vehicle or trailer.
5. Do not operate this furnace unless it is connected to the
supplied vent system with vent cap in place. Do not attempt
to extend vent pipes. 12 inches is maximum length.
6. Never use a match, candle, ame or other source of ignition to
check for gas leaks. Use only soapy water or liquid detergent.
7. Before cleaning or servicing, turn off the gas and allow furnace
to cool.
8. Do not operate furnace without grilles and front panel in place.
9. Due to high temperatures, locate furnace out of trafc and
away from furniture and drapes.
10. Children and adults should be alerted to the hazard of high
surface temperature and should be kept away to avoid
burns or clothing ignition.
11. Young children should be carefully supervised when they
are in the same room with the furnace.
12. Do not place clothing or other ammable material on or near
the furnace.
13. Installation and repair should be done by a qualied service
INTRODUCTION
SAFETY

1018028-A
Page 4
SAFETY - Continued
VENTING
1) Seal any unused openings in the venting system.
2) Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA54 or the Natural Gas and Propane Installation
Code, CSA B149.1 and these instructions. Determine that
there is no blockage or restriction, leakage, corrosion and
other deciencies which could cause an unsafe condition.
3) As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
4) Close replace dampers.
5) Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operating
at maximum speed. Do not operate a summer exhaust fan.
6) Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7) Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main burner
operation. Use the ame of a match or candle.
8) If improper venting is observed during any of the above
tests, the venting system must be corrected in accordance
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or Natural Gas and Propane Installation Code, CSA
B149.1.
9) After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows, exhaust
fans, replace dampers and any other gas-red burning
appliance to their previous conditions of use.
!WARNING: CARBON MONOXIDE POISONING HAZARD
Failuretofollowthestepsoutlinedbelowforeachapplianceconnectedtotheventingsystembeingplacedinto
operationcouldresultincarbonmonoxidepoisoningordeath.
The following steps shall be followed for each appliance connected to the venting system being placed into operation,
while all other appliances connected to the venting system are not in operation:
technician. The furnace should be inspected before use and
at least annually by a professional service technician. More
frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative that control
compartments, burners, and circulating air passageways of
the furnace be kept clean.
14. Do not put anything around the furnace or vent cap that will
obstruct the ow of combustion and ventilation air.
15. When installing the furnace allow adequate accessibility
clearances for servicing and proper operation. (See gure 1 on
page 5).
16. The wall furnace should be located near the center of the area
to be heated for optimal heat distribution. If the wall furnace
is installed directly on carpeting, tile or any combustible
material other than wood ooring, the wall furnace shall be
installed on a metal plate or wood panel secured to the oor,
extending the full width and depth of the wall furnace. If a
side register kit is to be installed, see Page 16.
17. Do not use this heater if any part has been under water.
Immediately call a qualied service technician to inspect the
heater and to replace any part of the control system which
has been under water.
18. For your safety, this furnace is equipped with a manual
reset auxiliary limit switch. In case of failure by the primary
limit switch, this switch will shut the valve down completely
before unsafe temperatures are reached. After a cool down
period, switch must be manually reset. If outages persist,
call a qualied service person.
19. Side discharge kit boots must not exceed 10 inches.
20. Locate the auxiliary limit switch and push in the red reset
button. This will reset the switch in case it accidentally
opened during shipping.

1018028-A
Page 5
CLEARANCES
E
D
B
FIXED
CLOSED FIXED
CLOSED
OPERABLE
C
H
B
B
B
B
F
B
AJ
I
M
K
OPERABLE
Clearance in
accordance with local
installation codes &
requirements of the
gas supplier
AClearance above grade, veranda, porch, deck, or balcony
E Clearance to unventilated soft
CClearance to permanently closed window
GClearance to inside corner
IClearance to service regulator vent outlet
BClearance to window or door that may be opened
FClearance to outside corner
JClearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other appliance.
K Clearance to a mechanical air supply inlet
H Clearance to each side of center line extended above
meter/regulator assembly
MClearance under veranda, porch, deck, or balcony
D Vertical clearance to ventilated soft located above the
terminal within a horizontal distance of 2 Feet (61 cm)
from the center line of the terminal
LClearance above paved sidewalk or paved driveway
located on public property
12 Inches (30 cm)
24 Inches (61 cm)
12 Inches (30 cm)
12 Inches (30 cm)
3 Feet (91 cm)
12 Inches (30 cm)
12 Inches (30 cm)
12 Inches (30 cm)
6 Feet (1.83 m)
3 Feet (91 cm) within a
height 15 Feet (4.5m) above the
meter / regulator assembly
12 Inches (30 cm)
permitted only if veranda, porch,
deck, or balcony is fully open on a
minimum of two sides.
18 Inches (46 cm)
7 Feet (2.13m) A vent shall not
terminate directly above a sidewalk
or paved driveway that is located
between two single family dwellings
and serves both dwellings.
12 Inches (30 cm)
24 Inches (61 cm)
9” (23 cm)
12 Inches (30 cm)
9” (23 cm) 12” (30 cm)
12” (30 cm)
12 Inches (30 cm)
9” (23 cm) 12” (30 cm)
3 Feet (91 cm) above if within
10 Feet (3 m) horizontally
Clearance in accordance
with local installation codes &
requirements of the gas supplier
18 Inches (46 cm)
REFERENCE LETTER TO DRAWING
CANADIAN
INSTALLATIONS* U.S.INSTALLATIONS**
DVCF40 DVCF55
G
A
Inside
Corner
Detail
*In accordance with the current CSA-B149.1
Natural Gas and Propane Installation Code
**In aaccordance with the current ANSI
Z223.1 / NFPA 54 National Fuel Gas Code
= Air Supply Inlet
= Vent Terminal
= Area where terminal is
not permitted

