DOLD SAFEMASTER BD 5987 Operating instructions

1BD 5987 / 22.01.19 de / 088A
SAFEMASTER
Not-Aus-Modul
BD 5987
0262943
Datenblatt / Betriebsanleitung DEUTSCH
E. DOLD & SÖHNE KG
Postfach 1251 • 78114 Furtwangen • Deutschland
Telefon +49 7723 6540 • Fax +49 7723 654356
Original
DE
EN
FR
IT

2BD 5987 / 22.01.19 de / 088A
Inhaltsverzeichnis
Symbol- und Hinweiserklärung..........................................................................................................................................3
Allgemeine Hinweise ........................................................................................................................................................3
Bestimmungsgemäße Verwendung...................................................................................................................................3
Sicherheitshinweise...........................................................................................................................................................3
Produktbeschreibung.........................................................................................................................................................5
Funktionsdiagramm...........................................................................................................................................................5
Blockschaltbild...................................................................................................................................................................5
Zulassungen und Kennzeichen .........................................................................................................................................5
Anwendungen....................................................................................................................................................................5
Geräteanzeigen.................................................................................................................................................................5
Schaltbilder........................................................................................................................................................................6
Anschlussklemmen............................................................................................................................................................6
Hinweise............................................................................................................................................................................6
Technische Daten..............................................................................................................................................................6
Technische Daten..............................................................................................................................................................7
Standardtype .....................................................................................................................................................................7
Vorgehen bei Störungen....................................................................................................................................................7
Wartung und Instandsetzung.............................................................................................................................................7
Varianten ...........................................................................................................................................................................7
Kennlinien..........................................................................................................................................................................8
Anwendungsbeispiele........................................................................................................................................................8
Anwendungsbeispiele........................................................................................................................................................9
Beschriftung und Anschlüsse ..........................................................................................................................................41
Maßbild (Maße in mm) ....................................................................................................................................................41
Sicherheitstechnische Kenndaten ...................................................................................................................................42
EG-Konformitätserklärung...............................................................................................................................................43
EG-Konformitätserklärung...............................................................................................................................................44

3BD 5987 / 22.01.19 de / 088A
Sicherheitshinweise
WARNUNG
Gefahr durch elektrischen Schlag!
Lebensgefahr oder schwere Verletzungsgefahr.
• Stellen Sie sicher, dass Anlage und Gerät während der elektrischen
Installation in spannungsfreiem Zustand sind und bleiben.
• Das Gerät darf nur für die in der mitgeltenden Betriebsanleitung / Daten-
blatt vorgesehenen Einsatzfälle verwendet werden. Die Hinweise in den
zugehörigenDokumentationenmüssenbeachtetwerden.Diezulässigen
Umgebungsbedingungen müssen eingehalten werden.
• Der Berührungsschutz der angeschlossenen Elemente und die Isolation
der Zuleitungen sind für die höchste am Gerät anliegende Spannung
auszulegen.
• Beachten Sie die VDE- sowie die örtlichen Vorschriften, insbesondere
hinsichtlich Schutzmaßnahmen.
WARNUNG
Brandgefahr oder andere thermische Gefahren!
Lebensgefahr, schwere Verletzungsgefahr oder Sachschäden.
• Das Gerät darf nur für die in der mitgeltenden Betriebsanleitung / Daten-
blatt vorgesehenen Einsatzfälle verwendet werden. Die Hinweise in den
zugehörigenDokumentationenmüssenbeachtetwerden.Diezulässigen
Umgebungsbedingungen müssen eingehalten werden. Insbesondere
muss die Stromgrenzkurve beachtet werden.
• Das Gerät darf nur von sachkundigen Personen installiert und in Betrieb
genommen werden, die mit dieser technischen Dokumentation und
den geltenden Vorschriften über Arbeitssicherheit und Unfallverhütung
vertraut sind.
WARNUNG
Funktionsfehler!
Lebensgefahr, schwere Verletzungsgefahr oder Sachschäden.
• Das Gerät darf nur für die in der mitgeltenden Betriebsanleitung / Daten-
blatt vorgesehenen Einsatzfälle verwendet werden. Die Hinweise in den
zugehörigenDokumentationenmüssenbeachtetwerden.Diezulässigen
Umgebungsbedingungen müssen eingehalten werden.
• Das Gerät darf nur von sachkundigen Personen installiert und in Betrieb
genommen werden, die mit dieser technischen Dokumentation und
den geltenden Vorschriften über Arbeitssicherheit und Unfallverhütung
vertraut sind.
• MontierenSie das GerätineinenSchaltschrankmit SchutzartIP 54oder
besser (nicht zwingend erforderlich für die Variante BD 5987.02/301 bei
Einsatz in einer Aufzugsanlage nach Aufzugsrichtlinie 2014/33/EU.
Der Einsatz istbeschränkt auf einen stationären Schaltschrank -Einsatz
nicht auf dem Fahrkorb. Umwelteinflüsse am Einbauort dürfen dabei
keine negativen Auswirkungen auf die Funktion der Schaltung haben.
Siehe auch Fußnote 1 im Abschnitt "Technische Daten" und Anwen-
dungsbeispiele M10429_a, M6899_c und M11384); Staub und Feuch-
tigkeit können sonst zur Beeinträchtigungen der Funktionen führen.
WARNUNG
Installationsfehler!
Lebensgefahr, schwere Verletzungsgefahr oder Sachschäden.
• Sorgen Sie an allen Ausgangskontakten bei kapazitiven und induktiven
Lasten für eine ausreichende Schutzbeschaltung.
!
Achtung!
• Die Sicherheitsfunktion muss bei Inbetriebnahme des Gerätes ausgelöst
werden.
• Entsteht ein Leitungsschluss über dem Ein-Taster nachdem die Span-
nung an S12, S22 bereits anliegt, erfolgt eine ungewollte Aktivierung,
weil sich dieser Leitungsschluss von der regulären Einschaltfunktion
nicht unterscheidet.
• AUTOMATISCHER START !
Gemäß IEC/EN 60 204-1 Punkt 9.2.5.4.2 darf nach dem Stillsetzen im
Notfall kein automatischer Start erfolgen. Deshalb muss in den Betriebs-
arten mit automatischem Start, eine übergeordnete Steuerung einen
automatischen Start nach einem Not-Aus verhindern.
• Durch Öffnen des Gehäuses oder eigenmächtige Umbauten erlischt
jegliche Gewährleistung.
GEFAHR:
Bedeutet, dass Tod oder schwere Körperverletzung eintreten
wird, wenn die entsprechenden Vorsichtsmaßnahmen nicht ge-
troffen werden.
WARNUNG:
Bedeutet, dass Tod oder schwere Körperverletzung eintreten
kann, wenn die entsprechenden Vorsichtsmaßnahmen nicht
getroffen werden.
VORSICHT:
Bedeutet, dass eine leichte Körperverletzung eintreten kann,
wenn die entsprechenden Vorsichtsmaßnahmen nicht getroffen
werden.
!
ACHTUNG:
Warnt vor Handlungen, die einen Schaden oder eine Fehlfunktion
des Gerätes, der Geräteumgebung oder der Hard-/Software zur
Folge haben können.
nfo
Hinweis:
Bezeichnet Informationen, die Ihnen bei der optimalen Nutzung
des Produktes behilflich sein sollen.
Die hier beschriebenen Produkte wurden entwickelt, um als Teil einer
Gesamtanlage oder Maschine sicherheitsgerichtete Funktionen zu über-
nehmen. Ein komplettes sicherheitsgerichtetes System enthält in der
Regel Sensoren, Auswerteeinheiten, Meldegeräte und Konzepte für si-
chere Abschaltungen. Es liegt im Verantwortungsbereich des Herstellers
einer Anlage oder Maschine die korrekte Gesamtfunktion sicherzustellen.
DOLD ist nicht in der Lage, alle Eigenschaften einer Gesamtanlage oder
Maschine, die nicht durch DOLD konzipiert wurde, zu garantieren. Das
Gesamtkonzept der Steuerung, in die das Gerät eingebunden ist, ist vom
Benutzer zu validieren. DOLD übernimmt auch keine Haftung für Empfeh-
lungen, die durch die nachfolgende Beschreibung gegeben bzw. impliziert
werden. Aufgrund der nachfolgenden Beschreibung können keine neuen,
über die allgemeinen DOLD-Lieferbedingungen hinausgehenden Garan-
tie-, Gewährleistungs- oder Haftungsansprüche abgeleitet werden.
Allgemeine Hinweise
Symbol- und Hinweiserklärung
Bestimmungsgemäße Verwendung
DasBD5987dientdemsicherheitsgerichtetenUnterbrecheneinesSicher-
heitsstromkreises. Es kann zum Schutz von Personen und Maschinen in
Anwendungen mit Not-Halt-Tastern und Schutztüren verwendet werden.
Das BD 5987.02/301 kann als elektronische Sicherheitsschaltung zum
Ersatz eines Sicherheitsschalters gem. EN 81-20, Abschnitt 5.11.2.2 ver-
wendet werden. Applikationen entsprechend der Anwendungsbeispiele
M10429_a, M6899_c und M11384.
Bei bestimmungsgemäßer Verwendung und Beachtung dieser Anleitung
sindkeine Restrisikenbekannt. Bei Nichtbeachtungkann es zuPersonen-
und Sachschäden kommen.
Installation nur durch Elektrofachkraft!
Nicht im Hausmüll entsorgen!
Das Gerät ist in Übereinstimmung mit den national gültigen
Vorgaben und Bestimmungen zu entsorgen.
Aufbewahren für späteres Nachschlagen
Um Ihnen das Verständnis und das Wiederfinden bestimmter Textstellen
und Hinweise in der Betriebsanleitung zu erleichtern, haben wir wichtige
Hinweise und Informationen mit Symbolen gekennzeichnet.
Vor der Installation, dem Betrieb oder der Wartung des Gerätes
muss diese Anleitung gelesen und verstanden werden.

