manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Delta
  6. •
  7. Control Unit
  8. •
  9. Delta DVP06XA-H User manual

Delta DVP06XA-H User manual

http://www.delta.com.tw/products/plc.asp
DVP-EH
DVP06XA-H
Analog Input/Output Mixed Module
Instruction Sheet
1 WARNING
Always read this manual thoroughly before using the DVP06XA-H.
In order to avoid electric shock, do not touch the terminals or conduct any maintenance while
power is applied to the PLC. Never open the PLC. Only qualified Delta personell should
conduct any internal electrical work on the PLC.
This is an OPEN-TYPE device and is certified to meet the safety requirements of IEC 61131-2
(UL 508) when installed in an enclosure.
The DVP06XA-H must be placed in an environment away from high temperatures, high humidity,
exceessive vibration, corrosive gases, liquids, airborne dust, and metallic particles.
Do not apply AC power to any of the input/output terminals, this will cause permanent damage to
the DVP06XA-H.
Do not touch the internal circuit for at least 1 minute after the power supply is disconnected.
Make sure that the DVP06XA-H is properly grounded , to avoid any electromagnetic noise.
2 INTRODUCTION
2.1 Model Explanation and Peripherals
 Thank you for choosing DELTA’s DVP Series PLC. The DVP06XA-H allows the connection of four
analog inputs and 2 groups 12 bits digital outputs (voltage/current). The DVP-PLC EH Series MPU
transforms the input into a 12 bit digital signal and the output into a 2 points analog signal, which
may then be manipulated using TO and FROM commands in the ladder logic program. There are
49 Controlled Registers (CR) in each module (each register is 16 bits).
 DVP06XA-H analog input/output module can update software version by RS-485 communication.
 Users can select input from voltage or current via wiring. Voltage input range is ±10V DC
(resolution is 5 mV) and current is ±20 mA (resolution is 20 µA).
 Users can select output from voltage or current via wiring. Voltage output range is 0V ~ +10V DC
(resolution is 2.5 mV) and current is 0 mA ~ 20 mA (resolution is 5 µA).
 Nameplate Explanation
20.4VDC ~ 28.8VDC
VX.XX 06XA-H0T4130003
0 ~ +10V or -0 ~+20mA
Model Name
Input power supply spec.
Analog input/output module spec.
Barcode
/0 ~ +10V or 2.5mA~+20mA
5mV or 20 A / 2.5mV or 5 A
 Model Explanation
Model Serial Number
Product Series
Input+Output point
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors(PT-100)
TC: Thermocouple sensors(Type J/K)
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
Production week
Production place (Taoyuan)
Production year (2004)
Production Model
XA: A/D , D/A Functions
RT: Resistor Thermocouple
HC: High speed count input module
PU: single axis positioning unit
2.2 Product Profile and Outline
Unit: mm
1. DIN rail location (35mm) 6. Terminals
2. Mounting hole to connect expansion
unit/expansion module
7. Expansion hole of the expansion unit
mounting pins
3. Model name 8. Terminal layout
4. Indicator LED for power, error and run state 9. Mounting port to connect expansion
unit/expansion module
5. DIN rail clip
2.3 External Wiring
CH1
104.7K
250
-10V~+10V
V+
I+
COM
CH1
104.7K
CH4
104.7K
250
-20mA~+20mA V+
I+
COM
CH4
104.7K
*3
*2
AG
AG
Current input
Voltage input
Shielded*1
Shielded*1
Note 1: Please isolate analog input and other
power wiring.
Note 2: If input connected current signal,
please short circuit between V+ and
I+ terminals.
Note 3: If wave of input terminal of loaded is
too big that noise interferes wiring,
please connect capacitance with
0.1~0.47µF 25V.
V+
I+
COM
CH5
-10V~+10V
*5
CH5
V+
I+
COM
CH6
0mA~20mA CH6
24+