1018028-A
Page 6
CLEARANCES - Continued
1. MINIMUM CLEARANCES
• Side Wall: Min. Clearance = 4”
(See Fig. 1) NOTE: The unit may be recessed and rest directly
against side studs and the inside surface of the rear wall.
• Ceiling: Min. Clearance = 4”
(See Fig. 1)
• Floor: Min. Clearance = 0”
(See Fig. 1)
• FromtheSideoftheVentCaptoAnyProtruding
ObstructionsorCorners: Min. Clearance = 12”
(See Fig. 2b)
• FromanyWindowtotheSideoftheVentCap
DVCF553C, 554C, 557C and 558C
FIG. 2-B
12”
Min.
12”
Min.
24” Minimum
12” Minimum
DVCF403C, 404C, 407C and 408C
FIG. 2-A
9”
Min.
12”
Min.
24” Minimum
12” Minimum
2. RESIDENTIAL GARAGE INSTALLATION:
Gas utilization equipment in residential garages shall be
installed so that all burners and burner ignition devices are
located not less than 18 inches (46 cm) above the oor. Such
equipment shall be located, or protected so it is not subject
to damage by a moving vehicle. Use care in selecting a good
location within the garage.
• DO NOT locate the appliance where heated air will
be directed onto a nearby parked vehicle.
• Paint may discolor or rubber
may harden and crack.
• DO NOT allow heated discharge air to blow directly
onto open or closed containers of paint, gasoline or
other liquids having ammable vapors.
DVCF403,404,
407,&408C
DVCF553,554,
557&558C
Min. Clearance = 9”
(See Figure 2)
Min. Clearance = 12”
(See Figure 2b)
• FromanyOverhangingProjectiontoTopofVentCap
Min. Clearance = 24”
(See Figure 2)
CEILING
4” Minimum
4” Minimum
SIDE
WALL
FLOOR 0”
FIG. 1

1018028-A
Page 7
FIG. 5
LOCATIONS
1. This furnace must be installed on an outside wall and vented to the
outside. If possible, this wall should be on the side of the house that
receives the least amount of wind since strong gusting winds could
cause pilot outage.
2. For most efcient performance, locate furnace as centrally as
possible in the area to be heated.
3. The furnace can be installed ush against a wall or recessed up to
10” maximum. For proper combustion, make sure unit is level front
to back and side-to-side.
4. Do not install the furnace in a closet, alcove or small hallway where
the furnace could be isolated from the space to be heated by closing
a door.
5. Be sure the vent cap will have the proper clearances.
(See Figure 2a)
6. Check inside the wall to make sure there are no obstacles such
as water pipes, electric wiring, etc. which could interfere with the
installation of the furnace or vent tubes.
7. Be sure to maintain adequate accessibility clearances for servicing
and proper operation.
8. If the furnace is installed in a basement, a 12” clearance must be
maintained between ground level and the bottom of the vent cap. Do
not install furnace where vent cap will terminate in a window well or
any other opening below ground level.
INSTALLATION
ELECTRICAL ROUGH-IN
For convenience, this furnace is equipped with a three-prong power cord
located on the top left of heater. The 115V wiring should be brought in
on the left side terminating in a receptacle box (not provided). Consult
local codes or ordinances. (For Amps, see Page 3 / Specications and
Dimensions).
ROUGH-IN GAS SUPPLY
Install a 1/2 inch diameter gas supply line. The gas line can enter the
cabinet through the right side or bottom (See Figure 3). The gas line
must have an individual manual shut off valve. Also, you must install a
drip leg and provide a 1/8” N.P.T. plugged tapping, accessible for test
gauge connection, immediately upstream of the gas supply connection
to the furnace (See Figure 4).
The furnace and its individual shut off valve must be disconnected from
the gas supply piping system during any pressure testing of that system
at test pressures in excess of ½ psig (3.5kPa). The furnace must be
isolated from the gas supply piping system by closing its individual
manual shut off valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than ½ psig (3.5kPa).
2-5/8”
3-1/2”
1-1/2” OA
FIG. 3
TO HEATER GAS
CONTROL VALVE
MANUAL CUT-OFF VALVE
DRIP LEG
1/8” NPT
PRESSURE TAP
GAS
SUPPLY
LINE
FIG. 4
WALL
STUDS
DVCF40 - 59”
DVCF55-68-1/2”
FINISHED
FLOOR
9-1/4
DIA.

