Deif AGC 150 User manual

OPERATOR's MANUAL
AGC 150
4189341186E

1. Introduction
1.1 About the operator's manual...............................................................................................................................................................................................3
1.2 Warnings and safety.................................................................................................................................................................................................................4
1.3 Legal information.......................................................................................................................................................................................................................4
2. Controller overview
2.1 Overview of buttons and LEDs...........................................................................................................................................................................................5
2.1.1 Display overview.................................................................................................................................................................................................................5
2.1.2 Display settings...................................................................................................................................................................................................................6
2.2 Controller types.......................................................................................................................................................................................................................... 7
2.2.1 Genset controller layouts................................................................................................................................................................................................ 7
2.2.2 Mains controller layouts...................................................................................................................................................................................................9
2.2.3 Bus tie breaker controller layouts............................................................................................................................................................................. 10
2.2.4 Engine Drive controller layout.................................................................................................................................................................................... 10
2.2.5 Hybrid controller layouts............................................................................................................................................................................................... 11
2.2.6 Mimic function................................................................................................................................................................................................................... 12
3. Running modes
3.1 Mode overview..........................................................................................................................................................................................................................14
4. Menu structure
4.1 Menu structure..........................................................................................................................................................................................................................15
4.2 The View menu..........................................................................................................................................................................................................................15
4.3 Status line texts........................................................................................................................................................................................................................16
4.4 Texts only related to power management..................................................................................................................................................................18
4.5 Default display views............................................................................................................................................................................................................ 20
4.6 Available display texts..........................................................................................................................................................................................................24
4.7 The Settings menu..................................................................................................................................................................................................................31
4.8 The Service View..................................................................................................................................................................................................................... 32
4.9 Menu numbers.......................................................................................................................................................................................................................... 32
4.10 The Jump function............................................................................................................................................................................................................... 33
4.11 Engine Drive shortcut menu........................................................................................................................................................................................... 33
4.12 Hybrid shortcut menu.........................................................................................................................................................................................................34
4.13 Remote Display local menu............................................................................................................................................................................................ 35
4.14 Exhaust after-treatment (Tier 4 Final/Stage V)......................................................................................................................................................35
5. Alarm handling and log list
5.1 Alarm handling......................................................................................................................................................................................................................... 37
5.2 Logs menu.................................................................................................................................................................................................................................. 38
OPERATOR's MANUAL 4189341186E EN Page 2 of 38

1. Introduction
1.1 About the operator's manual
General purpose
The general purpose of this document is to give the operator important information to be used in the daily operation of the controller.
DANGER!
Read this document before working with the AGC 150 controller. Failure to do this may result in human injury or damage to
the equipment.
Intended users of the Operator's manual
The Operator's manual is primarily intended for the operator that performs daily operations with the controller.
The manual includes an overview of the LEDs, push-buttons and screens on the controller, as well as general operator tasks,
alarms, and logs.
List of technical documentation for AGC 150
Document Contents
Product sheet
• Short description
• Controller applications
• Main features and functions
• Technical data
• Protections
• Dimensions
Data sheet
• General description
• Functions and features
• Controller applications
• Controller types and variants
• Protections
• Inputs and outputs
• Technical specifications
Designer's handbook
• Principles
• General controller sequences, functions and protections
• GENSET controller
• Mains controller
• BTB controller
• Hybrid controller
• Protections and alarms
• AC configuration and nominal settings
• Breaker and synchronisation
• Regulation
• Load sharing
• Hardware characteristics
• Modbus
Installation instructions • Tools and materials
OPERATOR's MANUAL 4189341186E EN Page 3 of 38

Document Contents
• Mounting
• Minimum wiring for the controller
• Wiring communication
Operator's manual
• Controller equipment (buttons and LEDs)
• Operating the system
• Alarms
• Log
Modbus tables
• Modbus address list
◦ PLC addresses
◦ Corresponding controller functions
• Descriptions for function codes, function groups
1.2 Warnings and safety
Factory settings
The controller is delivered pre-programmed from the factory with a set of default settings. These settings are based on typical values
and may not be correct for your system. You must therefore check all parameters before using the controller.
Data security
To minimise the risk of data security breaches DEIF recommends to:
• As far as possible, avoid exposing controllers and controller networks to public networks and the Internet.
• Use additional security layers like a VPN for remote access, and install firewall mechanisms.
• Restrict access to authorised persons.
1.3 Legal information
Third party equipment
DEIF takes no responsibility for the installation or operation of any third party equipment, including the genset. Contact the genset
company if you have any doubt about how to install or operate the genset.
Warranty
CAUTION
The AGC 150 controller is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not
take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.
If there is a discrepancy, the English version prevails.
Copyright
© Copyright DEIF A/S. All rights reserved.
OPERATOR's MANUAL 4189341186E EN Page 4 of 38

