Delta DOP-B08 User manual

DOP
-B08
High ColorɄ
Ʉ
Wide Screen
Ʉ
User-Friendly HMI Products
B08S515 / B08E515 Instrunction Sheet
(1) Preface
Thank you for purchasing DELTA’s DOP-B series. This instruction sheet will be helpful in the installation, wiring and inspection of
Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should thoroughly understand all
safety precautions before proceeding with the installation, wiring and operation. Place this instruction sheet in a safe location for
future reference. Please observe the following precautions:
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids.
Ensure that all wiring instructions and recommendations are followed.
Ensure that HMI is correctly connected to a ground. The grounding method must comply with the electrical standard of
the country (Please refer to NFPA70: National Electrical Code, 2005 Ed.).
Do not disassemble HMI, modify or remove wiring when power is applied to HMI.
Do not touch the power supply during operation. Otherwise, it may cause electric shock.
If you have any questions during operation, please contact our local distributors or Delta sales representatives.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most
updated version at http://www.delta.com.tw/ia
(2) Safety Precautions
Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating,
maintaining and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety
precautions when using the Delta’s HMI product. Failure to observe these precautions may void the warranty!
Installation
¾Comply with quick start for installation. Otherwise it may cause equipment damage.
¾Do not install the product in a location that is outside the stated specification for the HMI.
Failure to observe this caution may result in electric shock, fire, or explosion.
¾Do not install the product in a location where temperatures will exceed specification for
the HMI. Failure to observe this caution may result in abnormal operation or damage the
product.
¾Please note that this equipment has obtained EMC registration for commercial use. In the
event that it has been mistakenly sold or purchased, please exchange it for equipment
certified for home use.
¾Do not use this product as an alarm device for disaster early warning that may result in
personal injury, equipment damage, or system emergency stop.
Wiring
¾Connect the ground terminals to a class-3 ground (Ground resistance should not exceed
100ȍ). Improper grounding may result in communication error, electric shock or fire.
Operation
¾The users should use Delta Screen Editor software to perform editing in Delta's HMI
product. To perform editing and confirming HMI programs without using Delta Screen
Editor software in Delta's HMI product may result in abnormal operation.
¾To prevent the personal injury and equipment damage, when designing HMI programs,
please ensure that a communication error occurred between Delta’s HMI product and the
connecting controller or equipment will not result in system failure or malfunction.
¾Please be sure to backup the screen data and HMI programs in case they are lost,
accidentally deleted or worse.
¾Do not modify wiring during operation. Otherwise it may result in electric shock or
personal injury.
¾Never use a hardor pointed object to hit orstrike the screen as doingthis may damage the
screen and let the screen has not respond at all, and then cause HMI to work abnormally.
Maintenance and Inspection
¾Do not touch any internal or exposed parts of the HMI as electrical shock may result.
¾Do not remove operation panel while power is on. Otherwise electrical shock may result.
¾Wait at least 10 minutes after power has been removed before touching any HMI terminals