1018028-A
Page 8
INSTALLATION
LOCATE VENT OPENING
After the location of the heater has been determined, the opening
for the vent pipe should be cut. If the heater is to be recessed, cut
out opening for heater between studs on the interior wall and cut out
the oor plate between the studs, so heater will set at on oor as all
dimensions are given from a nished oor. The height of the cut out
for a 40,000 BTU model is 78-5/8”, for the 55,000 models the cut out
height is 87-5/16”. NOTE: This dimension may be increased to allow
more room for installation and making the wiring connection, then
renished.
Next, cut out a 9-1/4” opening in exterior wall for the vent tubes to
pass through. The center of opening for the 40,000 BTU furnace is
59”, the center for opening for 55,000 BTU furnace is 68-1/2”. See
Figure 5, on Page 6.
If the heater is to be surfaced mounted, cut out 9-1/4” opening
through the interior and exterior wall. The center of cut out will be 59”
for 40,000 BTU and 68-1/2” for 55,000 BTU models. Be sure both
cutouts are level with each other.
INSTALLING THE FURNACE
The vent system supplied with this furnace will accommodate walls ¾”
(when recessed) up to 12” thick. Use only the exhaust tube, air intake
tube and vent cap supplied with heater. Do not attempt to lengthen
the exhaust or air intake tubes, this could cause an imbalance in the
heater resulting in poor performance and pilot outage (See Figure 6).
Measure exact distance “X” between surface on which back of cabinet
will rest (inside of recessed cavity or face of wall when freestanding)
and the outside wall surface (see Figure 6).
GAS CONNECTION
Make the gas connection between the manual shut off valve
and the furnace gas control valve with approved ½” connectors.
Compounds used on threaded joints of gas piping shall be approved
for use with Propane gas. The gas lines must be checked for leaks
by the installer with soapy water or liquid detergent, never use
an open ame. If connections are not exposed, a pressure test
must be run. Be sure to disconnect the gas supply line from the
appliance valve before pressure testing. The manifold pressure is
pre-set at the factory and should be 3.5” w.c. for Natural Gas and
10” w.c. for Propane Gas. The minimum inlet pressure for Natural
Gas is 4.5” w.c. and 11” w.c. for Propane Gas, “for purpose of input
adjustment”. The maximum inlet pressure should never exceed
7.0” w.c. on Natural Gas or 14” w.c. on Propane Gas.
THERMOSTAT INSTALLATION
Follow the instructions included with the thermostat. Select a
location for the thermostat on an inside wall approximately 5 feet
above the oor where it won’t be affected by heat or cold sources
such as direct sunlight, televisions, replaces, hidden hot or cold
water pipes, drafts, etc., and a minimum of 4’ from the heater. The
thermostat must never be placed in an adjacent room. Connect
thermostat wires to thermostat and mount to wall. Run wire to
furnace and make connections to thermostat wires coming out of
top of furnace. Use insulated staples (provided) to secure wire to
wall.
OPERATION
This heater is equipped with a slow opening gas control. On a call
for heat the gas valve does not snap-open to full manifold pressure,
but opens with a gradual increase to normal manifold pressure. The
time lapse from the call for heat to normal operating pressure is two
to ve seconds. The slow open feature assures a safe, less noisy
ignition.
After the heat exchanger has warmed sufciently, the fan will
automatically come on to efciently transfer the heat into the room.
INLET AIR TUBE “A” – Measuring from gasketed
surface, mark and cut pipe same as dimension “X”.
Remove any burrs.
VENT EXHAUST TUBE “B” – Measuring from
gasketed surface, mark and cut pipe 1-3/4” greater
than dimension “X”. Remove any burrs.
Fasten vent exhaust tube “B” to heat exchanger collar and Inlet Air
Tube “A” to ange on back of furnace using 16 # 3/8 screws (“C”)
provided. Be sure gaskets are in place and not damaged. Anytime
the vent pipes are removed check and replace gaskets (if necessary).
Failure to replace missing or damaged gaskets may expose
homeowner to life threatening conditions.
Secure furnace in place using 2 holes provided in bottom of casing.
NOTE: Make sure both tubes are centered in cut out. Slide the vent
cap onto the pipes extending from the back of the furnace. A rotating
or twisting motion will ease this installation. Secure vent cap and
vent cap spacer plate to wall causing the vent tubes to have a slight
downward pitch. This will prevent water from entering. Anchors (not
provided) may be required. Caulk around vent cap spacer plate with
caulking provided.
NOTE: Some framing may be necessary to provide a at surface
against the vent cap spacer plate and to prevent rain from entering
the wall opening.
FIG. 6
Vent
Cap Vent Cap
Spacer Plate
WALL
“
X
”
OUTSIDE INSIDE
A
C
B
Heat
Exchange
Collar