24-
DC24V DC/DC +15V
-15V
AG
Voltage input
Shieled*1
Shieled*4
Current output
converter
connect to
of power module
AC drive
Class 3 grounding
(100 and less)
AC drive
Note 4: Please isolate analog output and other
power wiring.
Note 5: If wave of output terminal of loaded is
too big that noise interferes wiring,
please connect capacitance with
0.1~0.47µF 25V.
Note 6: Please connect terminal of power
module and terminal of analog
output module to system earth point
and make system earth point be
grounding or connects to machine
cover.
Warning: DO NOT wire to the No function
terminal ●.
3 STANDARD SPECIFICATIONS
3.1 Specifications
Mixed (06XA) module, Analog/
Digital (A/D) Module Voltage input Current input
Power Supply Voltage 24 VDC(20.4VDC~28.8VDC) ( –15%〜+20%)
Analog Input Channel 4 channels per module
Analog Input Range ±10V ±20 mA
Digital Data Range ±2000 ±1000
Resolution 12 bits(1LSB=5 mV) 11 bits (1LSB=20 µA)
Input Impedance 200 KΩand above 250Ω
Overall Accuracy ±0.5% of full scale of 25℃(77℉)
±1% of full scale during 0~55℃(32~131℉)
Response Time 3 ms ×channels
Isolation Method Isolation between digital and analog circuitry.
Absolution Input Range ±15 V ±32 mA
Digital Data Format 2’s complement of 16-bit, (13 Significant Bits)
Average Function Yes (CR#2~CR#5 can be set and the range is K1~K4096)
Self diagnostic function Self
Detection Upper bound and lower bound detection per channel
Mixed (06XA) module,
Digital/Analog (D/A) Module Voltage Output Current Output
Analog Signal Output Channels 2 channel per module
Analog Output Range 0~10V 0~20 mA
Digital Data Range 0~4000 0~4000
Resolution 12 bits (1LSB=2.5 mV) 12 bits (1LSB=5 µA)
Output Impedance 0.5Ωor lower
Overall Accuracy ±0.5% of full scale of 25℃(77℉)
±1% of full scale during 0~55℃(32~131℉)
Response Time 3 ms ×Channels
Max. Output Current 20 mA(1KΩ~2MΩ) -
Tolerance Carried Impedance -0〜500Ω
Digital Data Format 2’s complement of 16-bit, (13 Significant Bits)
Isolation Method Isolation between inner circuit and analog output terminal. There is
no isolation between channels.
Protection
Voltage output has short circuit protection but short circuit for a
long time may cause inner wiring damage and current output
break.
Communication mode (RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 /
9600 / 19200 / 38400 / 57600 / 115200. For ASCII mode, date
format is 7Bits, even, 1 stop bit (7 E 1). For RTU mode, date format
is 8Bits, even, 1 stop bit (8 E 1). The RS-485 is disabled when the
DVP06XA-H is connected in series to an MPU.
Connect to DVP-PLC MPU in
series
When DVP06XA-H modules are connected to an MPU, the
modules are numbered from 0 - 7. 0 is the closest to the MPU and
7 is the furthest. The Maximum number of modules is 8 modules
and they do not occupy any digital I/O points of the MPU.
3.2 Other Specification
Power Specification
Maximum Power Consumption 2W at 24 VDC (20.4VDC~28.8VDC) ( -15 % ~ +20 %) supply
from external power
Environment Condition
Environment Condition Follow the DVP-PLC MPU
Static Electricity Prevention Proper grounding and handling required of the unit and terminals
4CR(Controlled Register)
DVP06XA-H Analog Input/Output Mixed Module Explanation
CR
No
RS-485
Paramete
r Address
Latched Register Name b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0 H 40C8 ○R Model type System used. DVP06XA-H model code= H0604
CH6 CH5 CH4 CH3 CH2 CH1#1 H 40C9 ○R/W Input/Output mode setting
Input mode setting: (CH1~CH4)
Mode 0: input voltage mode (-10V~+10V). Factory Setting is H0000.
Mode 1: input voltage mode (-6V~+10V).
Mode 2: input current mode (-12mA~+20mA).