4BD 5987 / 22.01.19 de / 088A

5BD 5987 / 22.01.19 de / 088A
Ihre Vorteile
• Sichere Unterbrechung von Schaltkreisen
• Leitungsschlusserkennung am Ein-Taster
• Vergoldete Kontakte auch zum Schalten von Kleinlasten (Signal für SPS)
• Wahlweise Querschlusserkennung im Not-Aus-Steuerkreis
Merkmale BD 5987._ _:
• entspricht
-Performance Level (PL) e und Kategorie 4 nach EN ISO 13849-1
-SIL-Anspruchsgrenze (SIL CL) 3 nach IEC/EN 62061
-Safety Integrity Level (SIL) 3 nach IEC/EN 61508
• Ausgang: 2 Schließer für AC 250 V
• 1- oder 2-kanalige Beschaltung
• LED-Anzeigen für Kanal 1 / 2 und Netz
• Überspannungs- und Kurzschlussschutz
• Leiteranschluss: auch 2 x 1,5 mm2Litze mit Hülse und Kunststoffkragen
DIN 46 228-1/-2/-3/-4 oder 2 x 2,5 mm2Litze mit Hülse DIN 46 228-1/-2/-3/-4
• 45 mm Baubreite
BD 5987._ _/001: wie BD 5987._ _ jedoch
• Wahlweise automatische Ein-Funktion oder Aktivierung über die Ein-Taste
• Wahlweise Querschlusserkennung im Not-Aus-Steuerkreis
BD 5987.02/301: wie BD 5987.02/001 jedoch
• Auch für Aufzüge nach EN 81-20/-50 geeignet
• Entspricht den Anforderungen der Richtlinie 2014/33/EU über Aufzüge
• Entspricht
-Performance Level (PL) d und Kategorie 3 nach EN ISO 13849-1
-SIL-Anspruchsgrenze (SIL CL) 2 nach IEC/EN 62061
-Safety Integrity Level (SIL) 2 nach IEC/EN 61508
• Kürzere Rückfallzeit bei Unterbrechung im Netzkreis
• 1-kanalige Not-Aus-Schaltung
0210117
Sicherheitstechnik
SAFEMASTER
Not-Aus-Modul
BD 5987
Produktbeschreibung
DasBD5987dientdemsicherheitsgerichtetenUnterbrecheneinesSicher-
heitsstromkreises. Es kann zum Schutz von Personen und Maschinen in
Anwendungen mit Not-Halt-Tastern und Schutztüren verwendet werden.
Das BD 5987.02/301 kann als elektronische Sicherheitsschaltung zum
Ersatz eines Sicherheitsschalters gem. EN 81-20, Abschnitt 5.11.2.2.
verwendetwerden.ApplikationenentsprechendderAnwendungsbeispiele
M10429_a, M6899_c und M11384.
Funktionsdiagramm
Blockschaltbild
Zulassungen und Kennzeichen
Anwendungen
Schutz von Personen und Maschinen
- Not-Aus-Schaltungen von Maschinen
- Überwachung von Schiebeschutzgittern
Geräteanzeigen
LED Netz: leuchtet, bei anliegender Betriebsspannung
LED K2: leuchtet, bei bestromtem Relais K2
LED K3: leuchtet, bei bestromtem Relais K3
Ein-Taster
K2
M6895_a
K3 *
Kurzschlußerkennung
am Ein-Taster
*
Not-Aus
(Aus)
A1(+)A2(-) S33 PE(-)
S33S33 Y2 S12 S12
S21/
PE S22X6X5 332313
M6896_c
S34 Y1 34S23 2414
K2K1
K3
K2
K1
Netz
24V K3
Überspannung- und
Kurzschlußschutz
Überwachungs-
Logik
K2 K3
&
* siehe Varianten
Canada / USA
*

