OPERATOR'S MANUAL
Advanced Genset Controller, AGC 200
● Display readings
● Push-button functions
● Alarm handling
● Log list
Document no.: 4189340607E
SW version: 4.21.x or later

1. General information
1.1. Warnings, legal information and safety.................................................................................................. 3
1.1.1. Warnings and notes ......................................................................................................................3
1.1.2. Legal information and disclaimer ..................................................................................................3
1.1.3. Safety issues ................................................................................................................................ 3
1.1.4. Electrostatic discharge awareness ............................................................................................... 3
1.1.5. Factory settings ............................................................................................................................ 3
1.2. About the operator's manual.................................................................................................................. 4
1.2.1. General purpose ...........................................................................................................................4
1.2.2. Intended users ..............................................................................................................................4
1.2.3. Contents and overall structure ......................................................................................................4
2. AGC 200 variants
2.1. Front views.............................................................................................................................................5
2.1.1. Island, AGC 212/222/232/242....................................................................................................... 5
2.1.2. Automatic mains failure, AGC 213/233/243...................................................................................6
2.1.3. Mains, AGC 245............................................................................................................................ 7
2.1.4. Mains and tie breaker, AGC 246....................................................................................................8
2.1.5. Bus tie breaker, AGC 244..............................................................................................................9
3. Display, push-buttons and LEDs
3.1. Push-buttons functions.........................................................................................................................10
3.2. LED functions....................................................................................................................................... 11
4. Display and menu structure
4.1. About display and menu structures...................................................................................................... 12
4.1.1. LCD display ................................................................................................................................ 12
4.1.2. Menu structure ............................................................................................................................12
4.1.3. Entry window............................................................................................................................... 12
4.1.4. View menu...................................................................................................................................12
4.1.5. Status line text............................................................................................................................. 14
4.1.6. Running modes............................................................................................................................20
5. Alarm handling and log list
5.1. Alarm handling..................................................................................................................................... 21
5.2. Log list..................................................................................................................................................21
AGC 200 operators manual 4189340607
UK
DEIF A/S Page 2 of 21

1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
1.1.2 Legal information and disclaimer
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how
to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the
installation or the operation of the set must be contacted.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
1.1.3 Safety issues
Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,
the installation should only be carried out by authorised personnel who understand the risks involved in work-
ing with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
1.1.4 Electrostatic discharge awareness
Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the
unit is installed and connected, these precautions are no longer necessary.
1.1.5 Factory settings
The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values
and are not necessarily the correct settings for matching the engine/generator set in question. Precautions
must be taken to check the settings before running the engine/generator set.
AGC 200 operators manual 4189340607
UK
General information
DEIF A/S Page 3 of 21

1.2 About the operator's manual
1.2.1 General purpose
This Operator's Manual mainly includes general product information, display readings, push-button and LED
functions, alarm handling descriptions and presentation of the log list.
The general purpose of this document is to give the operator important information to be used in the daily
operation of the unit.
Please make sure to read this document before starting to work with the Multi-line 2 unit and
the generator set to be controlled. Failure to do this could result in human injury or damage to
the equipment.
1.2.2 Intended users
This Operator's Manual is mainly intended for the daily user. On the basis of this document, the operator will
be able to carry out simple procedures such as start/stop and control of the generator set.
1.2.3 Contents and overall structure
This document is divided into chapters, and in order to make the structure simple and easy to use, each
chapter will begin from the top of a new page.
AGC 200 operators manual 4189340607
UK
General information
DEIF A/S Page 4 of 21

2. AGC 200 variants
2.1 Front views
2.1.1 Island, AGC 212/222/232/242
AGC 200 operators manual 4189340607
UK
AGC 200 variants
DEIF A/S Page 5 of 21

2.1.2 Automatic mains failure, AGC 213/233/243
AGC 200 operators manual 4189340607
UK
AGC 200 variants
DEIF A/S Page 6 of 21

