CyberPower UT1500 User manual

UT1500/2200E/EI
User’s Manual K01-C000111-01
IMPORTANT SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the
unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive
contaminants. (See the specifications for the acceptable temperature and humidity range.)
CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and avoid exposing the unit to direct sunlight or
installing the unit near heat emitting appliances such as space heaters or furnaces.
CAUTION! Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum
cleaners to UPS.
CAUTION! Do not plug the UPS input into its own output.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any other liquid-containing vessels on or
near the unit.
CAUTION! In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly
disable the UPS.
CAUTION! Do not attach a power strip or surge suppressor to the UPS.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
CAUTION! Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries.
CAUTION! The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when
maintenance or service work inside the UPS is necessary.
CAUTION! Internal battery voltage is 12Vdc. Sealed, lead-acid, 6-cell battery.
CAUTION! When replacing the batteries, use the same number and type of batteries.
CAUTION! Do not dispose of batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to the skin and eyes.
INSTALLING YOUR UPS SYSTEM
UNPACKING
The box should contain the following:
UT1500/2200E-IN: (1) UPS Unit x1; (2) USB Cable x 1; (3) Warranty Card x 1; (4)User Manual x 1
UT1500/2200E-AS: (1) UPS Unit x1; (2) USB Cable x 1; (3)User Manual x 1
PowerPanel® Personal Edition software is available on our website. Please visit www.cyberpower.com and go tothe Software Section for
free download.
OVERVIEW
The UT1500/2200E series provide automatic voltage regulation for inconsistent utility power, and provides battery backup during power
outages. The UT1500/2200E series ensure consistent power to your computer system.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is recommended to ensure
that the battery's maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery,
simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
2. With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz
drive, Tape drive, etc. into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper
shredder or other large electrical device into the battery power supplied outlets. The power demands of these devices will
overload and possibly damage the unit.
3. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit
breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc. Avoid using
extension cords.
4. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will "beep".
5. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug
at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker / fuse is
normal and then turns the UPS on.
6. To maintain optimal battery charge, leave the UPS plugged into anAC outlet at all times.
7. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months
to ensure battery life.
BASIC OPERATION
1. Power Switch
Press the switch for 2 seconds to turn the UPS
ON or OFF.
2. Led Indicators
This LED is illuminated when the UPS is working.
3. Battery Capability Led Indicators
Indicate the battery capability from bottom up
Front panel
Back panel
1. USB Port to PC
This port allows connection and communication from the USB port on the computer to the UPS unit. The UPS communicates
its status to the PowerPanel®Personal Edition software.
2. Communication Protection Ports
Communication protection ports will protect any standard modem, fax, telephone line, or network cable
3. Input Circuit Breaker
The circuit breaker provides optimal overload protection.
4. Input power cord
Connect to utility power.
5. Battery Backup & Surge Protected Outlets
Provide battery backup and surge protection. They ensure power is provided to connected equipment over a
period of time during a power failure.
TECHNICAL SPECIFICATIONS
DEFINITIONS FOR ILLUMINATED LED INDICATORS
LED
Alarm
Condition
On Off Normal
Flash Beep Twice Utility Failure - The UPS is providing battery power to outlets.
Flash Rapid Beeping Utility Failure - The UPS is providing battery power. The rapid beeps indicate the battery will run out
of power shortly.
On/Flash Constant Tone Overload - Occurs when connected equipment exceeds the rating of the unit. Turn the UPS off and
unplug at least one piece of equipment from the UPS.
TROUBLESHOOTING
Problem
Possible Cause
Solution
The UPS does not perform
expected runtime. Batteries are not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is slightly worn out. Contact CyberPower Systems Technical Support.
The UPS will not turn on.
The unit is not connected to an AC outlet. The unit must be connected to a 220-240V outlet.
The battery is worn out. Contact CyberPower Systems Technical Support.
Mechanical problem. Contact CyberPower Systems Technical Support.
Outlets do not provide power to
equipment
Fuse is blown or breaker is tripped due to
overload.
Turn the UPS off and unplug at least one piece
connected equipment. Unplug the power cord of the
UPS then replace the blown fuse with a spare one or
press the circuit breaker knob. Connect power cord
then turn the UPS on. Make sure that your spare fuse
meets the specification.
Batteries are discharged Allow the unit to recharge for at least 4 hours.
Unit has been damaged by a surge or spike. Contact CyberPower Systems Technical Support.
For more information, visit www.cyberpower.com
All rights reserved. Reproduction without permission is prohibited.
6F, No. 32, Sec. 1, Chenggong Rd., Nangang District, Taipei 115, Taiwan
Model UT1500E UT1500EI UT1500E-AS UT1500E-IN UT2200E UT2200EI UT2200E-AS UT2200E-IN
Capacity (VA) 1500 2200
Watt (W) 900 1320
Input
Voltage Range 165~290Vac
Nominal Frequency 50 Hz
Output
On Battery Output
Voltage Simulated Sine Wave at 230Vac +/-5%
On Battery Output
Frequency 50 Hz +/-1%
Overload Protection Breaker / Fuse
Physical
Total # of UPS
Receptacles
4
SCHOKO 6 IEC 4 ASEAN 4 INDIA 4
SCHOKO 6 IEC 4 ASEAN 4 INDIA
Dimensions (W x H x
D)(mm) 148 X 178 X 298
Weight (kg) 9.1 kg 10.8 kg
Battery
Sealed Maintenance
Free Lead Acid Battery RBP0089 x2 RBP0090 x2
Typical Recharge Time 8 Hours
Warning Diagnostics
Indicators Power On / Using Battery
Audible Alarms On Battery, Low Battery, Overload, Fault
Surge Protection
Network/ Phone/ Fax/
Modem Protection YES
Communication
PowerPanel® Personal
Edition Software Windows 8/7/Vista/XP/2000,Server 2012/2008/2003, Linux
Environmental
Operating Temperature 0°C to 40°C
Operating Relative
Humidity 0 to 90%
Management
Auto-Charger Yes
Auto-Restart Yes