6BD 5987 / 22.01.19 de / 088A
Eingang
Nennspannung UN:AC 24, 42, 48, 110, 127, 230, 240 V 1)
DC 24 V
Spannungsbereich: AC 0,8 ... 1,1 UN
bei 10% Restwelligkeit: DC 0,9 ... 1,2 UN
bei 48% Restwelligkeit: DC 0,8 ... 1,1 UN
Nennverbrauch: ca. 5,5 VA
Nennfrequenz: 50 / 60 Hz
Steuerspannung an S33: DC 24 V
Steuerstrom
BD 5987.02: typ. DC 55 mA
BD 5987.02/001 + /301: typ. DC 45 mA
Mindestspannung
an Klemmen S12, S22: DC 21 V bei aktiviertem Gerät
Wiederbereitschaftszeit: 0,5 s nach Entriegelung
der Not-Aus-Taste
Ausgang
Kontaktbestückung
BD 5987.02: 2 Schließer
BD 5987.03: 2 Schließer, 1 Schließer als Meldekontakt
Der Schließer 33-34 ist nur als Meldekontakt verwendbar
Ansprechzeit: max. 100 ms
BD 5987.02/001 + /301: bei automatischem Start ca. 1 s
Rückfallzeit
bei 2-kanaliger Unterbrechung
im Sekundärkreis
(S12, S22 und S23): 50 ms ±25 %
bei Unterbrechung im Netzkreis
BD 5987.02: 350 ms ±50 %
BD 5987.02/001: 120 ms ±50 %
BD 5987.02/301: 40 ms ±50 %
Fehlererkennungszeit bei UN:
bei 1-kanaliger Unterbrechung
in S12:
BD 5987: typ. 430 ms
BD 5987/001+/201: typ. 85 ms
in S22 und S23: 50 ms ±25 %
Kontaktart: Relais, zwangsgeführt
Ausgangsnennspannung: AC 250 V 1)
DC: siehe Lichtbogengrenzkurve
Thermischer Strom Ith:siehe Dauerstromgrenzkurve
(max. 10 A in einem Kontaktstrang)
Schaltvermögen
Kontakte 13/14, 23/24:
nach AC 15: 3 A / AC 230V 1) IEC/EN 60 947-5-1
in Anlehnung an AC 15: 6 A / AC 230V 1) bei 0,25 Hz
nach DC 13: 2 A / DC 24 V IEC/EN 60 947-5-1
in Anlehnung an DC 13: 6 A / DC 24 V bei 0,1 Hz
Kontakt 33/34:
nach AC 15: 3 A / AC 230V IEC/EN 60 947-5-1
nach DC 13: 2 A / DC 24 V IEC/EN 60 947-5-1
Elektrische Lebensdauer
Kontakte 13/14, 23/24
bei AC 230 V, 6 A, cos ϕ= 1: > 5 x 105Schaltspiele
Kontakt 33/34
bei AC 230 V, 1 A, cos ϕ= 1: > 5 x 105Schaltspiele
Zulässige Schalthäufigkeit: 600 Schaltspiele / h
1) max. AC 160 V bzw. max. DC 160 V für die Variante BD 5987.02/301
bei Einsatz in einer Aufzugsanlage nach Aufzugsrichtlinie 2014/33/EU,
wenn das BD 5987.02/301 nicht in einem Schaltschrank mit Schutzart
IP 54 oder besser montiert wird.
Kurzschlussfestigkeit
max. Schmelzsicherung: 6 A gG / gL IEC/EN 60947-5-1
Mechanische Lebensdauer: 10 x 106Schaltspiele
Allgemeine Daten
Nennbetriebsart: Dauerbetrieb
Temperaturbereich:
Betrieb: - 15 ... + 55°C
Lagerung : - 25 ... + 85 °C
Betriebshöhe: < 2.000 m
bei max. 90% Luftfeuchte
Luft- und Kriechstrecken
Bemessungsstoßspannung /
Verschmutzungsgrad: 4 kV / 2 (Basisisolierung) IEC 60 664-1
EMV: IEC/EN 62 061
Funkentstörung: Grenzwert Klasse B EN 55 011
Schutzart
Gehäuse: IP 40 IEC/EN 60 529
Klemmen: IP 20 IEC/EN 60 529
Schaltbilder
Anschlussklemmen
Klemmenbezeichnung Signalbeschreibung
A1 (+) + / L
A2 (-) - / N
S12, S22, S23, S34, X6, Y2
T12, T22, T34 Steuereingänge
PE (-), S21/PE, S33, X5, Y1
T11, T12, T33 Steuerausgänge
13, 14, 23, 24 Schließer zwangsgeführt für
Freigabekreis
33, 34 Meldeausgang
Hinweise
Leitungsschlusserkennung am Ein-Taster:
Ist der Ein-Taster bereits vor Anlegen der Spannung an S12, S22 ge-
schlossen oder liegt ein Leitungsschluss über dem Ein-Taster vor, lassen
sich die Ausgangskontakte nicht einschalten.
Ein Leitungsschluss über dem Ein-Taster, der nach der Aktivierung
des Gerätes aufgetreten ist, wird beim erneuten Einschaltvorgang er-
kannt und das Einschalten der Ausgangskontakte wird verhindert.
Entsteht ein Leitungsschluss über dem Ein-Taster nachdem die Span-
nung an S12, S22 bereits anliegt, erfolgt eine ungewollte Aktivierung, weil
sich dieser Leitungsschluss von der regulären Einschaltfunktion nicht un-
terscheidet.
Durch die vergoldeten Kontakte eignet sich das BD 5987 auch zum Schal-
ten von Kleinlasten 1 mVA ... 7 VA, 1 mW ... 7 W im Bereich von 0,1 ... 60 V,
1 ... 300 mA. Die Kontakte lassen auch den max. Schaltstrom zu. Da die
Goldauflage bei dieser Stromstärke jedoch abgebrannt wird, ist das Gerät
danach nicht mehr zum Schalten von Kleinlasten geeignet.
Die Anschlussklemme PE dient dazu, das Gerät auch in IT-Netzen mit Iso-
lationsüberwachung zu betreiben, sowie als Bezugspunkt zur Prüfung der
Steuerspannung. Bei DC-Geräten wird durch Anschluss des Schutzleiters
an die Anschlussklemme PE der interne Kurzschlussschutz überbrückt.
Zur Kontaktvervielfältigung des Not-Aus-Moduls BD 5987 können ein
oder mehrere Erweiterungsmodule BN 3081 oder externe Schütze mit
zwangsgeführten Kontakten verwendet werden.
Bei automatischem Start gilt: S22 muss vor S12 geschlossen sein, da S12
den automatischen Start einleitet.
Bei Start-Funktion spielt die Reihenfolge keine Rolle.
Technische Daten
K3
K2
Y2 PE
A1 Y1
S33
S12
S22
S34
A2
23
2414
13
S12 S12 S34
S33
S33 S33
A1
(+)
PE
(-)
S22
14 24
Y1
13 23 Y2
A2
(-)
M7375_b
K3
K2
K1
X6 PE
A1 X5
S33
S12
S22
S34
A2
23
24 34
33
14
13
33 S34
S21
/PE
34 X6
X5
A1
(+) S22S12
14 24
S23
13 23 S33
A2
(-)
M7378_b
K3
K2
X6 PE
A1 X5
S33
S12
S22
S34
A2
23
2414
13
S12 S34
S21
/PE
S33 X6
X5
A1
(+) S22S12
14 24
S23
13 23 S33
A2
(-)
M7376_b
K3
K2
K1
X6 PE
A1 T11
T33
T12
T22
T34
A2
23
24 34
33
14
13
33 T34
PE
34 X6
T33
A1
(+) T22T12
14 24
S23
13 23 T11
A2
(-)
M7379_c
BD 5987.02 BD 5987.03/001
BD 5987.02/001 + /301 BD 5987.03/201