2. Controller overview
2.1 Overview of buttons and LEDs
2.1.1 Front overview
4
3
3
5
6
7
8
9
15 14 11 1112 12
1
17
16
2 3 3
18
1013
No. Name Function
1 Power ON Green: The controller power is ON.
OFF: The controller power is OFF.
2 Display screen
Resolution: 240 x 128 px.
Viewing area: 88.50 x 51.40 mm.
Six lines, each with 25 characters.
3 Navigation Move the selector up, down, left and right on the screen.
4 OK Enter the Menu system.
Confirm the selection on the screen.
5 Back Go to the previous page.
6 AUTO mode The controller automatically starts and stops gensets according to the system settings. No operator
actions are needed.
7 Silence horn Turns off an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Gives access to: Jump menu, Mode selection, Test, Lamp test, Hybrid (PV semi start and stop).
9 SEMI-AUTO
mode
The controller cannot automatically start, stop, connect or disconnect the genset.
The operator can start, stop, connect or disconnect the genset.
The controller automatically synchronises before closing a breaker, and automatically de-loads before
opening a breaker.
10 Mains symbol Green: Mains voltage and frequency are OK. The controller can synchronise and close the breaker.
Red: Mains failure.
11 Close breaker Press to close the breaker.
12 Open breaker Press to open the breaker.
OPERATOR's MANUAL 4189341186E EN Page 5 of 38

No. Name Function
13 Breaker symbols
Green: Breaker is ON.
Green flashing: Synchronising or de-loading.
Red: Breaker failure.
14 Generator
Green: Generator voltage and frequency are OK. The controller can synchronise and close the
breaker.
Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still running.
The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
15 Engine
Green: There is running feedback.
Green flashing: The engine is getting ready.
Red: The engine is not running, or there is no running feedback.
16 Stop Stops the genset if SEMI-AUTO or Manual is selected.
17 Start Starts the genset if SEMI-AUTO or Manual is selected.
18 Load symbol
OFF: Power management application.
Green: The supply voltage and frequency are OK.
Red: Supply voltage/frequency failure.
2.1.2 Display settings
It is possible to adjust the settings for the display to compensate for ambient lighting. Configure these settings under Settings >
Basic settings > Controller settings > Display > Display control.
Parameter no. Text Range Default
9151 Backlight dimmer 0 to 15 12
9152 Green LEDs dimmer 1 to 15 15
9153 Red LEDs dimmer 1 to 15 15
9154 Contrast level -20 to +20 0
9155 Sleep mode timer 1 to 1800 s 60 s
9156 Enable (Sleep mode timer) OFF
ON ON
9157 Alarm Jump OFF
ON ON
9158 Engineering units Bar/Celcius
PSI/Fahrenheit Bar/Celcius
OPERATOR's MANUAL 4189341186E EN Page 6 of 38

2.2 Controller types
2.2.1 Genset controller layouts
Single genset controller in Island mode
4
3
3
5
6
7
8
9
15 14 11 12
1
17
16
2 3 3
18
13
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. -
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
18. Load symbol
Single genset controller with Automatic Mains Failure (AMF)
4
3
3
5
6
7
8
9
15 14 11 1112 12
1
17
16
2 3 3
18
1013
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. Mains symbol
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
18. Load symbol
OPERATOR's MANUAL 4189341186E EN Page 7 of 38

Single genset controller in parallel without mains breaker
4
3
3
5
6
7
8
9
15 14 11 12
1
17
16
2 3 3
18
1013
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. Mains symbol
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
18. Load symbol
Genset controller in power management systems
4
3
3
5
6
7
8
9
15 14 11 12
1
17
16
2 3 3
13
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. -
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
OPERATOR's MANUAL 4189341186E EN Page 8 of 38

2.2.2 Mains controller layouts
Mains controller
4
3
3
5
6
7
8
9
1112
1
17
16
2 3 3
18
1013
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. Mains symbol
11. Close breaker
12. Open breaker
13. Breaker symbols
14. -
15. -
16. Stop
17. Start
18. Load symbol
Mains controller with tie breaker
4
3
3
5
6
7
8
9
11 1112 12
1
17
16
2 3 3
18
1013
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. Mains symbol
11. Close breaker
12. Open breaker
13. Breaker symbols
14. -
15. -
16. Stop
17. Start
18. Load symbol
OPERATOR's MANUAL 4189341186E EN Page 9 of 38

