Daikin Altherma ERHQ011-014-016BA How to use

Installer reference guide
Daikin Altherma – Low temperature split English
+
Installer reference guide
Daikin Altherma – Low temperature split
ERHQ011-014-016BA
ERLQ011-014-016CA
EHVZ16S18CB

Table of Contents
Installer reference guide
2
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
Table of Contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 4
1.2 For the installer.......................................................................... 4
1.2.1 General ....................................................................... 4
1.2.2 Installation site ............................................................ 4
1.2.3 Refrigerant .................................................................. 4
1.2.4 Brine............................................................................ 5
1.2.5 Water .......................................................................... 5
1.2.6 Electrical ..................................................................... 5
2 About the documentation 6
2.1 About this document.................................................................. 6
2.2 Installer reference guide at a glance ......................................... 6
3 About the box 7
3.1 Overview: About the box ........................................................... 7
3.2 Outdoor unit............................................................................... 7
3.2.1 To unpack the outdoor unit ......................................... 7
3.2.2 To handle the outdoor unit.......................................... 7
3.2.3 To remove the accessories from the outdoor unit....... 7
3.3 Indoor unit ................................................................................. 7
3.3.1 To unpack the indoor unit ........................................... 7
3.3.2 To remove the accessories from the indoor unit......... 7
4 About the units and options 8
4.1 Overview: About the units and options...................................... 8
4.2 Identification .............................................................................. 8
4.2.1 Identification label: Outdoor unit ................................. 8
4.2.2 Identification label: Indoor unit .................................... 8
4.3 Combining units and options ..................................................... 9
4.3.1 Possible options for the outdoor unit........................... 9
4.3.2 Possible options for the indoor unit............................. 9
4.3.3 Possible combinations of indoor unit and outdoor
unit .............................................................................. 10
5 Application guidelines 10
5.1 Overview: Application guidelines............................................... 10
5.2 Setting up the space heating system ........................................ 10
5.2.1 Multiple rooms – TwoLWT zones............................... 10
5.3 Setting up the domestic hot water tank ..................................... 11
5.3.1 System layout – Integrated DHW tank........................ 11
5.3.2 Selecting the volume and desired temperature for
the DHW tank.............................................................. 11
5.3.3 Setup and configuration – DHW tank.......................... 12
5.3.4 DHW pump for instant hot water................................. 12
5.3.5 DHW pump for disinfection ......................................... 12
5.4 Setting up the energy metering ................................................. 13
5.4.1 Produced heat............................................................. 13
5.4.2 Consumed energy....................................................... 13
5.4.3 Normal kWh rate power supply................................... 13
5.4.4 Preferential kWh rate power supply............................ 14
5.5 Setting up the power consumption control ................................ 14
5.5.1 Permanent power limitation ........................................ 14
5.5.2 Power limitation activated by digital inputs ................. 14
5.5.3 Power limitation process ............................................. 15
5.6 Setting up an external temperature sensor ............................... 15
6 Preparation 15
6.1 Overview: Preparation............................................................... 15
6.2 Preparing installation site .......................................................... 15
6.2.1 Installation site requirements of the outdoor unit ........ 16
6.2.2 Additional installation site requirements of the
outdoor unit in cold climates ....................................... 16
6.2.3 Installation site requirements of the indoor unit .......... 16
6.3 Preparing refrigerant piping....................................................... 17
6.3.1 Refrigerant piping requirements.................................. 17
6.3.2 Refrigerant piping insulation ........................................ 17
6.4 Preparing water piping ............................................................... 17
6.4.1 Water circuit requirements ........................................... 17
6.4.2 Formula to calculate the expansion vessel pre-
pressure ....................................................................... 18
6.4.3 To check the water volume and flow rate .................... 18
6.4.4 Changing the pre-pressure of the expansion vessel.... 19
6.4.5 To check the water volume: Examples ........................ 20
6.5 Preparing electrical wiring .......................................................... 20
6.5.1 About preparing electrical wiring.................................. 20
6.5.2 About preferential kWh rate power supply ................... 20
Overview of electrical connections except external
actuators ...................................................................... 21
6.5.3 Overview of electrical connections for external and
internal actuators ......................................................... 21
7 Installation 21
7.1 Overview: Installation ................................................................. 21
7.2 Opening the units ....................................................................... 22
7.2.1 About opening the units ............................................... 22
7.2.2 To open the outdoor unit.............................................. 22
7.2.3 To open the indoor unit ................................................ 22
7.2.4 To open the switch box cover of the indoor unit .......... 22
7.3 Mounting the outdoor unit........................................................... 22
7.3.1 About mounting the outdoor unit.................................. 22
7.3.2 Precautions when mounting the outdoor unit............... 23
7.3.3 To provide the installation structure ............................. 23
7.3.4 To install the outdoor unit............................................. 23
7.3.5 To provide drainage ..................................................... 23
7.3.6 To prevent the outdoor unit from falling over ............... 24
7.4 Mounting the indoor unit............................................................. 24
7.4.1 About mounting the indoor unit.................................... 24
7.4.2 Precautions when mounting the indoor unit................. 24
7.4.3 To install the indoor unit............................................... 24
7.5 Connecting the refrigerant piping ............................................... 24
7.5.1 About connecting the refrigerant piping ....................... 24
7.5.2 Precautions when connecting the refrigerant piping.... 25
7.5.3 Guidelines when connecting the refrigerant piping...... 25
7.5.4 Pipe bending guidelines............................................... 25
7.5.5 To flare the pipe end .................................................... 25
7.5.6 To braze the pipe end .................................................. 26
7.5.7 Using the stop valve and service port .......................... 26
7.5.8 To connect the refrigerant piping to the outdoor unit ... 27
7.5.9 To connect the refrigerant piping to the indoor unit ..... 28
7.5.10 To determine if oil traps are required ........................... 28
7.6 Checking the refrigerant piping .................................................. 28
7.6.1 About checking the refrigerant piping .......................... 28
7.6.2 Precautions when checking the refrigerant piping ....... 28
7.6.3 Checking refrigerant piping: Setup............................... 28
7.6.4 To check for leaks........................................................ 28
7.6.5 To perform vacuum drying ........................................... 29
7.7 Charging refrigerant ................................................................... 29
7.7.1 About charging refrigerant ........................................... 29
7.7.2 Precautions when charging refrigerant ........................ 29
7.7.3 To determine the additional refrigerant amount........... 29
7.7.4 To determine the complete recharge amount.............. 30
7.7.5 To charge refrigerant ................................................... 30
7.7.6 To fix the fluorinated greenhouse gases label ............. 30
7.8 Connecting the water piping....................................................... 30
7.8.1 About connecting the water piping............................... 30
7.8.2 Precautions when connecting the water piping............ 30
7.8.3 To connect the water piping......................................... 30
7.8.4 To connect the recirculation piping .............................. 31
7.8.5 To connect the pressure relief valve to the drain......... 31
7.8.6 To fill the water circuit .................................................. 31
7.8.7 To fill the domestic hot water tank ............................... 32
7.8.8 To insulate the water piping ......................................... 32
7.9 Connecting the electrical wiring.................................................. 32
7.9.1 About connecting the electrical wiring.......................... 32
7.9.2 About electrical compliance ......................................... 32