7BD 5987 / 22.01.19 de / 088A
Gehäuse: Thermoplast mit V0-Verhalten
nach UL Subj. 94
Rüttelfestigkeit: Amplitude 0,35 mm
Frequenz 10 ... 55 Hz, IEC/EN 60 068-2-6
Klimafestigkeit: 15 / 055 / 04 IEC/EN 60 068-1
Klemmenbezeichnung: EN 50 005
Leiteranschluss: 1 x 4 mm2massiv oder
1 x 2,5 mm2Litze mit Hülse
und Kunststoffkragen oder
2 x 1,5 mm2Litze mit Hülse und
Kunststoffkragen
DIN 46 228-1/-2/-3/-4 oder
2 x 2,5 mm2Litze mit Hülse
DIN 46 228-1/-2/-3
Leiterbefestigung: Plus-Minus-Klemmenschrauben
M 3,5 Kastenklemme mit
Drahtschutz
Anzugsdrehmoment: 0,8 Nm
Schnellbefestigung: Hutschiene IEC/EN 60 715
Nettogewicht: 450 g
Geräteabmessungen
Breite x Höhe x Tiefe: 45 x 74 x 121 mm
Technische Daten
Standardtype
BD 5987.02/001 DC 24 V
Artikelnummer: 0040954
• Ausgang: 2 Schließer
• Nennspannung UN: DC 24 V
• Baubreite: 45 mm
BD 5987.02/61: mit UL-Zulassung (Canada/USA)
BD 5987.02/001: wahlweise mit Querschlusserkennung im Not-Aus-
Steuerkreis (Anwendungsbeispiel M6904)
wahlweise automatische Ein-Funktion beim Anlegen
der Betriebsspannung oder Aktivierung über die
Ein-Taste.
Brückenbelegung bei den Funktionen:
Aktivierung über Ein-Taster / oder automatische Ein-Funktion:
M8687
Ein-Taster
S12-S34 oder
S33-S34
Brücke
X5 - X6 Funktion
Erst nach Betätigung des Ein-Tasters
werden die Ausgangskontakte
geschaltet. Leitungsschluss-
überwachung am Ein-Taster
Automatische Ein-Funktion bei Be-
triebsspannung AUS / EIN oder beim
Entriegeln von Not-Aus
BD 5987.03/001: mit 2 Schließern,
1 Meldekontakt AC/DC 0,1 ... 1 A / 10 ...120 V
BD 5987.03/201: wie BD 5987.03/001, jedoch mit
Anschlussbezeichnungen gemäß Schaltbild
Brückenbelegung bei den Funktionen:
Aktivierung über Ein-Taster / oder automatische Ein-Funktion
M8687
Ein-Taster
T11-T34 oder
T12-T34
Brücke
T33 - X6 Funktion
Erst nach Betätigung des Ein-Tasters
werden die Ausgangskontakte
geschaltet. Leitungsschluss-
überwachung am Ein-Taster
Automatische Ein-Funktion bei Be-
triebsspannung AUS / EIN oder beim
Entriegeln von Not-Aus
BD 5987.02/301: Startverhalten wie BD 5987.02/001,
kürzere Rückfallzeit bei Unterbrechung im Netzkreis,
auch für Aufzüge nach EN 81-20/-50 geeignet,
entspricht den Anforderungen der Richtlinie
2014/33/EU über Aufzüge
Bestellbeispiel für Varianten
BD 5987 .02 /_ _ _ AC 230 V 50 / 60 Hz
Nennfrequenz
Nennspannung
Variante, bei Bedarf
Kontaktbestückung
Gerätetyp
Varianten
Vorgehen bei Störungen
Fehler mögliche Ursache
LED "Netz" leuchtet nicht Versorgungsspannung
nicht angeschlossen
LED "K2" leuchtet,
aber "K3" nicht
- Sicherheitsrelais K2 ist verschweißt
(Gerät austauschen)
- Es hat eine einkanalige Abschaltung
an S22, T22 bzw. S23 stattgefunden
(Kanal an S12 bzw. T12 abschalten)
LED "K3" leuchtet,
aber "K2" nicht
- Sicherheitsrelais K3 ist verschweißt
(Gerät austauschen)
- Es hat eine einkanalige Abschaltung
an S12 bzw T12 stattgefunden
(Kanal an S22, T22 bzw.
S23 abschalten)
Gerät kann nicht gestartet
werden
- Ein Sicherheitsrelais ist verschweißt
(Gerät austauschen)
- Handstart-Modus:
Leitungsschluss am Start-Taster
(Versorgungspannung trennen und
Fehler beheben)
- Autostart-Modus:
X5 - X6 bzw. T33 - X6
nicht gebrückt
Wartung und Instandsetzung
- Das Gerät enthält keine Teile, die einer Wartung bedürfen.
- Bei vorliegenden Fehlern das Gerät nicht öffnen, sondern an de
Hersteller zur Reparatur schicken.
Nennspannung UN: AC 24, 42, 48, 110, 127, 230, 240 V
DC 24 V
Umgebungstemperatur: - 15 … + 55 °C
Schaltvermögen: 6 A, 250 Vac G.P.
Leiteranschluss: nur für 60°C / 75°C Kupferleiter
AWG 18 - 16 Torque 7 lb in
nfo
Fehlende technische Daten, die hier nicht explizit angegeben
sind, sind aus den allgemein gültigen technischen Daten zu
entnehmen.
UL-Daten

8BD 5987 / 22.01.19 de / 088A
Kennlinien Anwendungsbeispiele
L1
M6898_b
N
Not-
Aus
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
Y1
BD5987
13 23
14 24
Ein
L1
M6900_b
N
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
BD5987
Ein
Aus
Not-
Aus
Y1
13 23
14 24
L1
M10429_a
A1(+)
BD5987.02/301
Aus
Not-
Aus
N
A2(-) X5 X6 S34 14 24
Ein
S12 S12 S22 S21 S23 S33 13 23
S33
Zweikanalige Not-Aus-Schaltung.
Geeignet bis SIL3, Performance Level e, Kat. 4
Einkanalige Not-Aus-Schaltung.Diese Schaltung hat keine Redundanz im
Not-Aus-Befehlsgeberkreis.
Geeignet bis SIL2, Performance Level d, Kat. 3
1
010
Dauerstromgrenzkurve
(Strom über2Kontaktreihen)
20 30 40 50 T( C)
60
M6897_a
2
3
4
5
6
7
I (A)
Dauerstromgrenzkurve
Lichtbogen-Grenzkurve bei ohmscher Last
00,10,3 0,51 35 10
SchaltstromA
50
100
150
250
200
SchaltspannungVDC
M2001_c
Sicheres Abschalten, kein stehender Lichtbogen,
max. 1Schaltspiel / s