1018028-A
Page 9
A. This appliance has a pilot which must be
lighted by hand. When lighting the pilot,
follow these instructions exactly.
B. BEFORE LIGHTING smell all around the
appliance area for gas. Be sure to smell next
to the oor because some gas is heavier
than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
• DO NOT touch any electric switch.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
FOR YOUR SAFETY READ BEFORE LIGHTING
MODELS: DVCF403C-H / DVCF404C-H / DVCF553C-H / DVCF554C-H
• If you cannot reach your gas supplier, call
the re department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob
will not push in or turn by hand, don’t try to
repair it, call a qualied service technician.
Force or attempted repair may result in a
re or explosion.
D. Do not use this appliance if any part has
been under water. Immediately call a
qualied service technician to inspect the
appliance and to replace any part of the
control system and any gas control which
has been under water.
6. Wait five (5) minutes to clear out any gas. Then smell
for gas, including near the floor. Ifyousmellgas,
STOP! Follow “B” in the information on the safety
label. If you don’t smell gas, go to the next step.
7. Open sight glass cover.
8. Locate red piezo ignitor button on side of gas control.
Locate pilot behind sight glass. (Follow metal pilot
tube from gas control).
9. Turn gas control knob counterclockwise to
“PILOT”.
LIGHTING INSTRUCTIONS
WARNING:
Ifyoudonot
followthese
instructions
exactly,are
orexplosion
mayresult
causing
property
damage,
personal
injuryorloss
oflife.
LIGHTING INSTRUCTIONS
TURNING OFF GAS TO APPLIANCE
1. STOP! Read the information on the safety label.
2. Set thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. Remove lower front panel.
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
1. Turn thermostat to it’s lowest setting.
2. Turn off all electric power to the appliance if service
is to be performed.
3. Remove lower front panel.
4. Push in gas control knob slightly and turn clockwise
to “OFF”. Do not force.
5. Replace lower front panel.
10. Push in pilot control knob and hold in. Immediately
begin a series of pushing and releasing the red
piezo ignitor button, while observing the pilot through
the sight glass. Continue to spark until pilot is lit.
Continue to hold the pilot control knob in for about
one (1) minute after the pilot is lit. Release the pilot
control knob and it will pop back up. Pilot should
remain lit. If pilot goes out, repeat steps 4 thru 9.
- If knob does not pop up when released, STOP and
immediately call your service technician or gas supplier.
- If the pilot will not stay lit after several tries, turn the gas
control knob to “OFF” and call your service technician
or gas supplier.
11. Close sight glass cover.
12. Turn gas control knob counterclockwise to “ON.”
13. Replace lower front panel.
14. Turn on all electric to the appliance.
15. Set thermostat to desired setting.
NOTE:
Knob cannot
be turned from
“PILOT” to “OFF”
unless knob is
pushed in slightly.
Do not force.
Gas Control Knob
Pilot Control Knob

1018028-A
Page 10
A. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do not try to light the pilot by hand.
B. BEFOREOPERATING, smell all around the
appliance area for gas. Be sure to smell next
to the oor because some gas is heavier
than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
• DO NOT touch any electric switch.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
FOR YOUR SAFETY READ BEFORE LIGHTING
MODELS: DVCF407C-H / DVCF408C-H / DVCF557C-H / DVCF558C-H
• If you cannot reach your gas supplier, call
the re department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don’t try to repair
it, call a qualied service technician. Force
or attempted repair may result in a re or
explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualied
service technician to inspect the appliance
and to replace any part of the control system
and any gas control which has been under
water.
7. Wait ve (5) minutes to clear out any gas. Then smell for
gas, including near the oor. Ifyousmellgas,STOP!
Follow “B” in the information on the safety label. If you
don’t smell gas, go to the next step.
LIGHTING INSTRUCTIONS
WARNING:
Ifyoudonot
followthese
instructions
exactly,are
orexplosion
mayresult
causing
property
damage,
personal
injuryorloss
oflife.
LIGHTING INSTRUCTIONS
TURNING OFF GAS TO APPLIANCE
1. STOP! Read the information on the safety label.
2. Set thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which
automatically lights the pilot. DO NOT try to light the pilot
by hand.
5. Remove lower front panel.
6. Push in gas control knob slightly & turn clockwise
to “OFF”.
1. Turn thermostat to it’s lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Remove lower front panel.
4. Push in gas control knob slightly and turn clockwise
to “OFF”. Do not force.
5. Replace lower front panel.
9. Replace lower front panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions
“TO TURN OFF GAS TO APPLIANCE” and call your
service technician or gas supplier.
8. Turn gas control knob counterclockwise to “ON”.
NOTE:
Knob cannot be
turned to “OFF”
unless knob is
pushed in slightly.
Do not force.
Gas Control Knob
Gas Control Knob