2.1.3 Mains, AGC 245
AGC 200 operators manual 4189340607
UK
AGC 200 variants
DEIF A/S Page 7 of 21

2.1.4 Mains and tie breaker, AGC 246
AGC 200 operators manual 4189340607
UK
AGC 200 variants
DEIF A/S Page 8 of 21

2.1.5 Bus tie breaker, AGC 244
AGC 200 operators manual 4189340607
UK
AGC 200 variants
DEIF A/S Page 9 of 21

3. Display, push-buttons and LEDs
3.1 Push-buttons functions
The display unit holds a number of push-button functions which are described below:
5
13
20
19
15161718
1 2 3 4
6
7
9
8
10
111214
1. View of measured values
2. Log lists. The list holds 150 events. These events are deleted when the AGC is switched off
3. Parameter settings
4. Service menu
5. Navigation buttons
6. Alarm list
7. Silence horn
8. Escape/step backwards
9. Test mode
10. Lamp test
11. Semi-auto mode
12. Off mode
13. Manual mode
14. Auto mode
15. MB open
16. MB close
17. GB open
18. GB close
19. Stop: stop of the genset if semi-auto or manual is selected
20. Start: start of the genset if semi-auto or manual is selected
AGC 200 operators manual 4189340607
UK
Display, push-buttons and LEDs
DEIF A/S Page 10 of 21

3.2 LED functions
The display unit holds 10 LED functions. The colour is green or red or a combination in different situations.
The display LEDs are indicating as follows:
1
59101112 8 467
32
1. User-configurable LED
2. LED indicates that the auxiliary supply is switched on
3. LED flashing indicates that unacknowledged alarms are present. LED fixed light indicates that ALL alarms
are acknowledged, but some are still present
4. Off mode
5. Semi-auto mode
6. Manual mode
7. Auto mode
8. LED is green if the mains is present and OK. LED is red at a mains failure. LED is flashing green when
the mains returns during the "mains OK delay" time
9. LED indicates that the mains breaker is closed
10. LED indicates that the generator breaker is closed
11. LED green light indicates that the voltage/frequency is present and OK
12. LED indicates that the generator is running
AGC 200 operators manual 4189340607
UK
Display, push-buttons and LEDs
DEIF A/S Page 11 of 21

4. Display and menu structure
4.1 About display and menu structures
4.1.1 LCD display
The display is a backlit LCD graphical display. The display light intensity, LED indication and contrast can be
adjusted from menu 9150.
Basically, all measured and calculated values can be read in the display. These may be selected via the PC
utility software (USW).
For selection of values, please refer to the Designer's Reference Handbook.
4.1.2 Menu structure
The display includes two menu systems which can be used without password entry:
View menu system
This is the commonly used menu system. 20 windows are configurable and can be entered by using the ar-
row push-buttons.
Setup menu system (not commonly used by the operator)
This menu system is used to set up the unit, and if the operator needs detailed information that is not availa-
ble in the view menu system.
Changing of parameter settings is password protected.
4.1.3 Entry window
When the unit is powered up, an entry window appears. The entry window is the turning point in the menu
structure and as such the gateway to the other menus. It can always be reached by pushing the BACK push-
button three times.
The event and alarm list will appear at power-up if an alarm is present.
MAINS FAILURE
U-supply 24.1 V
G 0.001 PF 0 kW
G 0 kVA 0 kVAr
Energy Total 0 kWh
Run Absolute 0 hrs
4.1.4 View menu
The view menus (V1, V2 and V3) are the daily use menus for the operator.
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 12 of 21

MAINS FAILURE
U-supply 24.1 V
G 0.001 PF 0 kW
G 0 kVA 0 kVAr
Energy Total 0 kWh
Run Absolute 0 hrs
2
3
1/20
1
4
In the view menus, various measured values are on display. The views contain up to 20 different windows
which can be selected using the and push-buttons located on the right hand side of the display.
1. First display line: operational status or measurements
2. Second display line: measurements relating to operational status
3. Third display line: measurements relating to operational status
4. Fourth display line: selection of setup and view menus
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 13 of 21