9BD 5987 / 22.01.19 de / 088A
Anwendungsbeispiele
Zweipolige Not-Aus-Schaltung mit Not-Aus-Befehlsgeber im Versorgungs-
stromkreis, mit automatischer Ein-Funktion.
Applikation für lange Not-Aus-Schleifen, bei denen die Steuerspannung
unter die Mindestspannung von 21 V abfällt.
Achtung:
Bei dieser äußeren Beschaltung werden Einzelfehler (z.B. Leitungs-
schlüsse über dem Not-Aus-Befehlsgeber) nicht erkannt.
Geeignet bis SIL2, Performance Level d, Kat. 3
Kontaktverstärkung durch externe Schütze, zweikanalig.
Bei Schaltströmen >10 A können die Ausgangskontakte durch externe
Schütze mit zwangsgeführten Kontakten verstärkt werden. Die Funktion
der externen Schütze wird durch Einschleifen der Öffnerkontakte in den
Einschaltkreis (Klemmen Y2 - S12) überwacht.
Geeignet bis SIL3, Performance Level e, Kat. 4
Einkanalige Not-Aus-Schaltung.Diese Schaltung hat keine Redundanz im
Not-Aus-Befehlsgeberkreis.
Geeignet bis SIL2, Performance Level d, Kat. 3
Zweikanalige Not-Aus-Schaltung mit Querschlusserkennung.
Aktivierung über Ein-Taster. Brücke X5 - X6 entfällt.
Für automatische Ein-Funktion ist Brücke X5 -X6 zu setzen.
Der Ein-Taster entfällt.
Geeignet bis SIL3, Performance Level e, Kat. 4
Zweikanalige Überwachung eines Schiebeschutzgitters.
Geeignet bis SIL3, Performance Level e, Kat. 4
Zweikanalige Not-Aus-Schaltung ohne Querschlusserkennung.
Aktivierung über Ein-Taster. Brücke X5 - X6 entfällt.
Für automatische Ein-Funktion ist Brücke X5 -X6 zu setzen.
Der Ein-Taster entfällt.
Geeignet bis SIL3, Performance Level e, Kat. 4
L1
M6901_c
N
Not-
Aus
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
Y1
BD5987
13 23
14 24
K4
K5
Ein
K4
K5
M6899_c
Aus
Not-
Aus
L1
A1(+)
BD5987.02/301
N
A2(-) X5 X6 14 24
S12 S22S12 S21 S23S33 13 23
M11384
Not-
Aus
L1
A1(+)
BD5987.02/301
N
A2(-) X5 X6 14 24
S12 S22S12 S21 S23S33 13 23
L1
M6904_c
N
Not-
Aus
A2(-)
A1(+)
S21
PE S33S23S22S12
X5S33S12 X6 S34
BD5987.02/001
13 23
14 24
Ein
L1
M6903_b
N
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
Y1
BD5987
13 23
14 24
Ein
betätigter Schließer
(Kontaktstellung: geschlossen)
S1
S2
Schiebeschutzgitter
geschlossen
L1
M6905_c
N
Not-
Aus
A2(-)
A1(+)
S21
PE S33S23S22S12
X5S33S12 X6 S34
BD5987.02/001
13 23
14 24
Ein

10 BD 5987 / 22.01.19 de / 088A
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail: dold-relays
@dold.com • internet: http://www.dold.com
•
Postfach 1251 • Telefon 0 77 23 / 654-0 • Telefax 0 77 23 / 654-356

11 BD 5987 / 22.01.19 en / 088A
SAFEMASTER
Emergency Stop Module
BD 5987
Datasheet / Operating Instructions ENGLISH
E. DOLD & SÖHNE KG
P.O. Box 1251 • D-78114 Furtwangen • Germany
Tel: +49 7723 6540 • Fax +49 7723 654356
Translation
of the original instructions
0262943

12 BD 5987 / 22.01.19 en / 088A
Contents
Symbol and Notes Statement..........................................................................................................................................13
General Notes .................................................................................................................................................................13
Designated Use...............................................................................................................................................................13
Safety Notes ....................................................................................................................................................................13
Product Description .........................................................................................................................................................15
Fucntion Diagram ............................................................................................................................................................15
Block Diagram .................................................................................................................................................................15
Approvals and Markings ..................................................................................................................................................15
Applications .....................................................................................................................................................................15
Indication .........................................................................................................................................................................15
Circuit Diagrams..............................................................................................................................................................16
Connection Terminals ......................................................................................................................................................16
Notes ...............................................................................................................................................................................16
Technical Data.................................................................................................................................................................16
Technical Data.................................................................................................................................................................17
Standard Type..................................................................................................................................................................17
Troubleshooting ...............................................................................................................................................................17
Maintenance and repairs.................................................................................................................................................17
Variants............................................................................................................................................................................17
Characteristics.................................................................................................................................................................18
Application Examples ......................................................................................................................................................18
Application Examples ......................................................................................................................................................19
Labeling and connections................................................................................................................................................41
Dimensions (dimensions in mm) .....................................................................................................................................41
Safety Related Data ........................................................................................................................................................42
CE-Declaration of Conformity..........................................................................................................................................43
CE-Declaration of Conformity..........................................................................................................................................44