1 General safety precautions
Installer reference guide
3
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
7.9.3 Precautions when connecting the electrical wiring ..... 33
7.9.4 Guidelines when connecting the electrical wiring ....... 33
7.9.5 Specifications of standard wiring components............ 33
7.9.6 To connect the electrical wiring on the outdoor unit.... 33
7.9.7 To reposition the air thermistor on the outdoor unit .... 34
7.9.8 To connect the electrical wiring on the indoor unit...... 35
7.9.9 To connect the main power supply ............................. 36
7.9.10 To connect the backup heater power supply .............. 36
7.9.11 To connect the user interface ..................................... 37
7.9.12 To connect the shut-off valve...................................... 37
7.9.13 To connect the electrical meters ................................. 38
7.9.14 To connect the domestic hot water pump ................... 38
7.9.15 To connect the alarm output ....................................... 38
7.9.16 To connect the power consumption digital inputs ....... 38
7.9.17 To connect the safety thermostat (normal closed
contact) ....................................................................... 38
7.10 Finishing the outdoor unit installation ........................................ 39
7.10.1 To finish the outdoor unit installation .......................... 39
7.10.2 To close the outdoor unit ............................................ 39
7.11 Finishing the indoor unit installation .......................................... 39
7.11.1 To fix the user interface cover to the indoor unit......... 39
7.11.2 To close the indoor unit............................................... 39
8 Configuration 39
8.1 Overview: Configuration ............................................................ 39
8.1.1 To connect the PC cable to the switch box................. 40
8.1.2 To access the most used commands ......................... 40
8.1.3 To copy the system settings from the first to the
second user interface.................................................. 41
8.1.4 To copy the language set from the first to the second
user interface .............................................................. 41
8.1.5 Quick wizard: Set the system layout after first power
ON............................................................................... 41
8.2 Basic configuration .................................................................... 42
8.2.1 Quick wizard: Language / time and date..................... 42
8.2.2 Quick wizard: Standard............................................... 42
8.2.3 Quick wizard: Options ................................................. 43
8.2.4 Quick wizard: Capacities (energy metering) ............... 45
8.2.5 Space heating control ................................................. 46
8.2.6 Domestic hot water control ......................................... 48
8.2.7 Contact/helpdesk number........................................... 48
8.3 Advanced configuration/optimization......................................... 48
8.3.1 Space heating operation: advanced ........................... 48
8.3.2 Domestic hot water control: advanced........................ 51
8.3.3 Heat source settings ................................................... 54
8.3.4 System settings........................................................... 55
8.4 Menu structure: Overview user settings .................................... 58
8.5 Menu structure: Overview installer settings............................... 59
9 Commissioning 60
9.1 Overview: Commissioning......................................................... 60
9.2 Precautions when commissioning ............................................. 60
9.3 Checklist before commissioning................................................ 60
9.4 Checklist during commissioning ................................................ 60
9.4.1 To check the minimum flow rate ................................. 61
9.4.2 Air purge function........................................................ 61
9.4.3 To perform a test run .................................................. 62
9.4.4 To perform an actuator test run .................................. 62
9.4.5 Underfloor heating screed dryout................................ 62
10 Hand-over to the user 64
11 Maintenance and service 64
11.1 Overview: Maintenance and service ......................................... 64
11.2 Maintenance safety precautions................................................ 64
11.2.1 Opening the indoor unit............................................... 64
11.3 Checklist for yearly maintenance of the outdoor unit ................ 64
11.4 Checklist for yearly maintenance of the indoor unit................... 64
11.4.1 To drain the domestic hot water tank.......................... 65
12 Troubleshooting 65
12.1 Overview: Troubleshooting......................................................... 65
12.2 Precautions when troubleshooting ............................................. 66
12.3 Solving problems based on symptoms....................................... 66
12.3.1 Symptom: The unit is NOT heating as expected ......... 66
12.3.2 Symptom: The compressor does NOT start (space
heating or domestic water heating).............................. 66
12.3.3 Symptom: The pump is making noise (cavitation) ....... 66
12.3.4 Symptom: The pressure relief valve opens.................. 66
12.3.5 Symptom: The water pressure relief valve leaks ......... 67
12.3.6 Symptom: The space is NOT sufficiently heated at
low outdoor temperatures ............................................ 67
12.3.7 Symptom: The pressure at the tapping point is
temporarily unusual high.............................................. 67
12.3.8 Symptom: Decoration panels are pushed away due
to a swollen tank .......................................................... 67
12.3.9 Symptom: Tank disinfection function is NOT
completed correctly (AH-error)..................................... 67
12.4 Solving problems based on error codes ..................................... 68
12.4.1 Error codes: Overview ................................................. 68
13 Disposal 70
13.1 Overview: Disposal..................................................................... 70
13.2 About pump down ...................................................................... 70
13.3 To pump down............................................................................ 70
14 Technical data 71
14.1 Overview: Technical data ........................................................... 71
14.2 Dimensions and service space................................................... 71
14.2.1 Dimensions: Outdoor unit ............................................ 71
14.2.2 Service space: Outdoor unit......................................... 75
14.2.3 Dimensions and service space: Indoor unit ................. 77
14.3 Center of gravity ......................................................................... 78
14.3.1 Center of gravity: Outdoor unit..................................... 78
14.4 Components ............................................................................... 79
14.4.1 Components: Outdoor unit........................................... 79
14.4.2 Components: Indoor unit.............................................. 81
14.4.3 Components: Switch box (indoor unit) ......................... 81
14.5 Piping diagram ........................................................................... 82
14.5.1 Piping diagram: Outdoor unit ....................................... 82
14.5.2 Piping diagram: Indoor unit .......................................... 83
14.6 Wiring diagram ........................................................................... 84
14.6.1 Wiring diagram: Outdoor unit ....................................... 84
14.6.2 Wiring diagram: Indoor unit.......................................... 92
14.7 Technical specifications ............................................................. 97
14.7.1 Technical specifications: Outdoor unit ......................... 97
14.7.2 Technical specifications: Indoor unit ............................111
14.8 Operation range .........................................................................114
14.8.1 Operation range: Heating and cooling .........................114
14.8.2 Operation range: Domestic hot water ..........................115
14.9 ESP curve ..................................................................................116
14.9.1 ESP curve: Indoor unit .................................................116
15 Glossary 117
16 Field settings table 118
1 General safety precautions
1.1 About the documentation
▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be
performed by an authorized installer.