Mode 3: input current mode (-20mA~+20mA).
Mode 4: none use.
Output mode setting: (CH5~CH6)
Mode 0: output voltage mode (0V~10V).
Mode 1: output voltage mode (2V~10V).
Mode 2: output current mode (4mA~20mA).
Mode 3: output current mode (0mA~20mA).
#2 H 40CA ○R/W CH1 average times
#3 H 40CB ○R/W CH2 average times
#4 H 40CC ○R/W CH3 average times
#5 H 40CD ○R/W CH4 average times
The number of readings used for “average” times on channels CH1~CH4.
Setting range is K1~K4096 and factory setting is K10.
#6 H 40CE ╳R average value of CH1 input
signal
#7 H 40CF ╳R average value of CH2 input
signal
#8 H 40D0 ╳R average value of CH3 input
signal
#9 H 40D1 ╳R average value of CH4 input
signal
Display average value of CH1~CH4 input signal
#10 H 40D2 ╳R/W CH5 output signal value
#11 H 40D3 ╳R/W CH6 output signal value
Output value of CH5~CH6, the setting range is K0~K4000. The factory setting is
K0 and the unit is LSB.
#12 H 40D4 ╳R present value of CH1 input
signal
#13 H 40D5 ╳R present value of CH2 input
signal
#14 H 40D6 ╳R present value of CH3 input
signal
#15 H 40D7 ╳R present value of CH4 input
signal
Display present value of CH1~CH4 input signal
#16~ #17 Reserved
#18 H 40DA ○R/W To adjust OFFSET value of
CH1
#19 H 40DB ○R/W To adjust OFFSET value of
CH2
#20 H 40DC ○R/W To adjust OFFSET value of
CH3
#21 H 40DD ○R/W To adjust OFFSET value of
CH4
Offset setting of CH1~CH4. Factory setting is K0 and unit is LSB.
Voltage input: setting range is K-1000 ~K1000
Current input: setting range is K-1000 ~K1000
#22 H 40DE ○R/W To adjust OFFSET value of
CH5
#23 H 40DF ○R/W To adjust OFFSET value of
CH6
Offset setting of CH5~CH6. Factory setting is K0 and unit is LSB.
The setting range is K-2000~K2000
#24 H 40E0 ○R/W To adjust GAIN value of
CH1
#25 H 40E1 ○R/W To adjust GAIN value of
CH2
#26 H 40E2 ○R/W To adjust GAIN value of
CH3
#27 H 40E3 ○R/W To adjust GAIN value of
CH4
GAIN setting of CH1~CH4. Factory setting is K1000 and unit is LSB.
Voltage input: setting range is K-800 ~K4000
Current input: setting range is K-800 ~K2600
#28 H 40E4 ○R/W To adjust GAIN value of
CH5
#29 H 40E5 ○R/W To adjust GAIN value of
CH6
GAIN setting of CH5~CH6. Factory setting is K2000 and unit is LSB.
The setting range is K-1600~K8000
#30 H 40E6 ╳R Error status Data register stores the error status, refer to fault code chart for details.
#31 H 40E7 ○R/W Communication address
setting
RS-485 communication address.
Setting range is K1~K255 and factory setting is K1
#32 H 40E8 ○R/W Communication baud rate
setting
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps).
For ASCII mode, date format is 7Bits, even, 1 stop bit (7 E 1). For RTU mode,
date format is 8Bits, even, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec). b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec). b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec). b5: 115200 bps (bit/sec).
b6~b13: Reserved.
b14: switch between low bit and high bit of CRC code (only for RTU mode)
b15: RTU mode.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH6 CH5 CH4 CH3 CH2 CH1
#33 H 40E9 ○R/W Reset to factory setting and
set characteristics
adjustable priority Example: Setting of CH1
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18,
CR#24). When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1
(CR#18, CR#24).
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched),
b1=1 (not latched).
3. b2: Set to 1 and PLC will be reset to factory settings.
The setting of CH5~CH6, give CH5 setting for example:
b13, b12:
00: can be adjusted, latched.
01: can be adjusted, non-latched.
10: inhibit adjust.
11: reset to factory settings and clear b12, b13 to 0.