13 BD 5987 / 22.01.19 en / 088A
Safety Notes
WARNING
Risk of electrocution!
Danger to life or risk of serious injuries.
• Disconnect the system and device from the power supply and ensure
they remain disconnected during electrical installation.
• The device may only be used for the applications described in the mu-
tually applicable operating instructions / data sheet. The notes in the
respective documentation must be heeded. The permissible ambient
conditions must be observed.
• The contact protection of the elements connected and the insulation of
the supply cables must be designed in accordance with the requirements
in the operating instructions / data sheet.
• Note the VDE and local regulations, particularly those related to protec-
tive measures.
WARNING
Risk of fire or other thermal hazards!
Danger to life, risk of serious injuries or property damage.
• The device mayonly beused for the applicationsdescribedinthemutually
applicable operating instructions / data sheet. The notes in the respective
documentation must be heeded. The permissible ambient conditions
must be observed. In particular, the current limit curve must be heeded.
• The device may only be installed and put into operation by experts who
are familiar with this technical documentation and the applicable health
and safety and accident prevention regulations.
WARNING
Functional error!
Danger to life, risk of serious injuries or property damage.
• The device may only be used for the applications described in the mu-
tually applicable operating instructions / data sheet. The notes in the
respective documentation must be heeded. The permissible ambient
conditions must be observed.
• The device may only be installed and put into operation by experts who
are familiar with this technical documentation and the applicable health
and safety and accident prevention regulations.
• The unit should be panel mounted in an enclosure rated at IP 54 or
superior (not neccessary for variant BD5987.02/301 when used in
anelevatorcontrolaccordingtoelevatordirective2014/33/EU.Theusageis
limitedtothe applicationinstationarycabinets-notintheliftcabin.Ambient
conditions at the place of installation must not have a negative influence
to function of the circuit. See also note 1 in section " technical data"
and application examples M10430_a, M6745_b and M11385).Dust and
dampness may lead to malfunction.
WARNING
Installation fault!
Danger to life, risk of serious injuries or property damage.
• Make sure of sufficient protection circuitry at all output contacts for
capacitive and inductive loads.
!
Attention!
• The safety function must be triggered during commissioning.
• If a line fault occurs at the On pushbutton after the voltage is already
present at S12, S22 undesired activation will take place, because this
line fault does not differ from the normal closing function.
• AUTOMATIC START !
According to IEC/EN 60 204-1 part 9.2.5.4.2 and 10.8.3 it
is not allowed
to restart automatically after emergency stop.
Therefore the machine control has to disable the automatic start
after emergency stop.
• Opening the device or implementing unauthorized changes voids any
warranty
DANGER
DANGER:
Indicates that death or severe personal injury will result if
proper precautions are not taken.
WARNING
WARNING:
Indicates that death or severe personal injury can result if
proper precautions are not taken.
CAUTION
CAUTION:
Indicates that a minor personal injury can result if proper
precautions are not taken.
!
ATTENTION:
Warns against actions that can cause damage or malfunction of the
device, the device environment or the hardware / software result.
nfo
INFO:
Referred information to help you make best use of the product.
Symbol and Notes Statement
The installation must only be done by a qualified electrican!
Do not dispose of household garbage!
The device must be disposed of in compliance with nationally
applicable rules and requirements.
To help you understand and find specific text passages and notes in the
operating instructions, we have important information and information
marked with symbols.
Before installing, operating or maintaining this device, these in-
structions must be carefully read and understood.
The product hereby described was developed to perform safety functions
as a part of a whole installation or machine. A complete safety system
normally includes sensors, evaluation units, signals and logical modules
for safe disconnections. The manufacturer of the installation or machine
is responsible for ensuring proper functioning of the whole system. DOLD
cannot guarantee all the specifications of an installation or machine that
was not designed by DOLD. The total concept of the control system into
which the device is integrated must be validated by the user. DOLD also
takes over no liability for recommendations which are given or implied in
the following description. The following description implies no modification
of the general DOLD terms of delivery, warranty or liability claims.
General Notes
Designated Use
The BD 5987 is used to interrupt a safety circuit in a safe way. It can be
used to protect people and machines in applications with e-stop buttons
and safety gates. The BD 5987 is used to interrupt a safety circuit in a
safe way. It can be used to protect people and machines in applications
with e-stop buttons and safety gates. The BD 5987.02/301 can be used
as electronic replacement of a safety switch according to EN 81-20,
section5.11.2.2. Applicationsaccordingto applicationexamplesM10430_a,
M6745_b and M11385.
When used in accordance with its intended purpose and following these
operating instructions, this device presents no known residual risks.
Nonobservance may lead to personal injuries and damages to property.
Storage for future reference

14 BD 5987 / 22.01.19 en / 088A

15 BD 5987 / 22.01.19 en / 088A
Your Advantages
• Safe disconnection of electrical circuits
• Line fault detection at On pushbutton
• Gold-plated contacts to switch small loads (input for PLC)
• Optionally cross fault detection in emergency stop circuit
Features BD 5987._ _:
•According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• Output: 2 NO contacts for AC 250 V
• 1-channel or 2-channel connection
• LED displays for channels 1 and 2
• Overvoltage and short circuit protection
• Wire connection: also 2 x 1,5 mm2stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or
2 x 2.5 mm2stranded ferruled DIN 46 228-1/-2/-3
• Width 45 mm
BD 5987._ _/001: same as BD 5987._ _ but
• Optionally automatic On function or after activation by the On pushbutton
• Optionally cross fault detection in emergency stop circuit
BD 5987.02/301: same as BD 5987.02/001 but
• Suitable also for elevators according to EN 81-20/-50
• Complies to the requirements of the directive 2014/33/EU for elevators
•According to
- Performance Level (PL) d and category 3 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
- Safety Integrity Level (SIL) 2 to IEC/EN 61508
• Shorter release time when opening the supply circuit
• Single-channel e-stop circuit
0221553
Safety Technique
SAFEMASTER
Emergency Stop Module
BD 5987
Product Description
The BD 5987 is used to interrupt a safety circuit in a safe way. It can be
usedto protect people and machinesinapplications with e-stopbuttonsand
safety gates. The BD 5987.02/301 can be used as electronic replacement
of a safety switch according to EN 81-20, section 5.11.2.2. Applications
according to application examples M10430_a, M6745_b and M11385.
Approvals and Markings
* see variants
Canada / USA
*
Applications
Protection of people and machines
- Emergency stop circuits on machines
- Monitoring of safety gates
Indication
LED power supply: on when operating voltage present
LED K2: on when supply on K2
LED K3: on when supply on K3
Fucntion Diagram
Pushbutton
On
K2
M 6742
K3 * Short-circuit detection
at the On pushbutton
*
Emergency-
stop (Off)
Block Diagram
M6758_b
A1(+)A2(-) S33 PE(-)
S33S33 Y2 S12 S12
S21/
PE S22X6X5 332313
S34 Y1 34S23 2414
K2K1
K3
K1
24V K3
K2
&
power
monitoring
logic K2
K3
overvoltage and short-
circuit protection
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.