2.2.3 Bus tie breaker controller layouts
Bus tie braker controller
4
3
3
5
6
7
8
9
11 12
1
2 3 3
13
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. -
11. Close breaker
12. Open breaker
13. Breaker symbols
2.2.4 Engine Drive controller layout
Engine Drive controller
4
3
3
5
6
7
8
9
15
1
17
16
2 3 3
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. -
11. -
12. -
13. -
14. -
15. Engine
16. Stop
17. Start
18. -
OPERATOR's MANUAL 4189341186E EN Page 10 of 38

2.2.5 Hybrid controller layouts
Single genset controller in Island mode
4
3
3
5
6
7
8
9
15 14 11 12
1
17
16
2 3 3
18
13
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. -
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
18. Load symbol
Single genset controller with Automatic Mains Failure (AMF)
4
3
3
5
6
7
8
9
15 14 11 1112 12
1
17
16
2 3 3
18
1013
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. Mains symbol
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
18. Load symbol
OPERATOR's MANUAL 4189341186E EN Page 11 of 38

Single genset controller in parallel without mains breaker
4
3
3
5
6
7
8
9
15 14 11 12
1
17
16
2 3 3
18
1013
1. Power ON
2. Display screen (monochrome)
3. Navigation
4. OK
5. Back
6. AUTO mode
7. Silence horn
8. Short cut menu for commands
9. SEMI-AUTO mode
10. Mains symbol
11. Close breaker
12. Open breaker
13. Breaker symbols
14. Generator
15. Engine
16. Stop
17. Start
18. Load symbol
2.2.6 Mimic function
With the Mimic function the operator can choose how the control buttons and LED's are shown on AGC 150, and thereby get a
better overview of the controller in different applications.
Configure the Mimic function under Settings > Basic settings > Controller settings > Display > LED mimic.
Parameter no. Item Range
6082 LED mimic
Standard with genset
Standard
Guided with genset
Guided
Standard
Control buttons and LED's are continuously visible.
If the genset is stopped, the motor/generator symbols are OFF.
Standard with genset
Control buttons and LED's are continuously visible.
If the genset is stopped, the motor/generator symbols are shown in red.
OPERATOR's MANUAL 4189341186E EN Page 12 of 38

Guided
Active control buttons and LED's are visible, inactive are not shown.
Example: AGC 150 is in SEMI-AUTO mode. The generator is stopped.
The only possible action is to start the generator, and so only the Start
button is visible.
Guided with genset
Active control buttons, LED's and motor/generator symbols are visible,
inactive are not shown.
Example: AGC 150 is in SEMI-AUTO mode. The generator is stopped.
The only possible action is to start the generator, and so only the Start
button and the red motor/generator symbols are visible.
All Mimic settings
The breaker symbol flashes green:
• Controller is synchronising
• Controller is de-loading
The breaker symbol turns red:
• Breaker position failure
• Breaker close failure
OPERATOR's MANUAL 4189341186E EN Page 13 of 38

3. Running modes
3.1 Mode overview
AGC 150 has four different running modes and one block mode:
•AUTO: In AUTO mode, the controller will operate automatically, and the operator cannot initiate any sequences manually.
•SEMI-AUTO: In SEMI-AUTO mode, the operator has to initiate all sequences. This can be done via the push-button functions,
Modbus commands or digital inputs. When started in SEMI-AUTO mode, the genset will run at nominal values.
•Test: The test sequence will start when the test mode is selected.
•Manual: When Manual mode is selected, the digital increase/decrease inputs can be used (if they have been configured) as well
as the Start and Stop push-buttons. When starting in Manual mode, the genset will start without any subsequent regulation.
•Block: When the block mode is selected, the controller is not able to initiate any sequences, for example the start sequence.
Block mode must be selected when maintenance work is carried out on the genset.
CAUTION
The genset will shut down if block mode is selected while the genset is running.
OPERATOR's MANUAL 4189341186E EN Page 14 of 38