#34 H 40EA ○R Software version Display software version in hexadecimal. Example: H 010A = version 1.0A.
#35~#48 System used
○means latched.
╳means non-latched.
R means can read data by using FROM command or RS-485.
W means can write data by using TO command or RS-485.
LSB (Least Significant Bit): 1. Voltage input: 1LSB=10V/2000=5mV. 2. Current input: 1LSB=20mA/1000=20µA.
1. Voltage output: 1LSB=10V/4000=2.5mV. 2. Current output: 1LSB=20mA/4000=5µA.
Explanation:
1. CR#0: The PLC model type.
2. CR#1: b11~b0 is used to set 4 inner channels working mode of analog input module (AD).
b12~b15 is used to set 2 channels working mode of analog output module (DA). Every channel
has four modes to set and can be set individually. For example: if setting CH1 to mode 0
(b2~b0=000), CH2 to mode 1(b5~b3=001), CH3: mode2 (b8~b6=010), CH4: mode
3(b11~b9=011). It needs to set b0~b11 to H688. If setting CH5: mode 2 (b13~b12=10), CH6:
mode 1 (b15~b14=01), it needs to set b12~b15 to H5. The factory setting is H0000.
3. CR#2 ~ CR#5: Used to set the number of input readings used for the average temperature
calculation. The available range is K1~K4096 and factory setting is K10.
4. CR#6 to CR#9: The average temperature (℃). The average temperature is calculated using
multiple temperature readings. Example: If CR#2 is 10, the temperature in CR#6 will be the
average of the last 10 readings on CH1.
5. CR#10 ~ CR#11 are used to set the output value of CH5 and CH6. The setting range is
K0~K4000. The factory setting is K0 and unit is LSB.
6. CR#12 ~ CR#15: they are used to save the present value of input signal of CH1~CH4.
7. CR#16, CR#17, CR#28, CR#29 are reserved.
8. CR #18~ CR #21: the content is the value of adjusting OFFSET value of CH1~CH4 if analog
input voltage or current is 0 after it transfers from analog to digital. Voltage setting range:
-5V~+5V(-1000LSB~+1000LSB). Current setting range: -20mA~+20mA (-1000LSB~+1000LSB).
9. CR #22~ CR #23: the content is the value of adjusting OFFSET value of CH5~CH6 if analog
input voltage or current is 0 after it transfers from analog to digital. The factory setting is K0 and
the unit is LSB. The setting range is -2000~+2000. Voltage setting range:
-5V~+5V(-2000LSB~+2000LSB). Current setting range: -10mA~+10mA (-2000LSB~+2000LSB).
10. CR #24~ CR #27: That is the value of adjust GAIN value of CH1~CH4. That is the value of
analog input voltage or current when conversion value from analog signal to digital is 4000.
Voltage setting range: -4V~+20V(-800LSB~+4000LSB). Current setting range: -16mA~+52mA
(-800LSB ~+2600LSB). But it needs to notice that GAIN VALUE – OFFSET VALUE =
+200LSB~+3000LSB (voltage) or +200LSB~+1600LSB (current). When this value under this
range, the resolution of the input signal will be thin and the variation of value will be larger. When
this value exceeds this range, the resolution of input signal will be thick and the variation of value
will be smaller.
11. CR #28~ CR #29: That is the value of adjust GAIN value of CH5~CH6. That is the value of
analog input voltage or current when conversion value from analog signal to digital is 2000.
Voltage setting range: -4V~+20V(-1600LSB~+8000LSB). Current setting range: -8 mA ~+40 mA
(-1600LSB~+8000LSB). But it needs to notice that GAIN VALUE – OFFSET VALUE = +400LSB
~+6000LSB (voltage/current). When this value under this range, the resolution of the input signal
will be thin and the variation of value will be larger. When this value exceeds this range, the
resolution of input signal will be thick and the variation of value will be smaller.