1 General safety precautions
Installer reference guide
4
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of
extreme hot or cold temperatures.
WARNING
Indicates a situation that could result in death or serious
injury.
CAUTION
Indicates a situation that could result in minor or moderate
injury.
NOTICE
Indicates a situation that could result in equipment or
property damage.
INFORMATION
Indicates useful tips or additional information.
1.2 For the installer
1.2.1 General
If you are not sure how to install or operate the unit, contact your
dealer.
NOTICE
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or
approved by Daikin.
WARNING
Make sure installation, testing and applied materials
comply with applicable legislation (on top of the
instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It
could be too hot or too cold. Give it time to return to
normal temperature. If you must touch it, wear
protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminum fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under
dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an
accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
1.2.2 Installation site
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre,
ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.
1.2.3 Refrigerant
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. In Europe, EN378 is the applicable
standard.
NOTICE
Make sure the field piping and connections are not
subjected to stress.

1 General safety precautions
Installer reference guide
5
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If
refrigerant gas leaks, ventilate the area immediately.
Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
WARNING
Always recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable
legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant
may only be charged after performing the leak test and the
vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging
of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign
materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with
"Liquid filling siphon attached")
Charge with the cylinder upright.
A siphon tube is NOT present Charge with the cylinder upside
down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when
pausing, close the valve of the refrigerant tank
immediately. If the valve is not closed immediately,
remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.
1.2.4 Brine
If applicable. See the installation manual or installer reference guide
of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the
applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If
brine leaks, ventilate the area immediately and contact
your local dealer.
WARNING
The ambient temperature inside the unit can get much
higher than that of the room, e.g. 70°C. In case of a brine
leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply
with the safety and environmental precautions specified in
the applicable legislation.
1.2.5 Water
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure water quality complies with EU directive
98/83EC.
1.2.6 Electrical
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or
touching electrical parts.
▪ Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you
can touch electrical components. For the location of the
terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, shall be installed in the fixed wiring.

2 About the documentation
Installer reference guide
6
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Install power cables at least 1metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2 About the documentation
2.1 About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
▪Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
▪Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
▪Installer reference guide:
▪ Preparation of the installation, technical specifications, good
practices, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
▪Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
http://www.daikineurope.com/support-and-manuals/product-
information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
2.2 Installer reference guide at a
glance
Chapter Description
General safety
precautions
Safety instructions that you must read
before installing
About the documentation What documentation exists for the
installer
About the box How to unpack the units and remove
their accessories
About the units and
options
▪ How to identify the units
▪ Possible combinations of units and
options
Application guidelines Various installation setups of the system
Preparation What to do and know before going
on‑site
Installation What to do and know to install the
system
Configuration What to do and know to configure the
system after it is installed
Commissioning What to do and know to commission the
system after it is configured
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and
kept for future reference
Note: There is also an installer settings
table in the user reference guide. This
table has to be filled in by the installer
and handed over to the user.

3 About the box
Installer reference guide
7
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
3 About the box
3.1 Overview: About the box
This chapter describes what you have to do after the boxes with the
outdoor and indoor unit are delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
3.2 Outdoor unit
3.2.1 To unpack the outdoor unit
21
3.2.2 To handle the outdoor unit
Carry the unit slowly as shown:
102~114 kg
CAUTION
To avoid injury, do NOT touch the air inlet or aluminum fins
of the unit.
3.2.3 To remove the accessories from the
outdoor unit
1×
2
1
a1× c1×
b2× d1×
e1× f1× g1×
aOutdoor unit installation manual
bCable tie
cFluorinated greenhouse gases label
dMultilingual fluorinated greenhouse gases label
eScrew (only for ERLQ)
fThermistor fixing plate (spare) (only for ERLQ)
gThermistor fixture (only for ERLQ)
3.3 Indoor unit
3.3.1 To unpack the indoor unit
3.3.2 To remove the accessories from the
indoor unit
1Remove the screws at the top of the unit.
2Remove the top panel.
3Remove the screws at the front of the unit.
4Push on the button on the bottom of the front plate.
5Remove the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower
part. Watch your fingers, there are sharp edges on the
lower part of the front plate.

4 About the units and options
Installer reference guide
8
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
a~e
g
f
5
4
1
2
3
4
4×
2×
6Remove the accessories.
1× 1× 1× 1×
2× 1×4×
abcd
f2×
g he
aGeneral safety precautions
bAddendum book for optional equipment
cIndoor unit installation manual
dOperation manual
eSealing ring for shut-off valve
fShut-off valve with drain/fill point
gShut-off valve
hUser interface cover
7Reinstall the top panel and the front plate.
4 About the units and options
4.1 Overview: About the units and
options
This chapter contains information about:
▪ Identifying the outdoor unit
▪ Identifying the indoor unit
▪ Combining outdoor and indoor units
▪ Combining the outdoor unit with options
▪ Combining the indoor unit with options
4.2 Identification
NOTICE
When installing or servicing several units at the same time,
make sure NOT to switch the service panels between
different models.
4.2.1 Identification label: Outdoor unit
Location
Model identification
▪ ERLQ: Contains components (insulation, bottom plate heater,…)
to prevent freeze-up in areas with low ambient temperature and
high humidity.
▪ ERHQ: Does NOT contain these components.
Example: ERLQ011CAW1
Code Explanation
ER European split outdoor pair heat pump
L H=Low water temperature – ambient zone:
0~−10°C
L=Low water temperature – ambient zone:
−10~−20°C
Q Refrigerant R410A
011 Capacity class
CA Model series
W1 Power supply
4.2.2 Identification label: Indoor unit
Location
Model identification
Example: EHVZ04S18CB3V
Code Description
E European model
HV Floor-standing indoor unit with integrated tank
Z Dual-zone model
04 Capacity class