1018028-A
Page 11
FIG. 9
MAINTENANCE
PILOT ADJUSTMENT
1. Locate the pilot adjustment screw on
the valve.
2. The pilot ame should surround at
least the top 3/8” of the powerpile
(pilot generator) or ame sensor (see
Figure 8).
The pilot is unregulated so it will be
operating at inlet line pressure (Max.
7” w.c. for Natural Gas and 11” w.c. for
Propane).
MANUAL RESET SWITCH
For your safety this furnace is equipped
with a manual reset limit switch. In case
of failure by the primary limit switch, this
switch will shut the valve down completely
before unsafe temperatures are reached.
After a cool down period, switch must be
manually reset. If outages persist, call a
qualied service person.
TO DECREASE
THE PILOT FLAME
Turn the screw clockwise.
(Approximately six full turns to bottom of pilot
light channel) until you produce a sufcient
ame at the minimum noise level.
For proper and safe operation, keep furnace and furnace area clean. At regular intervals turn
control valve off, let cool and clean inside control compartment. To clean cabinet, use only
a damp cloth. Do not use any kind of solvent or cleaning uid that could leave a residue or
invisible coating that would burn or give off fumes when furnace is turned on.
Have the furnace checked, cleaned, and repaired by a qualied service technician, including
the vent system, pilot and burner operation prior to use each year.
The bearings of the fan motor should be oiled every twelve (12) months with S.A.E. 20 oil.
(See Figure 7).
Follow a regular service and maintenance schedule for safe and efcient operation.
Examine the venting system as a routine part of the safety performance check on an
annual basis.
OIL
TUBE
FIG. 7
FIG. 8-A Standing Pilot
Pilot flame should envelop 3/8 to
1/2 inch of the tip of sensor.
3/8”-1/2”
FIG. 8-D
Pilot Adjustment Screw
IID Pilot
FIG. 8-C
Pilot Adjustment Screw
Standing Pilot
1-1/2” 3/4”
WARNING: Thisisagas-redappliance.Keeptheareaclearofgasolineandotherammablevapors
andliquids.Allcombustiblematerialmustbekeptclearofthisareatoavoidreorexplosion.
!
FIG. 8-B IID Pilot
Pilot flame should envelop 3/8 to
1/2 inch of the tip of sensor.
3/8”
to
1/2”

1018028-A
Page 12
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper & dangerous operation. Verify
proper operation after servicing.
!
MAINTENANCE
TERMINAL BLOCK WIRING DIAGRAMS
TO REMOVE MAIN BURNER
FOR INSPECTION & CLEANING
1. Turn thermostat to lowest setting and allow
the furnace to cool.
2. Turn off all electric power to furnace.
3. Remove lower grille.
4. Disconnect gas supply to valve.
5. Disconnect wires from gas valve.
6. Remove 15 screws holding burner door to
burner box. Pull door forward to remove
complete burner, gas valve assembly.
7. After inspecting and cleaning, place burner
assembly back into burner box and tighten
15 screws.
NOTE: Be sure door gasket is not damaged
and will effect a proper seal or pilot outage
will occur.
8. Connect wires back to valve.
9. Connect gas supply back to valve.
10. Turn on electric to furnace.
11. Follow lighting instructions, and replace
lower grille.
It is recommended that the furnace and all
components be inspected at least annually by a
qualied service technician. This should include
the burner, pilot, heat exchanger, and vent system.
Be sure that the ow of combustion and ventilation
air is not obstructed.
IMPORTANT: Keep burner & control compartment
clean. Vacuum control compartment at the start of
the heating season and as often as needed.
PROPER BURNER FLAME
The burner ame may be observed by raising the sight glass cover. A proper
ame will have a dark blue inner mantle that sits right on top of the burners with
a lighter blue outer mantle rising above the burner (See Figure 9 on page 11).
There may be some yellow where the pilot ame and burner ame meet. There
is no primary air adjustment on the burner, and proper ame is assured since the
correct manifold pressure and oricing has been done at the factory. NOTE: It
is advised that the burner ames be checked at least twice during the heating
season for any changes in burner ame characteristics.
The appliance area must be kept clear and free from combustible materials,
gasoline, and other ammable vapors and liquids. This appliance is equipped
only for altitudes 0-2,000 feet. Heaters installed above 2,000 feet must be derated
4% for every 1,000 feet. For the proper orice size, nd the Model Number and
elevation on the orice chart. Replace burner orice. Orice change must be
completed by a qualied installer or service technician.
Model Number
0 to
2,000’
2,000’ -
4,000’
4,000’ -
6,000’
6,000’ -
8,000’
8,000’ -
10,000’
NATURAL GAS
FIG 10: Orice Chart for Specic Elevations
DVCF403C .............32 34 35 36 40
DVCF407C .............32 34 35 36 40
DVCF553C ........... 3.6mm 29 30 30 31
DVCF557C ........... 3.6mm 29 30 30 31
DVCF404C .............49 50 51 52 52
DVCF408C .............49 50 51 52 52
DVCF554C .............44 45 47 48 49
DVCF558C .............44 45 47 48 49
PROPANE GAS
ORDERKIT#49840 2287-1 High Altitude Kit
DVCF403,404,407&408(C-H)
91122
Motor (White)
Fan/Limit Switch (Brown)
Motor (Green) Motor (Black)
Power Cord (White)
Power Cord (Black)
Transformer (Black)
Transformer (Black)
Limit
Switch
(Blue)
Terminal
Board
Ground
(Green)
Power
Cord
(Green)
Fan
Switch
(Black)
DVCF553,554,557&558(C-H)
91123
Motor (White)
Fan/Limit Switch (Brown)
Motor (Green) Motor (Black)
Power Cord (Black)
Power Cord (White)
Transformer (Black)
Transformer (Black)
Limit
Switch
(Blue)
Terminal
Board Ground
(Green)
Power Cord
(Green)
Selector
Switch
(Black)
Selector Switch (Red)
Motor (Red)