12. CR#30 is fault code. Please refer to the following chart.
Fault description Content b15~b8 B7 b6 b5 b4 b3 b2 b1 b0
Power source abnormal
(Low voltage alarm)
K1(H1) 0 0 0 0 0 0 0 1
User setting D/A output exceeds range K2(H2) 0 0 0 0 0 0 1 0
Setting mode error K4(H4) 0 0 0 0 0 1 0 0
Offset/Gain error K8(H8) 0 0 0 0 1 0 0 0
Hardware malfunction K16(H10) 0 0 0 1 0 0 0 0
Digital range error K32(H20) 0 0 1 0 0 0 0 0
Average times setting error K64(H40) 0 1 0 0 0 0 0 0
Command error K128(H80)
Reserved
1 0 0 0 0 0 0 0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at
the same time. 0 means normal and 1 means having fault.
13. CR#31: RS-485 communication address. Setting range is 01~255 and factory setting is K1.
14. CR#32: RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600 and 115200.
b0:4800bps, b1:9600bps (factory setting), b2:19200bps, b3:38400 bps, b4:57600 bps,
b5:115200 bps, b6~b13: Reserved, b14: switch between low bit and high bit of CRC code (only
for RTU mode) b15: ASCII / RTU mode. For ASCII mode, date format is 7Bits, even, 1 stop bit
(7 E 1). For RTU mode, date format is 8Bits, even, 1 stop bit (8 E 1).
15. CR#33 is used to set the inner function priority. For example: characteristic register. Output
latched function will save output setting in the inner memory before loss power.
16. CR#34: software version.
17. CR#35~ CR#48: system used.
18. The corresponding parameters address H 40C8~H 40F9 of CR#0~CR#48 can provide user to
read/write data by RS-485.
A. Baud rate can be 4800, 9600, 19200, 38400, 57600, 115200bps.
B. Communication protocol ca be Modbus ASCII / RTU mode. For ASCII mode, date format is
7Bits, even, 1 stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop bit (8 E 1).
C. Function code: 03H read data from register.
06H write a WORD into register.
10H write many WORD into register.
5 ADJUST A/D CONVERSION CHARACTERISTIC CURVE
5.1 Adjust A/D Conversion Characteristic Curve of CH1~CH4
Voltage input mode
Mode 0 of CR#1: GAIN=5V(1000LSB), OFFSET=0V (0LSB).
Mode 1 of CR#1: GAIN=6V(1200LSB), OFFSET=2V (400LSB).
GAIN: Voltage input value when digital output is 4000.
Setting range is -4V~+20V(-800LSB~ +4000LSB)
OFFSET: Voltage input value when digital output is 0.
Setting range: -5V~+5V(-1000LSB ~ +1000LSB)
+2000
+1000
-1000
10V
digital output
Voltage
input
-2000
-6V-10V
6V5V2V
0
Mode 1
Mode 0
GAIN
OFFSET
GAIN-OFFSET: Setting range is +1V~+15V (+200LSB~ +3000LSB)
Current input mode:
Mode 2 of CR#1: GAIN = 20mA(1000LSB), OFFSET=4mA (200LSB).
Mode 3 of CR#1: GAIN = 20mA(1000LSB), OFFSET=0mA (0LSB).
GAIN: Current input value when digital output is +4000.
Setting range is -20 mA~+20 mA (-1000LSB ~
+1000LSB )
OFFSET: Current input value when digital output value is
0. Setting range is-16 mA ~+52 mA (-800LSB ~
+2600LSB)
+2000
Digital output
Current
Input
-2000
-12mA-20mA
4mA
0
Mode 2
Mode 3
OFFSET
20mA
GAIN
GAIN-OFFSET: Setting range is +4mA ~ +32mA (200LSB~
+1600LSB)
The chart above is to adjust A/D conversion characteristic curve of voltage input mode and current
input mode. Users can adjust conversion characteristic curve by changing OFFSET values
(CR#18~CR#21) and GAIN values (CR#24~CR#27) depend on application.
LSB(Least Significant Bit): 1. voltage input: 1LSB=10V/2000=5mV. 2. current input:
1LSB=20mA/1000= 20µA.
5.2 Adjust D/A Conversion Characteristic Curve of CH5~CH6
Voltage output mode
Mode 0 of CR#1: GAIN = 5V(2000LSB), OFFSET=0V (0LSB)
Mode 1 of CR#1: GAIN = 6V(2400LSB), OFFSET=2V (800LSB).
GAIN: Voltage output value when digital input is K2000.
Setting range is -4V~+20V(-1600LSB ~+8000 LSB).
OFFSET: Voltage output value when digital input is K0.