4 About the units and options
Installer reference guide
9
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
Code Description
S Integrated tank material: Stainless steel
18 Integrated tank volume
CB Model series
3V Backup heater model
4.3 Combining units and options
4.3.1 Possible options for the outdoor unit
Demand PCB (KRP58M51) (only for ERLQ)
▪ Limits the maximum current. However, this also decreases the
heating/cooling capacity of the system.
▪ Only the "Setting of demand running" function of the demand PCB
is applicable.
▪ For installation instructions, see the installation manual of the
demand PCB.
Snow cover (EK016SNC) (only for ERLQ)
▪ Prevents the outdoor unit from being snowed up.
▪ Recommended in areas with low ambient temperatures or heavy
snowfall.
▪ For installation instructions, see the installation manual of the
snow cover.
Drain plug kit (EKDK04) (only for ERHQ)
▪ Gathers the condensate from the outdoor unit and guides it away
through 1 plug in the bottom plate.
▪ For ERLQ: Drain plug kit is not applicable.
▪ For ERHQ: Drain plug kit is option.
▪ Cannot be combined with bottom plate heater.
▪ For installation instructions, see the installation manual of the
drain plug kit.
Bottom plate heater (EKBPHTH16A) (only for ERHQ in
combination with C* indoor unit)
▪ Prevents freeze-up of the bottom plate.
▪ Recommended in areas with low ambient temperature and high
humidity.
▪ For ERLQ: Bottom plate heater is standard (factory-mounted).
▪ For ERHQ: Bottom plate heater is option.
▪ Cannot be combined with drain plug kit.
▪ If you install EKBPHTH16A, you also have to install the digital I/O
PCB (EKRP1HB).
▪ For installation instructions, see the installation manual of the
bottom plate heater and addendum book for optional equipment.
4.3.2 Possible options for the indoor unit
User interface (EKRUCBL*)
The user interface and a possible additional user interface are
available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the indoor unit,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or
copied from an user interface to the other.
For installation instructions, see "7.9.11 To connect the user
interface"on page37.
Simplified user interface (EKRUCBS)
▪ The simplified user interface can only be used in combination with
the main user interface.
▪ The simplified user interface acts as room thermostat and needs
to be installed in the room that you want it to control.
For installation instructions, see the installation and operation
manual of the simplified user interface.
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This
thermostat can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room
thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only
in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room
thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating On/OFF output
▪ Changeover to external heat source
▪ Only for EHVZ16S18 model: Control signal for bottom plate heater
kit EKBPHTH16A.
For installation instructions, see the installation manual of the digital
I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs
you must install the demand PCB.
For installation instructions, see the installation manual of the
demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room
temperature sensor.
As an option the remote indoor sensor can be installed to measure
the room temperature on another location.
For installation instructions, see the installation manual of the remote
indoor sensor and addendum book for optional equipment.

5 Application guidelines
Installer reference guide
10
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
INFORMATION
▪ The remote indoor sensor can only be used in case the
user interface is configured with room thermostat
functionality.
▪ You can only connect either the remote indoor sensor
or the remote outdoor sensor.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure
the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure
the outdoor temperature on another location (e.g. to avoid direct
sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote
outdoor sensor.
INFORMATION
You can only connect either the remote indoor sensor or
the remote outdoor sensor.
PC configurator (EKPCCAB)
The PC cable makes a connection between the switch box of the
indoor unit and a PC. It gives the possibility to upload different
language files to the user interface and indoor parameters to the
indoor unit. For the available language files, contact your local
dealer.
The software and corresponding operating instructions are available
on http://www.daikineurope.com/support-and-manuals/software-
downloads/.
For installation instructions, see the installation manual of the PC
cable and "8Configuration"on page39.
Heat pump convector (FWXV)
For providing space heating/cooling, it is possible to use heat pump
convectors (FWXV).
For installation instructions, refer to the installation manual of the
heat pump convectors, and the addendum book for optional
equipment.
4.3.3 Possible combinations of indoor unit and
outdoor unit
Outdoor unit Indoor unit
EHVZ16
ERHQ011+ERLQ011 O
ERHQ014+ERLQ014 O
ERHQ016+ERLQ016 O
5 Application guidelines
5.1 Overview: Application guidelines
The purpose of the application guidelines is to give a glance of the
possibilities of the Daikin heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant
for reference only, and are NOT to be used as detailed
hydraulic diagrams. The detailed hydraulic
dimensioning and balancing are NOT shown, and are
the responsibility of the installer.
▪ For more information about the configuration settings to
optimize heatpump operation, see "8Configuration"on
page39.
This chapter contains application guidelines for:
▪ Setting up the space heating system
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption
▪ Setting up an external temperature sensor
5.2 Setting up the space heating
system
The Daikin heat pump system supplies leaving water to heat
emitters in one or more rooms.
Because the system offers a wide flexibility to control the
temperature in each room, you need to answer the following
questions first:
▪ How many rooms are heated by the Daikin heatpump system?
▪ Which heat emitter types are used in each room and what is their
design leaving water temperature?
Once the space heating requirements are clear, Daikin recommends
to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
INFORMATION
In case an external room thermostat is used and room frost
protection needs to be guaranteed in all conditions, then
you have to set auto emergency [A.5.1.2] to 1.
5.2.1 Multiple rooms – TwoLWT zones
This unit is designed to deliver water at 2 different temperatures. A
typical installation consists of underfloor heating at a lower
temperature and radiators at a higher water temperature.
In this document:
▪ Main zone = Zone with the lowest design temperature
▪ Additional zone = Zone with the highest design temperature
Typical example:
Room (zone) Heat emitters: Design
temperature
Living room (main zone) Underfloor heating: 35°C
Bed rooms (additional zone) Heat pump convectors: 45°C
Setup

5 Application guidelines
Installer reference guide
11
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
j
k
j
HPC1
FHL1 FHL2 FHL3
HPC2 HPC3
B
AC
E
D
M
a b c
g hf
d e
i
i
hh
h
AAdditional leaving water temperature zone
BRoom 1
CRoom 2
DMain leaving water temperature zone
ERoom 3
aOutdoor unit
bIndoor unit
cHeat exchanger
dBackup heater
eMotorised 3-way valve (mixing the main zone)
fAdditional pump
gMain pump
hShut-off valve
iCollector (field supply)
jRemote controller of the heat pump convectors (field
supply)
kUser interface (field supply)
HPC1...3 Heat pump convectors (field supply)
FHL1...3 Floor heating loops (field supply)
▪ For the main zone: the room temperature is controlled by the user
interface, which is used as room thermostat.
▪ For the additional zone:
▪ The external thermostat is directly connected to the indoor unit.
▪ The desired room temperature is set via the external thermostat
and the thermostatic valves of the radiators in each room.
▪ The heating demand signal from the external thermostat is
connected to the digital input on the indoor unit (X2M/1a and
X2M/4). The indoor unit will only supply the desired additional
leaving water temperature when there is an actual demand.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Note:
▪ Main room = user interface
used as room thermostat
functionality
▪ Other rooms = external room
thermostat functionality
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
1 (2 LWT zones): Main +
additional
Setting Value
In case of heatpump convectors:
External room thermostat for the
additional zone:
▪ #: [A.2.2.5]
▪ Code: [C-06]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Shut-off valve output Set to follow the thermo demand
of the main zone.
Benefits
▪Comfort. The smart room thermostat functionality can decrease
or increase the desired leaving water temperature based on the
actual room temperature (modulation).
▪Efficiency.
▪ Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of
the different heat emitters.
▪ Underfloor heating has the best performance with Altherma LT.
5.3 Setting up the domestic hot water
tank
5.3.1 System layout – Integrated DHW tank
MM
a b c d ge h ii
ij
j
f
k
i
HPC1
UI
FHL1 FHL2 FHL3
HPC2 HPC3
aOutdoor unit
bIndoor unit
cHeat exchanger
dBackup heater
eMotorised 3‑wave valve (switch between space heating
and domestic hot water)
fMotorised 3‑way valve (mixing the main zone)
gMain pump
hAdditional pump
iShut-off valve
jCollector (field supply)
kDomestic hot water tank
FHL1...3 Floor heating loops (field supply)
UI User interface (field supply)
HPC1...3 Heat pump convectors (field supply)
5.3.2 Selecting the volume and desired
temperature for the DHW tank
People experience water as hot when its temperature is 40°C.
Therefore, the DHW consumption is always expressed as equivalent
hot water volume at 40°C. However, you can set the DHW tank
temperature at a higher temperature (example: 53°C), which is then
mixed with cold water (example: 15°C).