4.1.5 Status line text
This table explains the different messages.
Status text Condition Comment
BLOCK Block mode is activated
SIMPLE TEST Test mode is activated
LOAD TEST
FULL TEST
SIMPLE TEST ###.#min Test mode is activated and test timer count-
ing down
LOAD TEST ###.#min
FULL TEST ###.#min
ISLAND MAN Genset stopped or running and no other ac-
tion taking place
ISLAND SEMI
READY ISLAND AUTO Genset stopped in Auto
ISLAND ACTIVE Genset running in Auto
AMF MAN Genset stopped or running and no other ac-
tion taking place
AMF SEMI
READY AMF AUTO Genset stopped in Auto
AMF ACTIVE Genset running in Auto
FIXED POWER MAN Genset stopped or running and no other ac-
tion taking place
FIXED POWER SEMI
READY FIXED P AUTO Genset stopped in Auto
FIXED POWER ACTIVE Genset running in Auto
PEAK SHAVING MAN Genset stopped or running and no other ac-
tion taking place
PEAK SHAVING SEMI
READY PEAK SHAV AUTO Genset stopped in Auto
PEAK SHAVING ACTIVE Genset running in Auto
LOAD TAKEOVER MAN Genset stopped or running and no other ac-
tion taking place
LOAD TAKEOVER SEMI
READY LTO AUTO Genset stopped in Auto
LTO ACTIVE Genset running in Auto
MAINS P EXPORT MAN Genset stopped or running and no other ac-
tion taking place
MAINS P EXPORT SEMI
READY MPE AUTO Genset stopped in Auto
MPE ACTIVE Genset running in mains power export mode
DG BLCKD FOR START Generator stopped and active alarm(s) on
the generator
GB ON BLOCKED Generator running, GB open and an active
"Trip GB" alarm
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 14 of 21

Status text Condition Comment
SHUTDOWN OVERRIDE The configurable input is active
ACCESS LOCK The configurable input is activated, and the
operator tries to activate one of the blocked
keys
GB TRIP EXTERNALLY Some external equipment has tripped the
breaker
An external trip is
logged in the event
log
MB TRIP EXTERNALLY Some external equipment has tripped the
breaker
An external trip is
logged in the event
log
IDLE RUN The "Idle run" function is active The genset
will not stop, until a timer has expired
IDLE RUN ###.#min The timer in the "Idle run" function is active
COMPENSATION FREQ. Compensation is active The frequency is not
at the nominal set-
ting
Aux. test ##.#V ####s Battery test activated
DELOAD Decreasing the load of the genset in order to
open the breaker
START DG(s) IN ###s The start genset set point is exceeded
STOP DG(s) IN ###s The stop genset set point is exceeded
START PREPARE The start prepare relay is activated
START RELAY ON The start relay is activated
START RELAY OFF The start relay is deactivated during the start
sequence
MAINS FAILURE Mains failure and mains failure timer expired
MAINS FAILURE IN ###s Frequency or voltage measurement is out-
side the limits
The timer shown is
the mains failure de-
lay
MAINS U OK DEL ####s Mains voltage is OK after a mains failure The timer shown is
the mains OK delay
MAINS f OK DEL ####s Mains frequency is OK after a mains failure The timer shown is
the mains OK delay
Hz/V OK IN ###s The voltage and frequency of the genset is
OK
When the timer runs
out it is allowed to
operate the genera-
tor breaker
COOLING DOWN ###s Cooling down period is activated
Genset STOPPING This info is shown when cooling down has
finished
EXT. STOP TIME ###s
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 15 of 21

