DOLD VARIMETER IMD Series User manual

106.05.21 en / 393A
0278362
Your Advantages
• Suitable for DC charging stations for electric vehicles acc. to
IEC/EN 61851-23:2014
• Insulation monitoring according to IEC/EN 61557-8
• Connection of an external coupling device RL 5898
for voltages up to AC 400 V / DC 500 V or
RP 5898 for voltages up to AC 690 V / DC 1000 V
• Extended operating temperature range of - 40 ... + 70 °C
• Very fast reaction time ≤1 s
• Optimised insulation resistance monitoring also during
mains voltage variation
• Self-test every full operating hours
• Preventive fire and system protection
• Detection of symmetric and asymmetric insulation faults
• Universal application in non-earthed AC, DC, AC/DC networks
• Easy adjustment of response values and setting parameter via
rotational switch
• Suitable for large leakage capacitances up to 5 µF
• Monitoring also with voltage-free mains
• Measuring circuit L1(+)/L2(-) with broken wire detection (can be switched off)
• Protective conductor PE1/PE2 with broken wire detection
(can't be switched off)
Features
• 2 separate adjustable response thresholds
(using e.g. for pre-alarm and Alarm)
• Setting range of 1st response value (Pre-alarm): 20 kΩ… 500 kΩ
• Setting range of 2nd response value (alarm): 1 kΩ… 100 kΩ
• 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
• Energized or de-energized on trip can be selected for indicator relay
• With multicolour status LED to indicate the state of operation.
• Automatic and manual device self-test
• Alarm storage selectable
• Protection against manipulation by sealable transparent cover
• External control input for combined test- / reset-button
with additional Stop of the measuring function
• 3 wide voltage input for auxiliary voltage
• Additional coupling device is necessary
• Width 52.5 mm
Product Description
Approvals and Markings
Applications
Insulation monitoring of:
• Non-earthed AC, DC, AC/DC networks
• DC charging stations for electric vehicles
• UPS systems
• Networks with frequency inverters
• Battery networks
• Networks with direct current drives
• Hybrid and battery-powered vehicles
• Mobile generator sets
Monitoring Technique
VARIMETER IMD
Insulation monitor
RN 5897/320
RN 5897/320 RP 5898
Coupling devices
RL 5898
The insulation monitor RN 5897/020 of the VARIMETER IMD family
provides best and up to date insulation monitoring of modern IT systems
in an optimum and state of the art way fulfilling the relevant standards.
The device can be used in the most flexible way for AC, DC and AC/
DC systems. Mains areas of applications are non-earthed DC charging
stations for electric vehicles with mains voltages up to DC 1000 V, that
need an extended temperature range. The connection to the monitored
voltage system is done via one of the coupling units. The setting of the
parameters and the switching values is done by simple and operator
friendly rotational switches on front of the device. The operating status is
indicated user friendly via a multicolour LED. With a sealable transparent
cover the device is protectet against manipulation.
AC/DC
Canada / USA 1) RN 5897 only
Translation
of the original instructions
Connection Terminals
Terminal designation Signal description
A1(+), A2 Auxiliarx voltage AC or DC
L(+), L(-), VSG1, VSG2 Connection for coupling device
PE1, PE2 Connection for protective conductor
X1, X2
Control input
(combined external Test- and Reset-input
with additional Stop of the measuring
function)
11, 12, 13 Alarm signal relay K1(1 changeover contact)
21, 22, 23 Prewarning signal relay K2 (1 changeover
contact)
Circuit Diagram
X1 X2
11 12 14 21 22 24 PE1 PE2
A2
A1(+)
L(+)VSG1 VSG2
L(-)
22
12
L(+) L(-)
24
14
21
PE2
11
PE1
UH
M11956_a
All Technical Data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.

206.05.21 en / 393A
The device is supplied with DC auxiliary voltage via terminals A1(+) / A2.
Switching on the auxiliary voltage (Power-On) is followed by an internal
self-test for 12 s (see „Device test functions“). The test process is visible
with the status LED. After this, measurement of the insulation resistance
in the measuring circuits begins and the status LED changes into green.
Measuring circuit
(Insulation measurement between terminals L1(+) / L2(-) on the
coupling device and PE1/PE2 on the insulation monitor)
The insulation monitor RN 5897/320 can only be used with a coupling
device. Max. mains voltage and connection diagrams have to be observed!
To connect the insulation Monitor RN5897/320 to a coupling device the
terminals with identical designations are connected (VSG1, VSG2, L(+),
L(-)) .The votage system to be monitored is connected to L1(+) und L2(-)
of the coupling device.
A broken wire detection that can be disabled provides a fault signal if
both terminals L1(+) and L2(-) are not linked by the connected network.
Broken wire between coupling device and insulation monitor cannot be
directly detected but the the measured value of the insulation resistance
when one or more connections are interrupted, is much lower then the real
insulation value which will cause a tripping of the alarm relays.
The type of the voltage system or the connection method (AC, DC, 3NAC)
has to be correctly adjusted on the rotational switch "UN"
Also the terminals PE1 and PE2 have to be connected with 2 separate
wires to the protective earth. An interruption of a wire also causes a fault
signal (see section ”Behavior on faulty connection”). The monitoring of
the PE connection cannot be de-activated.