16 BD 5987 / 22.01.19 en / 088A
Input
Nominal voltage UN:AC 24, 42, 48, 110, 127, 230, 240 V 1)
DC 24 V
Voltage range: AC 0.8 ... 1.1 UN
at 10% residual ripple: DC 0.9 ... 1.2 UN
at 48% residual ripple: DC 0.8 ... 1.1 UN
Nominal consumption: approx. 5.5 VA
Nominal frequency: 50 / 60 Hz
Control voltage at S33: DC 24 V
Control current
BD 5987.02: typ. DC 55 mA
BD 5987.02/001 + /301: typ. DC 45 mA
Minimum voltage at
terminals S12, S22: DC 21 V with activated device
Recovery time: 0.5 s after release of the e-stop pushbutton
Output
Contacts
BD 5987.02: 2 NO contacts
BD 5987.03: 2 NO contacts, 1 NO contact used for
monitoring
The NO contact 33-34 can only be used for monitoring.
Operate time: max. 100 ms
BD 5987.02/001 + /301: with automatic restart approx. 1 s
Release time
2-channel disconnecting in
secondary circuit
(S12, S22 and S23): 50 ms ±25 %
Opening in supply circuit
BD 5987.02: 350 ms ±50 %
BD 5987.02/001: 120 ms ±50 %
BD 5987.02/301: 40 ms ±50 %
Fault detection time at UN:
at 1-channel interruption
at S12:
BD 5987: typ. 430 ms
BD 5987/001+/201: typ. 85 ms
at S22 and S23: 50 ms ±25 %
Contact type: relay, forcibly guided
Nominal output voltage: AC 250 V 1)
DC: see arc limit curve
Thermal current Ith:see continuous current limit curve
(max. 10 A in one contact path)
Switching capacity
contacts 13/14, 23/24:
to AC 15: 3 A / AC 230V 1) IEC/EN 60 947-5-1
to AC 15: 6 A / AC 230V 1) at 0.25 Hz
to DC 13: 2 A / DC 24 V IEC/EN 60 947-5-1
to DC 13: 6 A / DC 24 V at 0.1 Hz
contacts 33/34:
to AC 15: 3 A / AC 230V IEC/EN 60 947-5-1
to DC 13: 2 A / DC 24 V IEC/EN 60 947-5-1
Electrical life
contacts 13/14, 23/24
at AC 230 V, 6 A, cos ϕ= 1: > 5 x 105switching cycles
contacts 33/34
at AC 230 V, 1 A, cos ϕ= 1: > 5 x 105switching cycles
Permissible operating
frequency: 600 switching cycles / h
1) max. AC 160 V or DC 160V for the variant BD 5987.02/301 when used
in an elevator control acc. to elevator directive 2014/33/EU, if the
BD 5987.02/301 is not installed in a cabinet with prot. degree IP 54 or better.
Short circuit strength
max. fuse rating: 6 A gG / gL IEC/EN 60 947-5-1
Mechanical life: 10 x 106switching cycles
General Data
Operating mode: Continuous operation
Temperature range
operation: - 15 ... + 55°C
at max. 90 % humidity
storage : - 25 ... + 85 °C
altitude: < 2.000 m
Clearance and creepage
distances
rated impuls voltage /
pollution degree: 4 kV / 2 (basis insulation) IEC 60 664-1
EMC: IEC/EN 62 061
Interference suppression: Limit value class B EN 55 011
Degree of protection
Housing: IP 40 IEC/EN 60 529
Terminals: IP 20 IEC/EN 60 529
Connection Terminals
Terminal designation Signal description
A1 (+) + / L
A2 (-) - / N
S12, S22, S23, S34, X6, Y2
T12, T22, T34 Inputs
PE (-), S21/PE, S33, X5, Y1
T11, T12, T33 Outputs
13, 14, 23, 24 Forcibly guided NO contacts for
release circuit
33, 34 Indicator output
Notes
Line fault detection at the On pushbutton:
The output contacts cannot be closed if the On pushbutton is already
closed before the voltage is applied to S12, S22 (also in the event of a line
fault at the On pushbutton).
A line fault at the On pushbutton which occurs after activation of the de-
vice is recognized when switching- on takes place again and closing of the
output contacts is then prevented.
If a line fault occurs at the On pushbutton after the voltage is already
present at S12, S22 undesired activation will take place, because this line
fault does not differ from the normal closing function.
The gold-plated contacts of the BD 5987 mean that this module is also
suitable for switching small loads of 1 mVA ... 7 VA, 1 mW ... 7 W in the
range 0.1 ... 60 V, 1 ... 300 mA. The contacts also permit the maximum
switching current. However, since the gold plating will be burnt off at this
current level, the device is no longer suitable for switching small loads
after this.
The PE terminal permits operation of the device in IT systems with insula-
tion monitoring and also serves as a reference point for testing the control
voltage.The internal short-circuit protection will be bridged on DC devices,
if the protective ground is connected to terminal PE.
One or more extension modules BN 5989 or external contactors with for-
cibly guided contacts may be used to multiply the number of contacts of
the emergency stop module BD 5987.
For automatic restart:
S22 must be connected before S12. S12 initiates the automatic restart.
With manual restart it is not necessary to follow this order.
Technical Data
Circuit Diagrams
K3
K2
Y2 PE
A1 Y1
S33
S12
S22
S34
A2
23
2414
13
S12 S12 S34
S33
S33 S33
A1
(+)
PE
(-)
S22
14 24
Y1
13 23 Y2
A2
(-)
M7375_b
K3
K2
K1
X6 PE
A1 X5
S33
S12
S22
S34
A2
23
24 34
33
14
13
33 S34
S21
/PE
34 X6
X5
A1
(+) S22S12
14 24
S23
13 23 S33
A2
(-)
M7378_b
K3
K2
X6 PE
A1 X5
S33
S12
S22
S34
A2
23
2414
13
S12 S34
S21
/PE
S33 X6
X5
A1
(+) S22S12
14 24
S23
13 23 S33
A2
(-)
M7376_b
K3
K2
K1
X6 PE
A1 T11
T33
T12
T22
T34
A2
23
24 34
33
14
13
33 T34
PE
34 X6
T33
A1
(+) T22T12
14 24
S23
13 23 T11
A2
(-)
M7379_c
BD 5987.02 BD 5987.03/001
BD 5987.02/001 + /301 BD 5987.03/201