4. Menu structure
4.1 Menu structure
The AGC 150 has two menu systems, which can be used without password entry:
•The View menu system: The commonly used menu system, with 20 configurable windows that can be entered with the arrow
buttons.
•The Settings menu system: The menu system for setting up the controller, and to see detailed information that is not available
in the view menu system.
Changes to the parameter settings are password protected.
4.2 The View menu
When AGC 150 is powered up, the View menu appears. It is the daily use menu for the operator, which shows various measured
values. If an alarm is present, the event and alarm list is shown at power-up.
Figure 4.1 The View menu
1. Status line.
2. Operational status or measurements.
3. View Page number, Power Management priority (if available) or Engine DEF level (if available).
The View menu contains up to 20 different pages. Navigate through the pages with the Up and Down buttons.
Figure 4.2 Example: Navigating the View menu
G
G
PM-Prio:01 1/20
DG BLOCKED FOR START
U-Supply
Energy Total
Run absolute
0kvar
0kWh
0hrs
0kW
25.9V
0.00PF
0kVa
BB L1
G
PM-Prio:01 2/20
DG BLOCKED FOR START
Energy Total
Run absolute
0kvar
0kWh
0hrs
0kW
0.00Hz 0kW
G L1 0.00Hz
0.00PF
Press
OPERATOR's MANUAL 4189341186E EN Page 15 of 38

4.3 Status line texts
Status text Condition Comment
BLOCK Block mode is activated.
SIMPLE TEST
Test mode is activated.
LOAD TEST
FULL TEST
SIMPLE TEST ###.#min
Test mode is activated and test timer
counting down.
LOAD TEST ###.#min
FULL TEST ###.#min
ISLAND MAN Genset stopped or running and no other
action taking place.
ISLAND SEMI
ISLAND AUTO
Genset stopped in AUTO mode.
READY ISLAND AUTO
ISLAND ACTIVE Genset running in AUTO mode.
AMF MAN Genset stopped or running and no other
action taking place.
AMF SEMI
AMF AUTO
Genset stopped in AUTO mode.
READY AMF AUTO Genset is stopped, ready to auto start with
mains failure.
AMF ACTIVE Genset running in AUTO mode.
FIXED POWER MAN Genset stopped or running and no other
action taking place.
FIXED POWER SEMI
READY FIXED P AUTO Genset stopped in AUTO mode.
FIXED POWER ACTIVE Genset running in AUTO mode.
PEAK SHAVING MAN Genset stopped or running and no other
action taking place.
PEAK SHAVING SEMI
PEAK SHAVING AUTO
READY PEAK SHAV AUTO Genset stopped in AUTO mode.
PEAK SHAVING ACTIVE Genset running in AUTO mode.
LOAD TAKE OVER MAN Genset stopped or running and no other
action taking place.
LOAD TAKE OVER SEMI
LOAD TAKE OVER AUTO
READY LTO AUTO Genset stopped in AUTO mode. Genset is stopped, ready to start and load
take-over.
LTO ACTIVE Genset running in AUTO mode. Genset is running, ready for load take-
over.
MAINS P EXPORT MAN Genset stopped or running and no other
action taking place.
MAINS P EXPORT SEMI
MAINS P EXPORT AUTO
READY MPE AUTO Genset stopped in AUTO mode.
OPERATOR's MANUAL 4189341186E EN Page 16 of 38

Status text Condition Comment
MPE ACTIVE Genset running in mains power export
mode.
DG BLOCKED FOR START Generator stopped and active alarm(s) on
the generator.
GB ON BLOCKED Generator running, GB open and an
active Trip GB alarm.
SHUTDOWN OVERRIDE The configurable input is active.
ACCESS LOCK
The configurable input is activated, and
the operator tries to activate one of the
blocked keys.
GB TRIP EXTERNALLY Some external equipment has tripped the
breaker. An external trip is logged in the event log.
MB TRIP EXTERNALLY Some external equipment has tripped the
breaker. An external trip is logged in the event log.
IDLE RUN The Idle run function is active. The genset
will not stop until a timer has expired.
IDLE RUN ###.#min The Idle run function is active and the
timer is counting down.
COMPENSATION FREQ Compensation is active. The frequency is not at the nominal
setting.
Aux. test ##.#V ####s Battery test activated, and the timer is
counting down.
DELOAD Decreasing the load of the genset in order
to open the breaker.
START DG(s) IN ###s The start genset set point is exceeded. Genset will start when timer expires.
STOP DG(s) IN ###s The stop genset set point is exceeded. Genset will stop when timer expires.
START PREPARE The start prepare relay is activated.
START RELAY ON The start relay is activated.
START RELAY OFF The start relay is deactivated during the
start sequence.
MAINS FAILURE Mains failure and mains failure timer
expired.
MAINS FAILURE IN ###s Frequency or voltage measurement is
outside the limits.
The timer shown is the mains failure
delay.
MAINS U OK DEL ####s Mains voltage is OK after a mains failure. The timer shown is the mains OK delay.
MAINS f OK DEL ####s Mains frequency is OK after a mains
failure. The timer shown is the mains OK delay.
Hz/V OK IN ###s The voltage and frequency on the genset
is OK.
When the timer runs out, it is allowed to
operate the generator breaker.
COOLING DOWN ###s Cooling-down period is activated.
GENSET STOPPING This info is shown when cooling down has
finished.
EXT. STOP TIME ###s
---xx-------- >00< ------------ Generator is synchronising.
The "xx" marks the actual generator
phase angle position in the
synchronisation. When the "xx" is aligned
OPERATOR's MANUAL 4189341186E EN Page 17 of 38