Setting range: -5V~+5V(-2000LSB ~ +2000 LSB).
0+2000 +4000
2V
5V
6V
10V
OFFSET
GAIN
Voltage output
mode 1
mode 0
Digital
input
GAIN-OFFSET: Setting range is +1V~+15V(+400LSB ~ +6000 LSB)
Current output mode:
Mode 2 of CR#1: GAIN = 12mA(2400LSB ),OFFSET=4mA (800LSB).
Mode 3 of CR#1: GAIN = 10mA(2000LSB), OFFSET=0mA (0LSB).
GAIN: Current output value when digital input value is
K2000. Setting range is -8 mA ~+40 mA
(-1600LSB ~+8000LSB).
OFFSET: Current output value when digital input is K0.
Setting range is -10 mA ~+10 mA (-2000LSB
~+2000LSB).
0+2000 +4000
20mA
OFFSET
GAIN
12mA
10mA
4mA
Current output
Mode 2
Mode 3
Digital
input
GAIN-OFFSET: Setting range is +2mA~+30mA(+400LSB
~+6000LSB)
The chart above is to adjust D/A conversion characteristic curve of voltage output mode and current
output mode. Users can adjust conversion characteristic curve by changing OFFSET values
(CR#14~CR#15) and GAIN values (CR#18~CR#19) depend on application.
LSB(Least Significant Bit): 1. voltage output: 1LSB=10V/4000=2.5mV. 2. current output:
1LSB=20mA/4000=5µA.
5.3 Program Example for Adjusting A/D Conversion Characteristics Curve
Example: setting OFFSET value of CH1 to 0V(=K0LSB) and GAIN value of CH1 to 2.5V(=K500LSB).
M1002
K0TO
K0TO
X0
K0TO
K0TO
 Writing H0 to CR#1 (b0~b2) of analog
input/output module #0 and set CH1 to mode
0 (voltage input -10V~+10V)
 Writing H0 to CR#33 (b0~b2) and allow to
adjust characters of CH1.
 When X0 switches from Off to On, K0LSB of
OFFSET value will be wrote in CR#18 and
K500LSB of GAIN value will be wrote in
CR#24.
5.4 Program Example for Adjusting D/A Conversion Characteristics Curve
Example: setting OFFSET value of CH5 to 0V(=K0LSB) and GAIN value of CH1 to 2.5V(=K1000LSB).
M1002
K0TO
K0TO
X0
K0TO
K0TO
 Writing H3000 into CR#1 (b12~b15) of analog
input/output module#0. Setting CH5 to mode
3 (current output 0mA~ +20mA).
 Writing H0 into CR#33 (b12~b15) and allow
CH5, CH6 to adjust characteristics.
 When X0 switches from Off to On, K0LSB of
OFFSET value will be wrote in CR#22 and
K1000LSB of GAIN value K1000LSB will be
wrote in CR#28.
6INITIAL PLC START-UP
 Lamp display:
1. Upon power-up, the ERROR LED will light for 0.5 seconds the POWER LED will light
continuously.
2. No errors= POWER LED on and ERROR LED off.
Low Voltage error (lower than 19.5V), ERROR LED will blink continuously till the power
supply rises above 19.5V.
3. DVP06XA-H connected to PLC MPU in series = RUN LED on MPU will be lit and A/D LED
or D/A LED should blink.
4. After receiving the first RS-485 command the A/D LED or D/A LED will blink.
5. If the input or output exceeds the upper or lower bounds, then the ERROR LED will blink.
6. When main CPU and expansion unit communicate time-out or abnormal interrupt, LED
ERROR of expansion unit will keep lighting.
Example:
M1000
FROM K0
INC D100
ADD D101
RST
TO K0
= K4000 D100
M1013
= K4000 D101
= H0604 D0
RST
D100
D101
TO K0
FROM K0
TO K0
END
M1002
Explanation:
 Reading the model type of expansion module K0 (should be H0604 for DVP06XA-H model type).
 If the model type is DVP06XA-H, set the input mode is (CH1, CH3, CH4)= mode 0, (CH2)= mode 2,
and set the output mode is (CH5)=mode 0, (CH6)=mode 2.
 Setting the average times of CH1 and CH2 are K32.
 Reading the input signal average value of CH1~CH4 (4 data) from CR#6~CR#9 and save in
D20~D23.
 In each second, D100 will increase K1 and D101 will increase K5. When the value of D100 and
D101 are K4000, it will clear to 0.
 Writing the output setting value of D100 and D101 into CR#10 and CR#11. The analog output value
of CH5~CH6 will change with the value of D100 and D101.