1018028-A
Page 13
WIRING SCHEMATICS
Standing Pilot Models IID Models
PILOT
PICTORIAL SCHEMATIC
Models Amps
DVCF407C-H .............2.20
DVCF408C-H .............2.25
DVCF557C-H .............3.30
DVCF558C-H .............3.35
See page 22
for a larger
schematic of
the IID.

1018028-A
Page 14
14-PEK:14’PLUGEXTENSIONKIT (For Non-Recessed Installations Only)
UnitswithTerminalBoard
1. Turn heater off following Section 3 in the Lighting Instructions
and allow to cool.
2. Turn off all electricity to heater.
3. Remove top louver assembly, fan shroud and fan blade.
4. Loosen two screws on romex connector.
5. Remove junction box cover plate.
6. Disconnect three power cord terminals and pull power cord out of top of
heater.
7. Insert power cord provided in kit through romex connector and plug onto
terminal board following wiring diagram found in lighting and operating
instructions.
8. Tighten two screws on romex connector.
9. Replace junction box cover plate.
10. Replace fan blade, fan shroud and top louver assembly.
11. Snap 90 degree outside corner (Ref. 1) onto 3 foot section (Ref. 2) plastic
raceway. Insert power cord and remove blue backing from adhesive strip
on raceway and apply to side of heater.
12. Insert power cord into second 3-foot section of raceway (Ref. 3) and
remove blue backing and apply to side of heater, butting up against bottom
of other section.
13. Cut 14-inch long bottom section to required length (see chart), insert
power cord, remove backing and apply to side of heater.
14. Plug power cord into wall receptacle.
15. Light the heater following lighting instructions.
BOTTOM SECTION (4)
90 DEGREE
OUTSIDE
CORNER
(1)
3FT.
SECTION
(2)
3FT.
SECTION
(3)
FIG. 11
DVCF40 5-5/16 Inches NOTE: Lengths terminate approximately 2 inches above oor.
DVCF55 14 Inches NOTE: Lengths terminate approximately 2 inches above oor.
MODELNO. LENGTH OF BOTTOM SECTION (Ref. 4) PLASTIC RACEWAY
CAUTION: These kits must be installed by a qualified installer or service technician.

1018028-A
Page 15
31300-A:CABINETTRIMKIT
FIG. 12-A
UnitswithTerminalBoard
1. Install top ange and secure with two (2) screws.
2. Select one of the remaining side anges and position as shown in
Figure 12-B (below), making sure that the side with holes is held against
the side of the furnace (and that the ange is ush with the bottom of the
top trim piece).
Mark these holes and removed side ange. Drill the marked holes with No.
30 drill bit. Re-position ange and secure with screws provided.
3. Measure from the bottom of the side ange you have just installed to the
oor. Cut one of the remaining side anges to the measurement and install
as in step 2.
Repeat steps 2 and 3 for opposite side of furnace.
48” Long Side Flange ............................Qty. 4 31310
15-1/2” Wide Top Flange ..........................Qty. 1 31320
#8 Phillips Head Screws .........................Qty. 10 50134
TOP
FLANGE
LONG
SIDE
FLANGE
FIG. 12-B
Wall
Trim Kit
Side
Flange
Wall
Stud
Vent
Pipe
FURNACE
Trim
Kit Top
Flange
CAUTION: These kits must be installed by a qualified installer or service technician.
PART DESCRIPTION PARTNO.QUANTITY