5 Application guidelines
Installer reference guide
12
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
Selecting the desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the desired temperature for the DHW tank.
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures
for each day.
▪ The lower the desired DHW tank temperature, the more cost
effective. By selecting a larger DHW tank, you can lower the
desired DHW tank temperature.
▪ The heatpump itself can produce domestic hot water of maximum
55°C (50°C if outdoor temperature is low). The electrical
resistance integrated in the heat pump can increase this
temperature. However, this consumes more energy. Daikin
recommends to set the desired DHW tank temperature below
55°C to avoid using the backup heater.
▪ The higher the outdoor temperature, the better the performance of
the heatpump.
▪ If energy prices are the same during the day and the night,
Daikin recommends to heat up the DHW tank during the day.
▪ If energy prices are lower during the night, Daikin recommends
to heat up the DHW tank during the night.
▪ When the heatpump produces domestic hot water, it cannot heat
up a space. When you need domestic hot water and space
heating at the same, Daikin recommends to produce the domestic
hot water during the night when there is lower space heating
demand.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption
(equivalent hot water volume at 40°C) using the typical water
volumes:
Question Typical water volume
How many showers are needed
per day?
1shower = 10min×10l/min =
100l
How many baths are needed per
day?
1bath = 150l
How much water is needed at the
kitchen sink per day?
1sink = 2min×5l/min = 10l
Are there any other domestic hot
water needs?
—
Example: If the DHW consumption of a family (4 persons) per day is
as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l
Determining the volume and desired temperature for the DHW
tank
Formula Example
V1=V2+V2×(T2−40)/(40−T1) If:
▪ V2=180l
▪ T2=54°C
▪ T1=15°C
Then V1=280l
V1DHW consumption (equivalent hot water volume at 40°C)
V2Required DHW tank volume if only heated once
T2DHW tank temperature
T1Cold water temperature
5.3.3 Setup and configuration – DHW tank
▪ For large DHW consumptions, you can heat up the DHW tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heatpump
▪ Electrical backup heater
▪ For more information about optimizing the energy consumption for
producing domestic hot water, see "8Configuration"on page39.
5.3.4 DHW pump for instant hot water
Setup
c
f
a
bg
h
i
aIndoor unit
bDHW tank
cDHW pump (field supply)
fShower (field supply)
gCold water
hDomestic hot water OUT
iRecirculation connection
▪ By connecting a DHW pump, instant hot water can be available at
the tap.
▪ The DHW pump and the installation are field supply and the
responsibility of the installer.
▪ For more information about connecting the recirculation
connection: see "7Installation"on page21.
Configuration
▪ For more information, see "8Configuration"on page39.
▪ You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference
guide.
5.3.5 DHW pump for disinfection
Setup
c
a
bd f
e g
h
i
aIndoor unit
bDHW tank
cDHW pump (field supply)
dHeater element (field supply)
eNon‑return valve (field supply)
fShower (field supply)
gCold water
hDomestic hot water OUT
iRecirculation connection
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ The temperature of the DHW tank can be set to maximum 60°C. If
applicable legislation requires higher temperature for disinfection,
you can connect a DHW pump and heater element as shown
above.
▪ If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater
element (if needed) as shown above.
▪ To ensure a complete disinfection, you have to open the tapping
point.

5 Application guidelines
Installer reference guide
13
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
WARNING
When opening the tapping point, the water temperature
can be up to 55°C.
Configuration
The indoor unit can control DHW pump operation. For more
information, see "8Configuration"on page39.
5.4 Setting up the energy metering
▪ Via the user interface, you can read out the following energy data:
▪ Produced heat
▪ Consumed energy
▪ You can read out the energy data:
▪ For space heating
▪ For domestic hot water production
▪ You can read out the energy data:
▪ Per month
▪ Per year
INFORMATION
The calculated produced heat and consumed energy are
an estimation, the accuracy cannot be guaranteed.
5.4.1 Produced heat
INFORMATION
The sensors used to calculate the produced heat are
calibrated automatically.
▪ The produced heat is calculated internally based on:
▪ The leaving and entering water temperature
▪ The flow rate
▪ Setup and configuration: No additional equipment needed.
5.4.2 Consumed energy
You can use the following methods to determine the consumed
energy:
▪ Calculating
▪ Measuring
INFORMATION
You cannot combine calculating the consumed energy
(example: for backup heater) and measuring the
consumed energy (example: for outdoor unit). If you do so,
the energy data will be invalid.
Calculating the consumed energy
▪ Only applicable for EHVZ04+08.
▪ The consumed energy is calculated internally based on:
▪ The actual power input of the outdoor unit
▪ The set capacity of the backup heater
▪ The voltage
▪ Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via
the user interface for the backup heater (step1).
Measuring the consumed energy
▪ Applicable for all models.
▪ Preferred method because of higher accuracy.
▪ Requires external power meters.
▪ Setup and configuration:
▪ For the specifications of each type of meter, see "14Technical
data"on page71.
▪ When using electrical power meters, set the number of pulses/
kWh for each power meter via the user interface. Consumed
energy data for EHVZ16 model will only be available if this
setting is configured.
INFORMATION
When measuring the electrical power consumption, make
sure ALL power input of the system is covered by the
electrical power meters.
5.4.3 Normal kWh rate power supply
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/7 and X5M/8.
Power meter type
In case of… Use a… power meter
▪ Single-phase outdoor unit
▪ Backup heater supplied from a
single-phase grid
Single-phase
Three-phase outdoor unit Three-phase
Example
Single-phase power meter Three-phase power meter
b
580150
0
0
c c
fed
A B
a
A Outdoor unit
B Indoor unit
a Electrical cabinet (L1/N)
b Power meter (L1/N)
c Fuse (L1/N)
d Outdoor unit (L1/N)
e Indoor unit (L1/N)
f Backup heater (L1/N)
b
580150
0
0
gfe
A B
c d
a
A Outdoor unit
B Indoor unit
a Electrical cabinet (L1/L2/L3/N)
b Power meter (L1/L2/L3/N)
c Fuse (L1/L2/L3/N)
d Fuse (L1/N)
e Outdoor unit (L1/L2/L3/N)
f Indoor unit (L1/L2/L3/N)
g Backup heater (L1/N)
Exception
▪ You can use a second power meter if:
▪ The power range of one meter is insufficient.
▪ The electrical meter cannot easily be installed in the electrical
cabinet.
▪ 230 V and 400 V three-phase grids are combined (very
uncommon), because of technical limitations of power meters.