This manual suits for next models

5

Other CyberPower UPS manuals

CyberPower CyberShield CSN75A12V3 User manual

CyberPower

CyberPower CyberShield CSN75A12V3 User manual

CyberPower OL6000RT3UTF User manual

CyberPower

CyberPower OL6000RT3UTF User manual

CyberPower PR3000 User manual

CyberPower

CyberPower PR3000 User manual

CyberPower CyberShield CBN50U48A-1 User manual

CyberPower

CyberPower CyberShield CBN50U48A-1 User manual

CyberPower CPS725SL User manual

CyberPower

CyberPower CPS725SL User manual

CyberPower Smart App Sinewave Series User manual

CyberPower

CyberPower Smart App Sinewave Series User manual

CyberPower CP1500AVRLCDa User manual

CyberPower

CyberPower CP1500AVRLCDa User manual

CyberPower BL1250U User manual

CyberPower

CyberPower BL1250U User manual

CyberPower PR1500LCD User manual

CyberPower

CyberPower PR1500LCD User manual

CyberPower PR2000LCD User manual

CyberPower

CyberPower PR2000LCD User manual

CyberPower 649532016006 User manual

CyberPower

CyberPower 649532016006 User manual

CyberPower UPS BR850ELCD User manual

CyberPower

CyberPower UPS BR850ELCD User manual

CyberPower PR750LCDRM1U User manual

CyberPower

CyberPower PR750LCDRM1U User manual

CyberPower OL6000RT3UTAA User manual

CyberPower

CyberPower OL6000RT3UTAA User manual

CyberPower PR3000LCDRT2U User manual

CyberPower

CyberPower PR3000LCDRT2U User manual

CyberPower CPS625AVR User manual

CyberPower

CyberPower CPS625AVR User manual

CyberPower EC750G User manual

CyberPower

CyberPower EC750G User manual

CyberPower CPS600E User manual

CyberPower

CyberPower CPS600E User manual

CyberPower 3000 VA User manual

CyberPower

CyberPower 3000 VA User manual

CyberPower CyberShield CSN27U12V-NA3-G User manual

CyberPower

CyberPower CyberShield CSN27U12V-NA3-G User manual

CyberPower CSN27U12V Installation guide

CyberPower

CyberPower CSN27U12V Installation guide

CyberPower CP1300EPFCLCD User manual

CyberPower

CyberPower CP1300EPFCLCD User manual

CyberPower CP850AVRLCD User manual

CyberPower

CyberPower CP850AVRLCD User manual

CyberPower LX1100G3 User manual

CyberPower

CyberPower LX1100G3 User manual

Popular UPS manuals by other brands

Ditek DTK-UPS400 user manual

Ditek

Ditek DTK-UPS400 user manual

Intex KOM0315 user manual

Intex

Intex KOM0315 user manual

Cyber Power CP850PFCLCD user manual

Cyber Power

Cyber Power CP850PFCLCD user manual

LEGRAND NUMERIC intizon user guide

LEGRAND

LEGRAND NUMERIC intizon user guide

Enersafe ESOL T-E 6kVa user manual

Enersafe

Enersafe ESOL T-E 6kVa user manual

Tripp Lite AVR750U owner's manual

Tripp Lite

Tripp Lite AVR750U owner's manual

Tripp Lite TM500 Specifications

Tripp Lite

Tripp Lite TM500 Specifications

Ablerex KRONOS Installation and operation manual

Ablerex

Ablerex KRONOS Installation and operation manual

ONEAC ONm 300 I User instruction manual

ONEAC

ONEAC ONm 300 I User instruction manual

Wieland wipos operating instructions

Wieland

Wieland wipos operating instructions

Tecnoware EVO TM 15.0 user manual

Tecnoware

Tecnoware EVO TM 15.0 user manual

AmazonBasics B073Q48Z95 manual

AmazonBasics

AmazonBasics B073Q48Z95 manual

Speco UPS-500VA Specifications

Speco

Speco UPS-500VA Specifications

Maruson PowerPro 550VA user manual

Maruson

Maruson PowerPro 550VA user manual

Gamatronic Centric 3x480 Vac installation guide

Gamatronic

Gamatronic Centric 3x480 Vac installation guide

Velleman UPS400N manual

Velleman

Velleman UPS400N manual

Mitsubishi Electric Netcom 2 user manual

Mitsubishi Electric

Mitsubishi Electric Netcom 2 user manual

GE 600 - 1500 VA user manual

GE

GE 600 - 1500 VA user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.