17 BD 5987 / 22.01.19 en / 088A
Housing: Thermoplastic with V0 behaviour
according to Ul subject 94
Vibration resistance: Amplitude 0,35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz
Climate resistance: 15 / 055 / 04 IEC/EN 60 068-1
Terminal designation: EN 50 005
Wire connection: 1 x 4 mm2solid or
1 x 2,5 mm2stranded ferruled (isolated)
or
2 x 1,5 mm2stranded ferruled (isolated)
DIN 46 228-1/-2/-3/-4 or
2 x 2,5 mm2stranded ferruled
DIN 46 228-1/-2/-3
Wire fixing: Plus-minus terminal scews
M3.5 box terminal with wire protection
Fixing torque: 0.8 Nm
Mounting: DIN rail IEC/EN 60 715
Weight: 450 g
Dimensions
Width x height x depth: 45 x 74 x 121 mm
Technical Data
Standard Type
BD 5987.02/001 DC 24 V
Article number: 0040954
• Output: 2 NO contacts
• Nominal voltage UN: DC 24 V
• Width: 45 mm
BD 5987.02/61: with UL approval (Canada/USA)
BD 5987.02/001: Optionally cross fault monitoring on the
emergency stop loop (see application M6749)
OptionallyautomaticOnfunctionwhenoperatingvoltage
is applied or after activation by the On pushbutton.
Jumper asignment for functions:
Activation via On pushbutton / or automatic On function:
M8687
On pushbutton
S12-S34 or
S33-S34
Jumper
X5 - X6 Function
The output contacts are switched only
after operation of the On pushbutton.
Line fault monitoring at the On push-
button.
Automatic On function for operating
voltage Off/On or after emergency-
stop release
BD 5987.03/001: with 2 NO contacts,
1 signalling contact AC/DC 0,1 ... 1 A / 10 ...120 V
BD 5987.03/201: see BD 5987.03/001,
but with special terminal designation
Jumper asignment for functions:
Activation via On pushbutton / or automatic On function
M8687
On pushbutton
T11-T34 or
T12-T34
Jumper
T33 - X6 Function
The output contacts are switched only
after operation of the On pushbutton.
Line fault monitoring at the On push-
button.
Automatic On function for operating
voltage Off/On or after emergency-
stop release
BD 5987.02/301: Starting behaviour as with BD 5987.02/001,
shorter release time when opening the supply circuit,
Suitable also for elevators according to EN 81-20/-50,
Complies to the requirements of the directive
2014/33/EU for elevators.
Ordering example for variants
BD 5987 .02 /_ _ _ AC 230 V 50/60 Hz
Nominal frequency
Nominal voltage
Variant, if required
Contacts
Type
Variants
Troubleshooting
Failure Potential cause
LED "Power" does not light up Power supply not connected
LED "K2" lights up,
but "K3" remains off
- Safety relay K2 is welded
(replace device)
- A 1-channel switch-off occurred on
S22, T22 e.g. S23
(switch channel off on S12 e.g. T12)
LED "K3" lights up,
but "K2" remains off
- Safety relay K3 is welded
(replace device)
- A 1-channel switch-off occurred on
S12 e.g. T12
(switch channel off on S22, T22 e.g.
S23)
Device cannot be activated - Safety relay is welded
(replace device)
- Manual start mode:
Line fault on start-button (disconnect
power supply and remove fault)
- Automatic start mode:
X5 - X6 e.g. T33 - X6
are not bridged
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
Nominal voltage UN: AC 24, 42, 48, 110, 127, 230, 240 V
DC 24 V
Ambient temperature: - 15 … + 55 °C
Switching capacity: 6 A, 250 Vac G.P.
Wire connection: 60°C / 75°C copper conductors only
AWG 18 - 16 Torque 7 lb in
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
UL-Data

18 BD 5987 / 22.01.19 en / 088A
Characteristics Application Examples
Two-channel emergeny stop circuit.
Suited up to SIL3, Performance Level e, Cat. 4
Single-channel emergency stop circuit.This circuit does not have any red-
undancy in the emergency stop control circuit.
Suited up to SIL2, Performance Level d, Cat. 3
L1
M6744_a
N
emergency-
stop
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
BD5987
on
Y1
13 23
14 24
L1
M6743_a
N
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
BD5987
on
off
emergency-
stop
Y1
13 23
14 24
L1
M10430_a
A1(+) S12 S12 S22 S21 S23 S33
BD5987.02/301
off
emergency-
stop
13 23
N
A2(-) X5S33 X6 S34 14 24
on
00,10,3 0,513510
switching current A
50
100
150
250
200
switchingvoltage VDC
M2987_
c
safe breaking, no continuous arcing,
max.1switching cycle/s
Arc limit curve with resistive load
1
010
Continuous current limit curve
(Current via two contact rows)
20 30 40 50 T(
C)
60
M6759
2
3
4
5
6
7
I (A)
Continouos current limit curve

19 BD 5987 / 22.01.19 en / 088A
Application Examples
Two-pole emergency stop circuit with emergency stop control device in
supply circuit with automatic ON-function.
Application for long emergency stop loops where the control voltage drops
below the minimum voltage of 21 V.
Attention:
Single faults (e.g. line faults at the emergency stop control device) are not
detected with this external circuit configuration.
Suited up to SIL2, Performance Level d, Cat. 3
Contact reinforcement by external contactors, 2-channel.
The output contacts can be reinforced by external contactors with forcibly
guided contacts for switching currents > 10 A. Functioning of the external
contactors is monitored by looping the NC contacts into the closing circuit
(terminals Y2 - S12).
Suited up to SIL3, Performance Level e, Cat. 4
Single-channel emergency stop circuit. This circuit does not have any
redundancy in the emergency stop control circuit
Suited up to SIL2, Performance Level d, Cat. 3
Two-channel emergency stop circuit with cross fault detection.
Activation via On pushbutton. ---- Jumper X5 -X6:
Jumper X5 - X6 must be fitted for the automatic On function.
The On pushbutton is not required.
Suited up to SIL3, Performance Level e, Cat. 4
Two-channel monitoring of a safety gate.
Suited up to SIL3, Performance Level e, Cat. 4
Two-channel emergency-stop circuit without cross fault detection.
Activation via On pushbutton. ---- Jumper X5 - X6:
Jumper X5 - X6 must be fitted for the automatic On function.
The On pushbutton is not required.
Suited up to SIL3, Performance Level e, Cat. 4
L1
M6745_b
A1(+)
BD5987.02/301
N
A2(-) X5 X6 14 24
S12 S22S12 S21 S23S33 13 23
off
emergency-
stop
L1
M6746_b
N
emergency-
stop
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
Y1
BD5987
13 23
14 24
K4
K5
on
K4
K5
M11385
emergency-
stop
L1
A1(+)
BD5987.02/301
N
A2(-) X5 X6 14 24
S12 S22S12 S21 S23S33 13 23
L1
M6749_a
N
emergency-
stop
A2(-)
A1(+)
S21
PE S33S23S22S12
X5S33S12 X6 S34
BD5987.02/001
13 23
14 24
on
L1
M6748_b
N
A2(-)
A1(+) S33S34 S33 S33 PE(-) Y2 S12 S12 S22
Y1
BD5987
13 23
14 24
on
S1
S2
safety gate
closed
activated NO contact
(contact position: closed)
L1
M6750_b
N
A2(-)
A1(+)
S21
PE S33S23S22S12
X5S33S12 X6 S34
BD5987.02/001
13 23
14 24
on
emergency-
stop

20 BD 5987 / 22.01.19 en / 088A
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail: dold-relays
@dold.com • internet: http://www.dold.com
•
POBox1251•Telephone(+49)77 23 / 654-0 •Telefax (+49) 77 23 / 654-356
This manual suits for next models
2
Table of contents
Languages:
Other DOLD Control Unit manuals

DOLD
DOLD INFOMASTER SMS RP 5812 User manual

DOLD
DOLD Safemaster Pro Series User manual

DOLD
DOLD SAFEMASTER M BH 5911 User manual

DOLD
DOLD SAFEMASTER BN 5930.48/203 User manual

DOLD
DOLD SAFEMASTER BG 5925 Series User manual

DOLD
DOLD SAFEMASTER C BH 5910 User manual

DOLD
DOLD SAFEMASTER LG 5928 User manual

DOLD
DOLD SAFEMASTER BH 5928 Operating instructions

DOLD
DOLD SAFEMASTER RK 5924 User manual

DOLD
DOLD SAFEMASTER PRO UG 6951 User manual