Other Delta Control Unit manuals

Delta TECK 81T2 -WHSHWA Series User manual

Delta

Delta TECK 81T2 -WHSHWA Series User manual

Delta RP70878 User manual

Delta

Delta RP70878 User manual

Delta DVP02TK-S User manual

Delta

Delta DVP02TK-S User manual

Delta RP70878 User manual

Delta

Delta RP70878 User manual

Delta EnviroStation EMS2000 User manual

Delta

Delta EnviroStation EMS2000 User manual

Delta DIGI-LAN User manual

Delta

Delta DIGI-LAN User manual

Delta JA-190X User manual

Delta

Delta JA-190X User manual

Delta MultiChoice T24876 User manual

Delta

Delta MultiChoice T24876 User manual

Delta ASRTU-EC16AP User manual

Delta

Delta ASRTU-EC16AP User manual

Delta R3270-MIXLF User manual

Delta

Delta R3270-MIXLF User manual

Delta DOP-A series User manual

Delta

Delta DOP-A series User manual

Delta DVP01PU-S User manual

Delta

Delta DVP01PU-S User manual

Delta 1700 Series Operating and maintenance instructions

Delta

Delta 1700 Series Operating and maintenance instructions

Delta T17TH Series User manual

Delta

Delta T17TH Series User manual

Delta DVP04AD-SL User manual

Delta

Delta DVP04AD-SL User manual

Delta IFD9503 Instructions for use

Delta

Delta IFD9503 Instructions for use

Delta Electronic Exposed Teck II User manual

Delta

Delta Electronic Exposed Teck II User manual

Delta DRU-24V40ABN Quick start guide

Delta

Delta DRU-24V40ABN Quick start guide

Delta MultiChoice Ara T27T867 Series User manual

Delta

Delta MultiChoice Ara T27T867 Series User manual

Delta IFD8540 User manual

Delta

Delta IFD8540 User manual

Delta R3707 User manual

Delta

Delta R3707 User manual

Delta AS Series User manual

Delta

Delta AS Series User manual

Delta DVP04AD-S User manual

Delta

Delta DVP04AD-S User manual

Delta TECK II 81T201BT User manual

Delta

Delta TECK II 81T201BT User manual

Popular Control Unit manuals by other brands

Pentair HI-FLOW 261049 Installation and user guide

Pentair

Pentair HI-FLOW 261049 Installation and user guide

Chargery BMS16Pro Series manual

Chargery

Chargery BMS16Pro Series manual

Comelit 47CPZ003 user manual

Comelit

Comelit 47CPZ003 user manual

roco 10772 manual

roco

roco 10772 manual

Siemens SINAMICS G120 List manual

Siemens

Siemens SINAMICS G120 List manual

Neoway N58 Hardware user's guide

Neoway

Neoway N58 Hardware user's guide

Okuma OSP-U100M Operation manual

Okuma

Okuma OSP-U100M Operation manual

NXP Semiconductors Freescale TWR-WIFI-GS1500M Lab Guide

NXP Semiconductors

NXP Semiconductors Freescale TWR-WIFI-GS1500M Lab Guide

Dea 202 E Operating instructions and warnings

Dea

Dea 202 E Operating instructions and warnings

Baldor 23H Series Installation & operating manual

Baldor

Baldor 23H Series Installation & operating manual

Siemens MVS661 N Series Mounting instructions

Siemens

Siemens MVS661 N Series Mounting instructions

Siemens SIMATIC NET operating instructions

Siemens

Siemens SIMATIC NET operating instructions

ABB FAIO-01 user manual

ABB

ABB FAIO-01 user manual

Cinterion EGS3 Hardware interface description

Cinterion

Cinterion EGS3 Hardware interface description

WEG DBW03 Series user manual

WEG

WEG DBW03 Series user manual

DFI KU968 user manual

DFI

DFI KU968 user manual

BFT ALTAIR manual

BFT

BFT ALTAIR manual

LEGRAND 0 676 96 manual

LEGRAND

LEGRAND 0 676 96 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.