Status text Condition Comment
over the 00 centre, the generator is
synchronised.
TOO SLOW 00<------------- Generator running too slow during
synchronisation.
-----------> 00 TOO FAST Generator running too fast during
synchronisation.
EXT. START ORDER A planned AMF sequence is activated. There is no failure on the mains during
this sequence.
SELECT GENSET MODE
Power management has been deactivated
and no other genset mode has been
selected.
RAMP TO #####kW
The power ramp is ramping in steps, and
the next step that will be reached after the
timer has expired will be displayed.
DERATED TO #####kW Displays the ramp-down set point.
UNEXPECTED GB ON BB
Another generator breaker is closed on to
the busbar (due to a GB position failure)
while no voltage is present on the busbar.
This indicates that other breakers cannot
close to the busbar because of position
failure on one or more GBs.
WARM UP RAMP Warm up ramp is active.
The available power is limited until the
predefined temperature is reached or
when the input which activated warm up
ramp is set low.
SUNSPEC IDENTIFYING* Connecting to PV inverter. Only Sunspec inverters
SUNSPEC INCOMPATIBLE* PV inverter is not compatible. Only Sunspec inverters
SUNSPEC INITIALIZED* PV inverter is successfully initialized. Only Sunspec inverters
NOTE *Only AGC 150 Hybrid version.
4.4 Texts only related to power management
Table 4.1 All controller types
Status text Condition Comment
BROADCASTING APPL. # Broadcast of an application through the
CAN line.
Broadcasts one of the four applications
from one AGC 150 to the other controllers
in the power management system.
RECEIVING APPL. # Receiving an application.
BROADCAST COMPLETED Successful broadcast of an application.
RECEIVE COMPLETED Application received successfully.
BROADCAST ABORTED Broadcast terminated.
RECEIVE ERROR Application is not received correctly.
QUICK SETUP ERROR Quick setup of the application failed.
MOUNT CAN CONNECTOR Connect the power management CAN
line.
ADAPT IN PROGRESS
The AGC 150 is receiving the
application,to which it has just been
connected.
OPERATOR's MANUAL 4189341186E EN Page 18 of 38

Status text Condition Comment
SETUP IN PROGRESS The new controller is being added to the
existing application.
SETUP COMPLETED Successful update of the application in all
AGC 150 controllers.
REMOVE CAN CONNECTOR Remove the power management CAN
lines.
Table 4.2 DG controller
Status text Condition Comment
BLACKOUT ENABLE
This info is shown if a CAN failure is
present in a power management
application.
UNIT STANDBY If redundant mains units are present, this
message is shown on the redundant unit.
DELOADING BTB XX
DG units are load sharing asymmetrically
to de-load BTB XX dividing two sections in
an island application.
BTB XX DIVIDING SEC. BTB XX is dividing two sections in an
island application.
SYNCHRONISING TB XX TB XX is synchronising.
SYNCHRONISING MB XX MB XX is synchronising.
SYNCHRONISING BTB XX BTB XX is synchronising.
De-loading TB XX Displays that a tie breaker is being de-
loaded in SEMI-AUTO mode.
Table 4.3 Mains controller
Status text Condition Comment
UNIT STANDBY If redundant mains units are present this
message is shown on the redundant unit.
TB TRIP EXTERNALLY Some external equipment has tripped the
breaker. An external trip is logged in the event log.
Table 4.4 BTB controller
Status text Condition Comment
DIVIDING SECTION A BTB unit is dividing two sections in an
island application.
READY AUTO OPERATION
BTB unit in AUTO mode and ready for
breaker operation (no active BTB trip
alarm).
SEMI OPERATION BTB unit in SEMI-AUTO mode.
AUTO OPERATION BTB unit in AUTO mode, but not ready for
breaker operation (active BTB trip alarm).
BLOCKED FOR CLOSING Last open BTB in a ring bus.
BTB TRIP EXTERNALLY Some external equipment has tripped the
breaker. An external trip is logged in the event log.
OPERATOR's MANUAL 4189341186E EN Page 19 of 38