1018028-A
Page 16
FIG. 11
ROUGH-INS FOR
SIDE DISCHARGE KITS
Install plaster grounds as shown to the left.
NOTE: When side discharge Kit No. 30SRB is being used,
furnace should be set exactly 4” from side wall.
306SR-A
SideDischargeonCasing
1. Cut out and remove embossed area on
casing side.
2. Remove knockout from inner liner.
3. Place 1-1/2” boot from kit through
opening, matching anges of boot to
knockout on inner liner.
4. Mark screw holes and remove boot.
5. Drill holes with a 1/8” drill.
6. Attach inner boot with screws provided.
7. Place grille into position, drill holes into
casing, and attach with screws provided.
306SR & 30SRB: SIDE DISCHARGE KITS (Optional Accessories)
30SRB-A
SideDischargewithExtensionBoot
1. Cut opening in drywall as shown in gure 11, below.
2. Position plaster ground as shown in gure 11, below. (Optional).
3. Cut out and remove embossed section on casing side.
4. Remove knockout on inner liner.
5. Put heater into position.
6. Place inner boot into position, mark and cut boot ush with wall. Place outer
boot into position, mark and cut boot ush with wall.
7. Place boot trim into position, slide INNER BOOT through wall from adjacent
room and attach to inner liner. Slide OUTER BOOT through wall from
adjacent room and attach to casing side.
8. Place grill in position and secure to wall.
NOTE:
Maximum boot
length is 10”
Back Wall
Side Wall
14-3/8”
Plaster
Ground
10-3/16”
CAUTION: These kits must be installed by a qualified installer or service technician.

1018028-A
Page 17
SYMPTOM POSSIBLE CAUSES
TROUBLESHOOTING CHART ( For Qualied Service Technician ) - MAIN BURNER
1. Gas leak.
1. Main gas off.
2. Thermostat not set high enough to
call for heat.
3. Clogged burner orice.
4. Thermostat wired wrong or
defective.
Gas Odor
Failure
to Ignite
CORRECTIVE ACTION
FlameToo
Large 1. Defective operator section of valve.
2. Burner orice too large.
3. If installed above 2,000 feet.
1. Replace valve.
2. Check with local gas company for proper orice size and replace.
3. See orice chart, (Fig.10onpage12).
1. Clogged burner ports.
2. Obstructions around vent cap.
YellowBurner
Flame
1. Remove main burner and check for obstructions in throat, ports, and orices. Clean - but do
not enlarge ports or orices.
2. Make sure area around vent cap is clear, be sure vent system is sealed.
1. Seepage1.
1. Pilot ame too small.
2. Burner ports clogged at pilot.
3. Low gas pressure.
4. Pilot decreases in size when main
burners come on.
Delayed
Ignition
1. Adjust pilot ame.
2. Clean burner ports (do not enlarge).
3. Check gas supply pressure.
4. Supply piping is too small. Consult local gas company or competent installer.
1. Open all manual gas valves.
2. Set thermostat to higher temperature.
3. Clean burner orice (do not enlarge).
4. Check wiring, jump across thermostat terminals at valve, if valve open, re-check wires,
replace thermostat.
1. Defective or damaged
thermostat wire, or thermostat.
2. Thermostat location.
3. Defective or sticking valve.
4. Excessive gas pressure.
BurnerWon’t
TurnOff
1. Can be checked by removing wire from valve terminal. If valve goes off, replace wire
or thermostat.
2. Follow instructions, check location.
3. Replace valve.
4. Contact utility supplying gas.
1. Weak thermocouple.
2. Input too high.
3. Cover around pilot lighter
hole not air tight.
4. Vent tubes not properly
installed or sealed.
Pilot and
Main Burner
go out During
Normal
Operation
1. Check millivoltage and replace if low.
2. Check input rate.
3. Tighten wing nuts securing cover and sight glass. Check and replace gasket if needed.
4. Follow instructions. Check both exhaust and air intake tubes, and vent cap. Be sure all
gaskets are in place and properly sealed. Use only tubes and vent cap supplied. Do not
alter vent tubes or cap.
1. Gas input not checked.
2. Clogged orice.
1. Thermostat set too high.
2. Combination control valve stuck
open.
Incorrect
GasInput
TooMuch
Heat
1. Re-check gas input.
2. Clean orice with a smooth wood toothpick, do not enlarge.
1. Lower temperature setting.
2. Replace combination control valve.
Pleasefollowthefollowingcorrectiveactionsinorder.
1. Furnace undersized.
2. Thermostat set too low.
3. Incorrect supply pressure.
Not Enough
Heat
1. This is especially true when a dwelling or room is enlarged. Have the heat loss
calculated and compare to furnace output. Your gas company can supply you with
this information. If furnace is undersized, replace with correct size unit.
2. Raise temperature setting.
3. Check supply pressure.