5 Application guidelines
Installer reference guide
14
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
▪ Connection and setup:
▪ Connect the second power meter to X5M/9 and X5M/10.
▪ In the software the power consumption data of both meters is
added so you do NOT have to set which meter covers which
power consumption. You only need to set the number of pulses
of each power meter.
▪ See "5.4.4 Preferential kWh rate power supply" on page 14 for
an example with two power meters.
5.4.4 Preferential kWh rate power supply
General rule
▪ Power meter1: Measures the outdoor unit.
▪ Power meter 2: Measures the rest (i.e. indoor unit and backup
heater).
Setup
▪ Connect power meter1 to X5M/7 and X5M/8.
▪ Connect power meter2 to X5M/9 and X5M/10.
Power meter types
▪ Power meter 1: Single- or three-phase power meter according to
the power supply of the outdoor unit.
▪ Power meter2: Use a single-phase power meter.
5.5 Setting up the power consumption
control
▪ The power consumption control:
▪ Is only applicable for EHVZ04+08.
▪ Allows you to limit the power consumption of the entire system
(sum of outdoor unit, indoor unit and backup heater).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (inA)
▪ Maximum power input (inkW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs
5.5.1 Permanent power limitation
Permanent power limitation is useful to assure a maximum power or
current input of the system. In some countries, legislation limits the
maximum power consumption for space heating and DHW
production.
Pi
t
DI a
b
PiPower input
tTime
DI Digital input (power limitation level)
aPower limitation active
bActual power input
Setup and configuration
▪ No additional equipment needed.
▪ Set the power consumption control settings in [A.6.3.1] via the
user interface (for the description of all settings, see
"8Configuration"on page39):
▪ Select full time limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level
NOTICE
Mind the following guidelines when selecting the desired
power limitation level:
▪ Set a minimum power consumption of ±3.6 kW to
guarantee defrost operation. Otherwise, if defrosting is
interrupted several times, the heat exchanger will
freeze up.
▪ Set a minimum power consumption of ±3 kW to
guarantee space heating and DHW production by
allowing the backup heater step1.
5.5.2 Power limitation activated by digital
inputs
Power limitation is also useful in combination with an energy
management system.
The power or current of the entire Daikin system is limited
dynamically by digital inputs (maximum four steps). Each power
limitation level is set via the user interface by limiting one of the
following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation
of a certain power limitation level. Example: To limit the maximum
power of the entire house (lighting, domestic appliances, space
heating…).
a
b
A B
C
1
2
3
4
5
A8P
AOutdoor unit
BIndoor unit
CEnergy management system
aPower limitation activation (4 digital inputs)
bBackup heater
Pi
t
DI4
DI3
DI1 a
b
PiPower input
tTime
DI Digital inputs (power limitation levels)
aPower limitation active
bActual power input
Setup
▪ Demand PCB (option EKRP1AHTA) needed.

6 Preparation
Installer reference guide
15
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
▪ Maximum four digital inputs are used to activate the
corresponding power limitation level:
▪ DI1 = weakest limitation (highest energy consumption)
▪ DI4 = strongest limitation (lowest energy consumption)
▪ For the specifications of the digital inputs, and for where to
connect them, refer to the wiring diagram.
Configuration
Set the power consumption control settings in [A.6.3.1] via the user
interface (for the description of all settings, see "8Configuration"on
page39):
▪ Select activation by digital inputs.
▪ Select the type of limitation (power in kW or current in A).
▪ Set the desired power limitation level corresponding to each digital
input.
INFORMATION
In case more than 1 digital input is closed (at the same
time), the digital input priority is fixed: DI4 priority>…>DI1.
5.5.3 Power limitation process
The outdoor unit has better efficiency than the electrical heater.
Therefore, the electrical heater is limited and turned OFF first. The
system limits power consumption in the following order:
1 Turns OFF the backup heater.
2 Limits the outdoor unit.
3 Turns OFF the outdoor unit.
Example
If the configuration is as follows: Power limitation level does NOT
allow operation of backup heater (step1).
Then power consumption is limited as follows:
Ph
Ce
a
bc
A B
PhProduced heat
CeConsumed energy
AOutdoor unit
BBackup heater
aLimited outdoor unit operation
bFull outdoor unit operation
cBackup heater step1 turned ON
5.6 Setting up an external temperature
sensor
You can connect one external temperature sensor. It can measure
the indoor or outdoor ambient temperature. Daikin recommends to
use an external temperature sensor in the following cases:
Indoor ambient temperature
▪ In room thermostat control, the user interface is used as room
thermostat and it measures the indoor ambient temperature.
Therefore, the user interface must be installed on a location:
▪ Where the average temperature in the room can be detected
▪ That is NOT exposed to direct sunlight
▪ That is NOT near a heat source
▪ That is NOT affected by outside air or air draught because of,
for example, door opening/closing
▪ If this is NOT possible, Daikin recommends to connect a remote
indoor sensor (option KRCS01-1).
▪ Setup: For installation instructions, see the installation manual of
the remote indoor sensor.
▪ Configuration: Select room sensor [A.2.2.B].
Outdoor ambient temperature
▪ In the outdoor unit, the outdoor ambient temperature is measured.
Therefore, the outdoor unit must be installed on a location:
▪ At the north side of the house or at the side of the house where
the most heat emitters are located
▪ That is NOT exposed to direct sunlight
▪ If this is NOT possible, Daikin recommends to connect a remote
outdoor sensor (option EKRSCA1).
▪ Setup: For installation instructions, see the installation manual of
the remote outdoor sensor.
▪ Configuration: Select outdoor sensor [A.2.2.B].
▪ During suspend (see "8Configuration" on page 39), the outdoor
unit is turned down to reduce the standby energy losses. As a
result, the outdoor ambient temperature is NOT read out.
▪ If the desired leaving water temperature is weather dependent, the
full time outdoor temperature measurement is important. This is
another reason to install the optional outdoor ambient temperature
sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged
or instantaneous) is used in the weather-dependent control
curves. To protect the outdoor unit, the internal sensor of
the outdoor unit is always used.
6 Preparation
6.1 Overview: Preparation
This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the water piping
▪ Preparing the electrical wiring
6.2 Preparing installation site
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit must be covered.
Choose the installation location with sufficient place for carrying the
unit in and out of the site.