4.5 Default display views
Overview of the default display views 1 to 20. The display views are customisable via the Utility Software .
Table 4.5 Display view 1
Line Generator Mains BTB Hybrid Engine Drive
1 U-Supply 0.0V U-Supply 0.0V U-Supply 0.0V PV OFF 0kvar 0kW U-Supply 0.0V
2 G 0.00PF 0kW M 0.00PF 0kW BA L1 0.00Hz 0V G 0.00PF 0kW MPU 0rpm
3 G 0kVA 0kvar M 0kVA 0kvar BA 0kVA 0kvar G 0kVA 0kvar -
4 Energy Total 0kWh Energy Total 0kWh BA 0.00PF 0kW G energy Total 0kWh [yyyy-mm-dd time]
5 Run absolute 0 hrs M 0.00PF 0kW BA 0 0 0A Run absolute 0hrs Run absolute 0 hrs
Table 4.6 Display view 2
Line Generator Mains BTB Hybrid Engine Drive
1 BB L1 0.00Hz 0V BB L1 0.00Hz 0V BB L1 0.00Hz 0V BB L1 0.00Hz 0V Multi input 20 0.0V
2 G L1 0.00Hz 0V M L1 0.00Hz 0V BA L1 0.00Hz 0V G L1 0.00Hz 0V Multi input 21 0.0V
3 G 0.00PF 0kW M 0.00PF 0kW BA 0kVA 0kvar G 0.00PF 0kW Multi input 22 0.0V
4 G 0kVA 0kvar M 0kVA 0kvar BA 0.00PF 0kW G 0kVA 0kvar Multi input 23 0.0V
5 G 0 0 0A M 0 0 0A BA 0 0 0A G 0 0 0A -
Table 4.7 Display view 3
Line Generator Mains BTB Hybrid Engine Drive
1 - - - - Aftertreatment
2 Synchroniser
(graphic)
Synchroniser
(graphic)
Synchroniser
(graphic)
Synchroniser
(graphic) -
3 - - - - -
4 - - - - -
5 - - - - -
Table 4.8 Display view 4
Line Generator Mains BTB Hybrid Engine Drive
1 BB L1 0.00Hz 0V M 0 0 0V BA 0 0 0V BB L1 0.00Hz 0V T. Coolant N.A.
2 G 0.00PF 0kW M L1 0.00Hz 0V BA f-L1 0.00Hz G 0.00PF 0kW T. TurboOil N.A.
3 G 0kVA 0kvar - - G 0kVA 0kvar T. Exh. R N.A.
4 G 0 0 0A BB 0 0 0V BB 0 0 0V G 0 0 0A T. Oil N.A.
5 G L1 0.00Hz 0V BB L1 0.00Hz 0V BB f-L1 0.00Hz G L1 0.00Hz 0V T. Fuel N.A.
Table 4.9 Display view 5
Line Generator Mains BTB Hybrid Engine Drive
1 G U-L1L2 0V M P 0kW BA P 0kW G U-L1L2 0V Serv1 0d 0h
2 G U-L2L3 0V M Q 0kvar BA Q 0kvar G U-L2L3 0V Serv2 0d 0h
OPERATOR's MANUAL 4189341186E EN Page 20 of 38
Other manuals for AGC 150
9
Table of contents
Other Deif Controllers manuals
Popular Controllers manuals by other brands

DoorKing
DoorKing 4302 owner's manual

ECS
ECS SiS180 user manual

Muller Elektronik
Muller Elektronik SPRAYER-Controller Orchard/Vineyard MIDI 3.0 operating instructions

DMP Electronics
DMP Electronics 736V V-PLEX Module Advanced Settings Guide

Datapath
Datapath X4 Setup guide

Emerson
Emerson Bettis G10 Series Service instructions

Zksoftware
Zksoftware C3-100 Installation Instructions and Connection Guide

Hobby-Wing
Hobby-Wing Xerun XR10 Pro user manual

TRENDnet
TRENDnet TEW-WLC100 user guide

WorkPro
WorkPro LM 5 user manual

EQ3
EQ3 HmIPW-DRS4 Installation instructions and operation manual

Targetti
Targetti Chroma-Cue installation guide