Status text Condition Comment
PROGRAMMING LANGUAGE This info is shown if the language file is
downloaded from the PC utility software
FAST SLOW
G
50.00 Hz
400 V
BB
50.19 Hz
400 V
Generator is synchronising The dot marks the
actual generator
phase angle position
in the synchronisa-
tion.
When the dot is at 12
o’clock, the genera-
tor and busbar are in
synchronism The
second dot indicates
when the relay out-
put for the generator
or mains breaker is
activated
FAST SLOW
G
50.00 Hz
400 V
BB
50.19 Hz
400 V
Generator running too slow during synchro-
nising
FAST SLOW
G
50.00 Hz
400 V
BB
50.19 Hz
400 V
Generator running too fast during synchronis-
ing
EXT. START ORDER A planned AMF sequence is activated There is no failure on
the mains during this
sequence
30 min data storage A safety precaution to protect the flash mem-
ory storage
Activated because
too many parameters
have been changed
within short time.
When active, no
flash or settings are
stored. This can be
caused by M-Logic
or Modbus
SELECT Genset MODE Power management has been deactivated
and no other genset mode has been selected
AGC 24x only
QUICK SETUP ERROR Quick setup of the application failed AGC 24x only
MOUNT CAN CONNECTOR Connect the power management CAN line AGC 24x only
ADAPT IN PROGRESS The AGC 200 is receiving the application that
it has just been connected to
AGC 24x only
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 16 of 21

Status text Condition Comment
SETUP IN PROGRESS The new AGC is being added to the existing
application
AGC 24x only
SETUP COMPLETED Successful update of the application in all
AGC units
AGC 24x only
REMOVE CAN CONNECTOR Remove the power management CAN lines AGC 24x only
RAMP TO #####kW The power ramp is ramping in steps, and the
next step that will be reached after the timer
has expired will be displayed
AGC 24x only
DERATED TO #####kW Displays the ramp down set point AGC 24x only
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 17 of 21

Texts only related to power management (AGC 24x and 22xvariants only)
Status text Condition Comment
DG unit
BLACKOUT ENABLE This information is shown if a CAN failure is present in
a power management application
UNIT STANDBY If redundant mains units are present, this message is
shown on the redundant unit
DELOADING BTB XX DG units are load sharing asymmetrically to deload
BTB XX dividing two sections in an application
BTB XX DIVIDING SEC. BTB XX is dividing two sections in an application
SYNCHRONISING TB XX TB XX is synchronising
SYNCHRONISING MB XX MB XX is synchronising
SYNCHRONISING BTB XX BTB XX is synchronising
Mains unit
UNIT STANDBY If redundant mains units are present, this message is
shown on the redundant unit
TB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is
logged in the event
log
BTB unit
DIVIDING SECTION A BTB unit is dividing two sections in an application
READY AUTO OPERATION BTB unit in Auto and ready for breaker operation (no
active "BTB trip" alarm)
SEMI OPERATION BTB unit in Semi
AUTO OPERATION BTB unit in Auto, but not ready for breaker operation
(active "BTB trip" alarm)
BLOCKED FOR CLOSING Last open BTB in a ring bus
BTB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is
logged in the event
log
All units
BROADCASTING APPL. # Broadcast of an application through the CAN line Broadcasts one of
the four applica-
tions from one unit
to the other AGCs
in the power man-
agement system
RECEIVING APPL. # AGC 200 receiving an application
BROADCAST COMPLETED Successful broadcast of an application
RECEIVE COMPLETED Application received successfully
BROADCAST ABORTED Broadcast terminated
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 18 of 21