or performing any wiring and/or inspection as an electrical charge may still remain in the
HMI with hazardous voltages even after power has been removed.
¾Turn the power off before changing backup battery and check system settings after
finishing change. (all data will be cleared after changing battery).
¾Be sure the ventilation holes are not obstructed during operation. Otherwise malfunction
may result due to bad ventilation or overheating troubles.
Wiring Method
¾Do not use a voltage that will exceed specification for the HMI. Failure to observe this
caution may result in electric shock or fire.
¾Remove the terminal block from the HMI before wiring.
¾Insert only one wire into one terminal on the terminal block.
¾If the wiring is in error, perform the wiring again with proper tools. Never use force to
remove the terminals or wires. Otherwise, it may result in malfunction or damage.
¾For the power line that forced to take out, ensure to check wiring again and restart.
Communication Wiring
¾Comply with communication wiring specification for wiring.
¾Wiring length should comply with the stated specification for the HMI.
¾Proper grounding to avoid bad communication quality.
¾To avoid noise and interference, the communication cable, all power cables, and motor
power cable should be placed in separate conduits.
(3) Pin Definition of Serial Communication
DOP-B08S515 / DOP-B08E515 COM1 Port (Supports Flow Control)
COM Port PIN Contact
RS-232
1
2RXD
3TXD
4
5GND
6
7 RTS
8CTS
9
Note: Blank = No Connection.
DOP-B08S515 / DOP-B08E515 COM2 Port (Supports Flow Control)
COM Port PIN MODE1 MODE2 MODE3
RS-232 RS-422 RS-485
1TXD+D+
2RXD
3TXD
4RXD+
5 GND GND GND
6TXD- D-
7 RTS
8CTS
9RXD-
Note1: Blank = No Connection.
Note2: When COM2 port is used for RS-232 flow control, i.e. RTS and CTS signals are used for flow control, COM3 port will
become incapable of being used.
Note3: When COM2 port is used for RS-422 flow control, please refer to the following COM3 Port signals table for pin
assignments. The signals, RTS+, CTS+, RTS- and CTS- shown in brackets are the signals used for flow control.
DOP-B08S515 / DOP-B08E515 COM3 Port
COM Port PIN MODE1 MODE2 MODE3
RS-232 RS-422 RS-485
1 TXD+(RTS+) D+
2RXD
3TXD
4RXD+(CTS+)
5 GND GND GND
6TXD-(RTS-) D-
7
8
9RXD-(CTS-)
Note1: Blank = No Connection.
Note2: When COM2 port is used for RS-422 flow control, please refer to the COM3 Port signals table above for pin assignments.
The signals, RTS+, CTS+, RTS- and CTS- shown in brackets are the signals used for flow control.
DOP-B08E515 Ethernet Interface (LAN)
Ethernet Interface (LAN) PIN Contact
Ethernet
1TX+
2TX-
3RX+
4
5
6RX-
7
8
Note: Blank = No Connection.
(4) Parts Names
DOP-B08S515
炾
DOP-B08E515 (Front View)
A: Power LED Indicator
Lights in green when HMI works normally.
C
: Operation LED Indicator (Blue) (Note1)
The operation LED indicator blinks in blue when either the communication is carried
out or the data is accessing (please refer to the “Note1” below for explanation).
: Alarm LED Indicator (Red)
The alarm LED indicator blinks in red when one of the alarms is on.
DTouch Screen / Display
NOTE
1. The definition of the operation LED indicator (Blue) can be determined by the users freely.
DOP-B08S515
炾
DOP-B08E515 (Rear View)
APower Input Terminal FEthernet Interface (LAN)
B
COM3
(It is provided with two LED indicators to
indicate that HMI is in Read or Write status
during the communication process.)
GUSB Host
C
COM2
(It is provided with two LED indicators to
indicate that HMI is in Read or Write status
during the communication process.)
HAudio Output Interface
DCOM1 IMemory Card Slot / Battery
EUSB Slave - -
A
C
B
PIN1
PIN1
PIN1
G
I
E
F
H
ABCD