6 Preparation
Installer reference guide
16
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
NOTICE
This unit is designed for operation on 2 temperature zones:
▪ underfloor heating in the main zone (water
temperature 35°C), this is the zone with the lowest
water temperature,
▪ radiators in the additional zone (water temperature
45°C), this is the zone with the highest water
temperature.
6.2.1 Installation site requirements of the
outdoor unit
INFORMATION
Also read the following requirements:
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Service space requirements. See the "Technical data"
chapter.
▪ Refrigerant piping requirements (length, height
difference). See further in this "Preparation" chapter.
See "14.2 Dimensions and service space" on page 71 for more
detailed information about spacing guidelines.
▪ Select a place where rain can be avoided as much as possible.
▪ Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
Note: If the sound is measured under actual installation
conditions, the measured value might be higher than the sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
It is NOT recommended to install the unit in the following places
because it may shorten the life of the unit:
▪ in coastal areas or other places where the air contains high levels
of salt. Corrosion may occur,
▪ where the voltage fluctuates a lot,
▪ in vehicles or vessels,
▪ where acidic or alkaline vapour is present.
Strong winds (≥18km/h) blowing against the outdoor unit’s air outlet
causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
a
b
c
b
aBaffle plate
bPrevailing wind direction
cAir outlet
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging 10~43°C in cooling mode and –
25~25°C in heating mode.
6.2.2 Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
INFORMATION
You can use the optional snow cover (EK016SNC).
a
b
c
c
d
aSnow cover or shed
bPedestal (minimum height = 150mm)
cPrevailing wind direction
dAir outlet
6.2.3 Installation site requirements of the
indoor unit
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪ Mind the measurement guidelines:

6 Preparation
Installer reference guide
17
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
Maximum refrigerant piping length between indoor
unit and outdoor unit
ERHQ: 75m
(95m)(a)
ERLQ: 50m
(70m)(a)
Minimum refrigerant piping length between indoor
unit and outdoor unit
3m
Maximum height difference between indoor unit and
outdoor unit
30m
(a) Parenthesised figure represents the equivalent length.
▪ Mind the following spacing installation guidelines:
>500
>10>10
(mm)
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full
of water into account.
Make sure, in the event of a water leak, water cannot cause any
damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~35°C.
6.3 Preparing refrigerant piping
6.3.1 Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪Piping material: Phosphoric acid deoxidised seamless copper.
▪Piping diameter:
Liquid piping Ø9.5mm (3/8")
Gas piping Ø15.9mm (5/8")
▪Piping temper grade and thickness:
Outer diameter
(Ø)
Temper grade Thickness (t)(a)
9.5mm (3/8") Annealed (O) ≥0.8mm
t
Ø
15.9mm (5/8") Annealed (O) ≥1.0mm
(a) Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
6.3.2 Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Ambient
temperature
Humidity Minimum thickness
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm
6.4 Preparing water piping
6.4.1 Water circuit requirements
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in
the "Installation" chapter, respecting the water inlet and outlet.
▪Connecting piping – Force. Do NOT use excessive force when
connecting the piping. Deformation of the piping can cause
malfunctioning of the unit.
▪Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get
damaged.
▪Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
▪Closed circuit. Use the indoor unit ONLY in a closed water
system. Using the system in an open water system will lead to
excessive corrosion.
▪Glycol. For safety reasons, it is NOT allowed to add any kind of
glycol to the water circuit.
▪Piping length. It is recommended to avoid long runs of piping
between the domestic hot water tank and the hot water end point
(shower, bath,…) and to avoid dead ends.
▪Piping diameter. Select the water piping diameter in relation to
the required water flow and the available external static pressure
of the pump. See "14Technical data"on page71 for the external
static pressure curves of the indoor unit.
▪Water flow. You can find the minimum required water flow for
indoor unit operation in the following table. In all cases, this flow
needs to be guaranteed. When the flow is lower, the indoor unit
will stop operation and display error 7H.
Minimum required flow rate during defrost/backup heater
operation
04+08 models 12l/min
16 model 15l/min

6 Preparation
Installer reference guide
18
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
▪Field supply components – Water. Only use materials that are
compatible with water used in the system and with the materials
used in the indoor unit.
▪Field supply components – Water pressure and temperature.
Check that all components in the field piping can withstand the
water pressure and water temperature.
▪Water pressure. The maximum water pressure is 4bar. Provide
adequate safeguards in the water circuit to ensure that the
maximum pressure is NOT exceeded.
▪Water temperature. All installed piping and piping accessories
(valve, connections,…) MUST withstand the following
temperatures:
INFORMATION
The following illustration is an example and might NOT
match your system layout.
60°C
55°C
MM
a b c d ge h ii
ij
j
f
k
i
HPC1
FHL1 FHL2 FHL3
HPC2 HPC3
aOutdoor unit
bIndoor unit
cHeat exchanger
dBackup heater
eMotorised 3‑way valve (switch between space heating and
domestic hot water)
fMotorised 3‑way valve (mixing the main zone)
gMain pump
hAdditional pump
iShut-off valve
jCollector (field supply)
kDomestic hot water tank
HPC1...3 Heat pump convector (field supply)
FHL1...3 Floor heating loop (field supply)
▪Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the water circuit.
▪Drainage – Pressure relief valve. Provide a proper drain for the
pressure relief valve to avoid water dripping out of the unit. See
"7.8.5 To connect the pressure relief valve to the drain" on
page31.
▪Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. An automatic air
purge is provided in the indoor unit. Check that the air purge is
NOT tightened too much, so that automatic release of air in the
water circuit is possible.
▪Zn-coated parts. Never use Zn-coated parts in the water circuit.
Because the unit's internal water circuit uses copper piping,
excessive corrosion may occur.
▪Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do
NOT make contact with each other. This to prevent galvanic
corrosion.
▪Valve – Change‑over time. When using a 2-way valve or a 3-way
valve in the water circuit, the maximum change-over time of the
valve must be 60seconds.
▪Filter. It is strongly recommended to install an additional filter on
both heating water circuits. Especially to remove metallic particles
from foul heating piping, it is recommended to use a magnetic or
cyclone filter, which can remove small particles. Small particles
may damage the unit and will NOT be removed by the standard
filter of the heat pump system.
▪Domestic hot water tank – Capacity. To avoid stagnation of
water, it is important that the storage capacity of the domestic hot
water tank meets the daily consumption of domestic hot water.
▪Domestic hot water tank – After installation. Immediately after
installation, the domestic hot water tank must be flushed with fresh
water. This procedure must be repeated at least once a day the
first 5 consecutive days after installation.
▪Domestic hot water tank – Standstills. In cases where during
longer periods of time there is no consumption of hot water, the
equipment MUST be flushed with fresh water before usage.
▪Domestic hot water tank – Disinfection. For the disinfection
function of the domestic hot water tank, see "8.3.2 Domestic hot
water control: advanced"on page51.
▪Thermostatic mixing valves. In accordance with the applicable
legislation, it may be necessary to install thermostatic mixing
valves.
▪Hygienic measures. The installation must be in compliance with
the applicable legislation and may require additional hygienic
installation measures.
▪Recirculation pump. In accordance with the applicable
legislation, it may be required to connect a recirculation pump in
between the hot water end point and the recirculation connection
of the domestic hot water tank.
c
d
a b
aRecirculation connection
bHot water connection
cShower
dRecirculation pump
6.4.2 Formula to calculate the expansion vessel
pre-pressure
The pre-pressure (Pg) of the vessel depends on the installation
height difference (H):
Pg=0.3+(H/10) (bar)
6.4.3 To check the water volume and flow rate
The indoor unit has an expansion vessel of 10litre with a factory set
pre-pressure of 1bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
Minimum water volume
Check that the total water volume in the installation is minimum
10 litre for EHVZ04+08 and 20litre for EHVZ16, the internal water
volume of the indoor unit NOT included. Do NOT split up the
minimum water volume over the 2 temperature zones.