Status text Condition Comment
RECEIVE ERROR Application is not received correctly
View menu example
MAINS FAILURE
U-supply 24.1 V
G 0.001 PF 0 kW
G 0 kVA 0 kVAr
AGC 200
2010-01-06 08:59:08
MAINS FAILURE
P 0 kW 0 %
Q 0 kVAr 0 %
S 0 kVA 0 %
AGC 200
2010-01-06 08:59:08
Press
MAINS FAILURE
Event log
Alarm log
Battery test log
MAINS FAILURE
MAINS FAILURE
Wed Jan 06 13:36:23
MB OFF
Wed Jan 06 13:36:23
Press Press
Press
MAINS FAILURE
Setup menu
1000 G -P> 1
1010 G -P> 2
1030 G I> 1
1040 G I> 2
MAINS FAILURE
Setup menu
1000 Protection
2000 Synchronisation
2500 Regulation
3000 Binary input
MAINS FAILURE
1010 G -P> 1
Setpoint : -9.0 %
Timer : 10.2 s
Output A : Not used
Output B : Not used
Press Press
The scrollbar
indicates that more
readings are
available below
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 19 of 21

4.1.6 Running modes
There are five buttons, located in the lower right corner of the AGC 200 display, which can be used to change
the running mode. (Some controller types will have less than five buttons). The running mode is changed by
pressing one of the buttons. There is also a lamp test button placed in the lower right corner. The table below
explains the functionality of the buttons.
Mode Description
SEMI ● Activate by pressing the SEMI button on the front of the AGC 200
● The display push-buttons (START, STOP, GB ON, GB OFF and so on) are active and can be
used by the operator
● The regulators are also active, that is the speed control will bring the generator to nominal
speed upon start
● When pushing a breaker button for closing, the AGC 200 will synchronise (if allowed) the
breaker. When the breaker closes, the regulation continues, but no breakers are opened or
closed
TEST ● Activate by pressing the TEST button on the front of the AGC 200
● The unit will start the generator, carry out the test sequence (predefined time period) and stop
the generator again. Subsequently, the generator will return to AUTO or SEMI-AUTO mode
(defined in parameter 7043). The mains breaker will remain closed, and the generator break-
er will remain open. NOTE: The test running can be: Simple test: Starting the genset without
closing the GB; Load test: Parallel to the mains and take load to a predefined value; Full test:
Transfer the load to the genset and open the MB (if the genset(s) is (are) capable of taking
the full load
AUTO ● Activate by pressing the AUTO button on the front of the AGC 200
● The unit will automatically carry out the genset/plant mode selected (AMF, fixed power, etc.)
● The display control push-buttons (START, STOP, GB ON, GB OFF) are disabled
● If the selected genset/plant mode is fixed power, mains power export, load takeover or island,
timer start/stop (week watch) or binary input, then start/stop can be used. (In PM systems
start/stop buttons can only be used from a mains unit with parameter 8021 set to local. If
used in a single DG application, start can only be set with a digital input or timer)
MAN ● Activate by pressing the MAN button on the front of the AGC 200
● The display push-buttons (START, STOP) are active and can be used by the operator
● The regulators are not active, that is speed (and voltage) control has to take place using ex-
ternal controls for generator speed and possibly generator voltage control
● The breakers will be able to open or close at any time. A synchronisation check will always
be performed to ensure safe closing of the breakers
BLOCK ● Activate by pressing the OFF button on the front of the AGC 200
● The unit will not be able to start. BLOCK mode can be selected during standstill or when run-
ning. If activated when running, the genset will stop and enter block mode. When block mode
is activated, no inputs will be able to start the genset. To exit block mode, press the AUTO/
SEMI or MAN button
AGC 200 operators manual 4189340607
UK
Display and menu structure
DEIF A/S Page 20 of 21
Other manuals for AGC 200 Series
4
Table of contents
Other Deif Controllers manuals
Popular Controllers manuals by other brands

Extreme Networks
Extreme Networks Summit WM3000 Series reference guide

LVS
LVS EPC-THPH installation instructions

Mitsubishi
Mitsubishi Alpha2 Series installation manual

Watlow Electric
Watlow Electric F4S Series user manual

Viessmann
Viessmann VITOTRONIC 300-K operating instructions

SSS Siedle
SSS Siedle SC 600-0 Product information