(5) Dimensions
DOP-B08S515 炾
炾
DOP-B08E515
T=1.6mm(0.06") ~
5.0mm(0.19")(2.06")
174.1(6.85")
227.1(8.94")
0
+0.04"
(8.63" )
0
219.4
+1
+0.04"
6.55"
0
+1
166.5
0
NOTE:
4-R1.0(0.04")
52.3
T
(6) Specifications
Model DOP-B08S515 DOP-B08E515
LCD MODULE
Display
Type 8” TFT LCD
(65536 colors)
Resolution 800 x 600 pixels
Backlight LED Back Light (less than 10,000 hours half-life at 25oC)(Note 1)
Display
Size 162 x 121.5mm
Operation
System Delta Real Time OS
MCU 32-bit RISC Micro-controller
NOR Flash ROM Flash ROM 128 MB(OS System: 30MB / Backup: 16MB / User Application: 82MB)
SDRAM 64Mbytes
Backup Memory 16Mbytes
Sound
Effect
Output
Buzzer Multi-Tone FrequencyƋ2K ~ 4K Hzƌƒ85dB
AUX N/A Stereo output
Ethernet
Interface N/A
IEEE 802.3, IEEE 802.3u
10/100 Mbps
auto-sensing(has built-in isolated
power circuit (Note 3)ƌ
USB 1 USB Host (Note 2) Ver 1.1 / 1 USB Slave Ver 2.0
Memory Card SD Card (supports SDHC)
Serial
COM
Port
COM1 RS-232 (supports hardware flow control)
COM2 RS-232ƒRS-422ƒRS-485 RS-232 / RS-422 / RS-485
(has built-in isolated power circuit (Note
3))
COM3 RS-232ƒRS-422ƒRS-485 RS-232 / RS-422 / RS-485
(has built-in isolated power circuit (Note
3))
Function Key N/A
Perpetual
Calendar (RTC) Built-in
Cooling Method Natural air circulation
Safety Approval CEƒUL (Note 4) ƒKCC (Note 4)
Waterproof
Degree IP65ƒNEMA4
Operation
Voltage(Note 5) DC +24V (-10% ~ +15%)
(please use isolated power supply)
DC +24V (-10% ~ +15%)
(has built-in isolated power circuit (Note
3))
Voltage
Endurance AC500V for 1 minute (between charging (DC24V terminal) and FG terminals)
Power
Consumption
(Note 5) 5.2W 7.8W
Backup Battery 3V lithium battery CR2032 x 1
Backup Battery
Life It depends on the temperature used and the conditions of usage, about 3
years or more at 25oC.
Operation
Temp. 0oC~50
oC
Storage Temp. -20oC~+60
oC
Ambient
Humidity 10% ~ 90% RH [0 ~ 40oC], 10% ~ 55% RH [41 ~ 50oC]
Pollution Degree 2
Vibration IEC 61131-2 compliant 5Hzʀf烋8.3Hz = Continuous: 3.5mm, 8.3Hzʀfʀ
150Hz = Continuous: 1.0g
Shock IEC 60068-2-27 compliant 15g peak for 11 ms duration, X, Y, Z directions
for 6 times
Dimensions
(W) x (H) x (D)
mm 227.1 x 174.1 x 61
Panel Cutout
(W) x (H) mm 219.4 X 166.5
Weight Approx.1226g
NOTE
1) The half-life of backlight is defined as original luminance being reduced by 50% when the maximum driving current is
supplied to HMI. The life of LED backlight shown here is an estimated value under 25oC normal temperature and humidity
conditions.
2) USB Host port can provide up to 5V/ 500mA of power.
3) The withstand voltage of the isolated power circuit is 1500V peak for 1 minute.
4) Some models are in the process of application to UL and KCC certification. For more information, please consult our
distributors.
5) The value of the power consumption indicates the electrical power consumed by HMI only without connecting to any
peripheraldevices. In order to ensure the normal operation, it is recommended to use a power supply which the capacity is
1.5 ~2 times the value of the power consumption.
6) The content of this quick start may be revised without prior notice. Please consult our distributors or download the most
updated version at http://www.delta.com.tw/ia/.
Units烉mm (inches)
This manual suits for next models
2
Other Delta Touch Panel manuals

Delta
Delta DIAVH-IPC003100 User manual

Delta
Delta DOP-H07 Series User manual

Delta
Delta DOP-107EG User manual

Delta
Delta TP70P-211LC1T User manual

Delta
Delta DOP-W127B User manual

Delta
Delta TP04G-AL User manual

Delta
Delta DOP-107H User manual

Delta
Delta Vivitek NovoTouch EK653i User manual

Delta
Delta DOP-110IS User manual

Delta
Delta DOP-A User manual
Popular Touch Panel manuals by other brands

Siemens
Siemens Simatic PC Panel PC 870 Equipment manual

Advantech
Advantech IPPC-9120G user manual

HWH
HWH 325 SERIES Operator's manual

AMX
AMX Modero ViewPoint MVP-7500 quick start guide

ICOP Technology
ICOP Technology PPC-090T-APL-N4-4G user manual

Avalue Technology
Avalue Technology RITY120 Quick reference guide