To measure the insulation resistance an active measuring voltage with
changing polarity is connected between L1(+) and L2(-) and PE1/PE2.
The duration of the positive and negative measuring phase depends on
the actual leakage capacity of the monitored system and in DC systems
also on the level and duration of possible voltage variations. This allows
a correct and fast measurement in different network conditions.
At the end of a measuring cycle the actual insulation resistance is produced
and indicated. The relays for alarm K1 and pre-alarm K2 switch when
dropping under the adjusted response values. In addition the status LED
changes to orange color on pre-alarm or to red color on alarm.
Manual reset of fault message
With the 2-section rotational switch "UN", manual or auto reset of the alarm
can be selected. If manual reset is activated the insulation fault signals
of the measuring circuit are stored when dropping under the adjusted
response values also if the insulation resistance goes back to healthy
state. Pressing the „Reset“ button on the front side for 2 s, the alarm signal
is reset if the actual insulation resistance is in healthy state.
Indicator relay for insulation fault signal
The function of the relays K1 (contacts 11-12-14 for alarm) and K2 (contacts
21-22-24) can be altered between energised on trip (relay n.o.) or de-
energized on trip (relay n.c.). When energised on trip the relays energize
when the value drops below the setting, when de-energised on trip, the
relays de-energize when the value drops below the setting.
Disable the measuring function
Using the external control input X1/X2 the measuring function of the
RN 5897/320 can be disabled. This could be used when several isolated
voltage systems with individual insulation monitors need to be coupled.
The measuring voltage is set to -90V (negative measuring phase) and
the evaluation of the measurement is stopped. The status of the output
relays is frozen and not changed any more. If the measurement is disabled
the status LED flashes continuously orange. Please be aware, only the
evaluation of the measurement is stopped and the measuring pulse is
interrupted! A high resistive disconnection to PE does not take place
(see internal resistance).
Broken wire detection
As described in section "Measuring circut", the measuring circuits L(1+)/
L2(-) and the protective conductors PE1/PE2 are constantly monitored for
wire breaks – not only at Power-On or a manual or occasional automatic
test. The response time of PE1/PE2 monitoring is only a few seconds.
The response time of monitoring of L1(+)/L2(-) can be up to approx.
2 min. Broken wire detection between L1(+) and L2(-) is performed via
coupled alternating voltage. This alternating voltage is short-circuited if
the terminals are connected to the connected mains at low-resistance.
The device detects that the mains to be monitored is properly connected.
Since this broken wire detection is carried out with alternating voltage, large
capacitances should be avoided between L1(+) and L2(-), since the
capacitive reactance of these capacitances also short-circuits this
alternating voltage. The device would no longer detect a connection fault
on L1(+)/L2(-).
Especially parallel lines should be prevented over larger distances.
If larger capacitances between L1(+)/L2(-) cannot be avoided or if the coupled
alternating voltage interferes with the system, the broken wire detection
can be de-activated on the 2-section rotational switch for alarm "RA". It
can be altered between continuously disabled (Broken Wire Detect OFF),
or continuously enabled (Broken Wire Detect ON) for 10 seconds every
2 minutes. If the broken wire detection on L1(+)/L2(-) is de-activated no
AC voltage is injected. The broken wire detection on PE1/PE2 cannot be
de-activated.
Device test functions
Principally, 2 different test functions are implemented: The "self-test" and
the "expanded test":
The self-test of the device is performed automatically after Power-On and
every full operating hours. It can also be triggered manually at any time by
pressing the "Test" button at the device front for 2 s.
With the self-test, contrary to the expanded test, the status of the Indicator
relays is not affected; the sequence is as follows:
The self test is indicated by the status LED with flash code 1 in orange colour.
First the negative measuring pules is activated for about 5 s and the internal
measuring circuit is checked on failures. Then the positive measuring pulse
is activated for about 5 s and more internal tests are performed. If no failures
are detected, the normal measurement continuous. The extended test is
started, when during or at the end of above procedure (12 s) the button
"Test" is pressed again for 2 s.
The procedure is the same as above (2 measuring phases with 5 sec
each) but in addition the output relays K1 and K2 go into alarm state. The
Status LED shows flash code 2 in orange colour. The test phases will be
continuously repeated. The extended test can be finished after the first
complete sequence (approx. 10 sec) by pressing the "reset" button for 2
seconds. The device starts the insulation monitoring again.
Test signal 1)
Reset signal 2)
Relay state K1 and K2
Measuring voltage
Positive
Alarm
No Alarm
Insulation
measurement Insulation
measurement
Insulation
measurement
3)
4)
Self test (Test 1)
Duration: approx. 12s
Self test (Test 1)
Duration: approx. 12s
Duration: approx. 10s
Continuous extended
test (Test 2)
Negative
M12462
U
t
1) Test signal: Button Test > 2 s oder X1/X2 > 1,5 s und < 10 s
2) Reset signal: Button Reset > 2 s oder X1/X2 < 1,5 s
3) To initiate the extended test (Test 2) the test signal must be operated
within the self test (Test 1) again..