1018028-A
Page 18
SERVICE RECORDS
TROUBLESHOOTING CHART ( For Qualied Service Technician ) - MAIN BURNER
Pleasefollowthefollowingcorrectiveactionsinorder.
SYMPTOM POSSIBLE CAUSES
1. Sparker won’t work.
2. Sparker won’t light pilot.
3. Manual reset switch
not engaged.
PilotWon’t
Light
CORRECTIVE ACTION
BurnerWon’t
Turn On 1. Gas valve not turned on.
2. No voltage to valve.
3. Defective thermostat.
4. No 115 V. Line voltage.
5. Gas valve defective.
6. Manual reset switch not engaged.
1. Turn gas valve to “on” position.
2. Check for 24 Volts to valve from transformer.
3. Check wall thermostat.
4. Provide line voltage.
5. Replace gas valve.
6. Depress red button on switch.
1. Air in line.
2. Defective thermocouple
3. Pilot ame too low.
4. Manual reset switch not engaged.
PilotWon’t
Light,orWon’t
StayLit
1. Bleed line.
2. Replace thermocouple.
3. Adjust pilot ame.
4. Depress red button on switch.
1. Check wire connections, provide adequate ground.
2. a. Pilot ame too small.
b. Turn valve to “on” position.
c. Check for pilot restriction.
3. Depress red button on switch.
I.I.D. Pilot
Standing Pilot

1018028-A
Page 19
TROUBLESHOOTING CHART ( Specically for Intermittent Ignition System ) - IID
OFF No Call for Heat Not Applicable None
Normal Operation
Heartbeat Not Applicable None
Recycle
Flame failed
during run
3Initiate new trial for ignition. Flash code
will remain through the ignition trial until
ame is proved.
If system fails to light on next trial ignition, check gas
supply, pilot burner, ame sense wiring, contamination of
ame rod, burner ground connection.
Flame sense
leakage to ground
7Control remains in wait mode. When the
fault corrects, control resumes normal
operation after a one minute delay.
Check ame sense lead wire for damage or shorting.
Check that ame rod is in proper position. Check ame
rod ceramic for cracks, damage or tracking.
5 minute Retry
Delay - On every
third retry on the
same “Call for Heat”
6+2 Initiate new trial for ignition after retry
delay completed.
Check gas supply, pilot burner, spark and ame sense
wiring, ame rod contaminated or out of position, burner
ground connection.
Flame sensed out
of sequence - longer
than 10 seconds
6 + 4 Control waits until ame is no longer
sensed and then goes to soft lockout.
Flash code continues. Control auto resets
from soft lockout after one hour.
Check for pilot ame. Replace gas valve if pilot ame
present. If no pilot ame, cycle “Call for Heat”. If error
repeats, replace control.
Low secondary
voltage supply -
(below 15.5 Vac)
8 Control remains in wait mode. When the
fault corrects, control resumes normal
operation after a one minute delay.
Check transformer and AC lines for proper input voltage
to the control. Check with full system load on the
transformer.
On every 6th
ame failure during
run on the same
“Call for Heat”
6 + 3 5 minute retry delay, then initiate new trial
for ignition.
Check gas supply, pilot burner, ame sense wiring,
contamination of ame rod, burner ground connection.
Startup - Flame
Sense Calibration
Flash Fast Not Applicable None
5 min. Retry Delay
Pilot ame not
detected during
trial for ignition
2 Initiate new trial for ignition after retry
delay completed.
If system fails to light on next trial for ignition check
gas supply, pilot burner, spark and ame sense wiring,
ame rod contaminated or out of position, burner ground
connection.
Flame sensed
out of sequence
4If situation self corrects within 10
seconds, control returns to normal
sequence. If ame out of sequence
remains longer than 10 seconds, control
goes to Flash code 6+4 (see below).
Check for pilot ame. Replace gas valve if pilot ame
present. If no pilot ame, cycle “Call for Heat”. If error
repeats, replace control.
Soft lockout due
to error detected
during self check
sequences
ON Control auto resets from soft lockout after
one hour.
Reset by cycling “Call for Heat”. If error repeats, replace
the control.
GREEN LED FLASH
CODE (XxY)ª INDICATES NEXT SYSTEM ACTION RECOMMENDED SERVICE ACTION
Pleasefollowthefollowingcorrectiveactionsinorder.
Other manuals for DVCF403C-H
1
This manual suits for next models
7
Table of contents
Languages:
Other COZY Wall Furnace manuals

COZY
COZY CF553D-H User manual

COZY
COZY FSK-A User manual

COZY
COZY DVCF40 User manual

COZY
COZY HEDV404 and User manual

COZY
COZY HEDV254A and User manual

COZY
COZY CDV155B and User manual

COZY
COZY CDV155DPPD User manual

COZY
COZY DVCF653B-H and User manual

COZY
COZY CDV15 User manual

COZY
COZY DVCF403C-H User manual