6 Preparation
Installer reference guide
19
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
It is sufficient to foresee the minimum water volume on the main
zone. In case of underfloor heating, this is easily done by 1 floor
heating loop that never will be closed by a (remotely) controlled
valve.
It is NOT required to foresee the minimum water volume on the
additional zone.
INFORMATION
In critical processes, or in rooms with a high heat load,
extra water might be required.
NOTICE
When circulation in each space heating loop is controlled
by remotely controlled valves, it is important that the
minimum water volume is guaranteed, even if all of the
valves are closed.
T1
M1
T1
M1
T2
M2
T3
M3
M
FHL1 FHL2 FHL3
M2 M3
T2 T3
HPC1 HPC2 HPC3
a b c
g hf
d e
i
i
hh
h
j
j
aOutdoor unit
bIndoor unit
cHeat exchanger
dBackup heater
eMotorised 3‑way valve (mixing the main zone)
fAdditional pump
gMain pump
hShut-off valve
iCollector (field supply)
jBy-pass valve (field supply)
FHL1...3 Floor heating loop (field supply)
HPC1...3 Heat pump convector (field supply)
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control loop FHL1...3 and
HPC1...3 (field supply)
Maximum water volume
Use the following graph to determine the maximum water volume for
the calculated pre-pressure.
0.3
0.5
1
1.5
2
2.5
100500
20
150 200 250 300 350 400 450
a
b
aPre-pressure (bar)
bMaximum water volume (l)
Example: Maximum water volume and expansion vessel pre-
pressure
Installation
height
difference(a)
Water volume
≤280l >280l
≤7m No pre-pressure
adjustment is required.
Do the following:
▪ Decrease the pre-
pressure.
▪ Check if the water
volume does NOT
exceed the maximum
allowed water volume.
>7m Do the following:
▪ Increase the pre-
pressure.
▪ Check if the water
volume does NOT
exceed the maximum
allowed water volume.
The expansion vessel of
the indoor unit is too
small for the installation.
In this case, it is
recommended to install
an extra vessel outside
the unit.
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is
at the highest point of the installation, the installation height
is 0m.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions on
each zone separately.
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating/operation).
Minimum required flow rate during defrost/backup heater
operation
04+08 models 12l/min
16 model 15l/min
See the recommended procedure as described in "9.4 Checklist
during commissioning"on page60.
6.4.4 Changing the pre-pressure of the
expansion vessel
NOTICE
Only a licensed installer may adjust the pre-pressure of the
expansion vessel.
When changing the default pre-pressure of the expansion vessel
(1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done
by releasing or increasing nitrogen pressure through the schräder
valve of the expansion vessel.

6 Preparation
Installer reference guide
20
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
a
aSchräder valve
6.4.5 To check the water volume: Examples
Example 1
The indoor unit is installed 5m below the highest point in the water
circuit. The total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit.
The total water volume in the water circuit is 350l.
Actions:
▪ Because the total water volume (350 l) is more than the default
water volume (280l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar=0.3bar.
▪ The corresponding maximum water volume at 0.3 bar is 410 l.
(See the graph in the chapter above).
▪ Because 350 l is lower than 410 l, the expansion vessel is
appropriate for the installation.
6.5 Preparing electrical wiring
6.5.1 About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
INFORMATION
Also read "7.9.5 Specifications of standard wiring
components"on page33.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable
legislation.
WARNING
The backup heater should have a dedicated power supply.
WARNING
ALWAYS use multicore cable for power supply cables.
6.5.2 About preferential kWh rate power supply
NOTICE
For applications with preferential kWh rate power supply:
The interruption of the outdoor unit power supply may not
be more than 2 hours to guarantee optimised startup
conditions for the compressor.
Electricity companies throughout the world work hard to provide
reliable electric service at competitive prices and are often
authorized to bill clients at benefit rates. E.g. time-of-use rates,
seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such preferential kWh rate
power supply delivery systems.
Consult with the electricity company acting as provider at the site
where this equipment is to be installed to know whether it is
appropriate to connect the equipment in one of the preferential kWh
rate power supply delivery systems available, if any.
When the equipment is connected to such preferential kWh rate
power supply, the electricity company is allowed to:
▪ interrupt power supply to the equipment for certain periods of time;
▪ demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the
unit switches into forced off mode. At that moment, the outdoor unit
compressor will not operate.
Whether the power supply is interrupted or not, the wiring to the unit
is different.
Other manuals for Altherma ERHQ011-014-016BA
1
This manual suits for next models
2
Table of contents
Other Daikin Temperature Controllers manuals

Daikin
Daikin REYQ-XA User manual

Daikin
Daikin Altherma EHVZ08S18CB Product information sheet

Daikin
Daikin 669529101 Instruction Manual

Daikin
Daikin EHVH04S18CA User manual

Daikin
Daikin FWEC2 User manual

Daikin
Daikin IOM 1177-1 Owner's manual

Daikin
Daikin BACnet 2508031 Manual

Daikin
Daikin EHBH04CB User manual

Daikin
Daikin 3MWKS80LV1 User manual

Daikin
Daikin BYCQ140E2GW1 User manual