4) The reset signal has here no function, as the first complete sequence
of extended test (Test 2) is not finished.
FunctionFunction

306.05.21 en / 393A
Function Diagram
Manual reset
Alarm
Alarm Pre-Alarm Pre-Alarm
Hysteresis function
Reset
21-24
21-24
21-24
21-24
11-14
11-14
11-14
11-14
11-12
11-12
11-12
11-12
Earth fault
E
R
A
RpA
R
21-22
21-22
21-22
21-22
t
t
Open circuit operation
Open circuit operation
Open circuit operation
Open circuit operation
De-energized on trip
De-energized on trip
De-energized on trip
De-energized on trip
UH
M11593
Flashing Codes Status LED
extended
test
self test
connection failure
measuring ciruit L(+)/L(-)
connection failure
protective conductor PE1/PE2
LED-colour:
orange
LED-colour:
red
internal
system error
M12104
t
measuring function
disabled
Behaviour with internal device faults
If internal device faults were detected during the test function, the status
LED flashes permanently red. The indicator relays K1 and K2 switch to
the alarm state.
Behavior on faulty connection
When detecting broken wire on terminals L1(+)/L2(-), the measurement
is disabled. The reaction time could be up to 2 min. The monitoring relays
K1 and K2 go in alarm state, the status LED shows flash code 1 in red
colour. After removing the interruption the fault is automatically reset
(max. reaction time up to 2 min) and the measurement of the insulation
resistance is continued. Stored alarm values remain stored. An interruption
of the protective earth connections PE1/PE2 causes the same reaction
as interrupting the measuring circuit, only the status LED shows flash
code 2 in red colour.
External control input
To terminals X1/X2 an external combined Test-/Reset button can be
connected. If the terminals X1/X2 are bridged for approx.
> 1,5 s and <
10 s
the test mode is started. This has the same function as pressing the
internal test button. When bridging X1/X2 for
< 1,5 s
, a stored alarm will
be reset. This has the same function as pressing the internal reset button.
If X1/X2 is activated for > 10 s, the measuring function is stopped.
The measuring function remains suspended for the duration of the control
of X1/X2.
Programming/setting of parameters/set-up of the insulation monitor
All settings are made via 3 rotational switches on the front of the device.
To avoid unauthorised manipulation of the settings, the unit has a sealable
transparent cover on the front.
With the first rotational switch "R
A
" the response value for Alarm is selected.
In addition the rotational switch has 2 sections. If the rotational switch is in the
first section the broken wire detection of the measuring circuit is continuously
on. If the rotational switch is in the second section it is continuously off. The
second rotational switch "R
pA
" has also 2 sections and selects the pre alarm
value as well as the output function. in section 1 the unit is de-energised on
trip (n.c.) in section 2 on energised on trip (n.o.).
The third rotational switch selects "UN" selects the voltage system connection
and manual or auto reset it has also 2 sections. In section one the unit is on
auto reset, in section 2 it is on manual reset. Changes of the setting the unit
accepts immediately without restart.
Function

406.05.21 en / 393A
Indicators
RN 5897/320
Indicators
The operational status of the device is indicated on a 3-colour LED:
Off: No auxiliary voltage connected
Green: Normal operation (Insulation resistance in healthy
state)
Red: Alarm (measured value below alarm response value)
Orange: Warning (measured value below pre-alarm response
value)
Orange flashing: Test mode / Measurement stopped procedure
(see flashing code diagramm)
Red flashing: Failure code (see flashing code diagramm)
Flash code
orange
Status-LED
Description
1
Selftest
(measuring circuit, measuring voltage,
internal tests)
2Advanced Test
(additional control of indicator relays)
continously
flashing Measuring function stopped
Error Indication
Flash code
red
Status-LED
Failure cause Failure recovery
1Broken wire detection
on L(+)/L(-).
Check
measuring circuit
L(+) and L (-)
2Broken wire detection
on PE1/PE2.
Check
protective earth
connections
PE1 and PE2
continously
flashing
Internal failure
detected in
test mode
Press test button again or restart
the unit by interrupting the
auxiliary supply temporarily. If the
fault remains permanent, send
device back to manufacturer for
examination.
continously
flashing
Faulty calibration
values detected in
device memory.
Send device back to manufacturer
for recalobration and examination.
Notes
WARNING
Risk of electrocution!
Danger to life or risk of serious injuries.
• Disconnect the system and device from the power supply and ensure
they remain disconnected during electrical installation.
• Determine voltage free status by using appropriate instruments
• The terminals of the control input X1-X2 have no galvanic separation
to the measuring circuit L1(+) and L2(-) and are electrically connected
together, therefore they have to be controlled by volt free contacts or
bridge. These contacts ore bridges must provide a sufficient separation
depending on the mains voltage on L1(+)-L2(-).
• Please do not connect external voltage to terminals X1/X2. The control
must only be made by bridging X1 and X2.
• The coupling unit
RL 5898 or RP 5898
must only be used in conjunction
with the RP5897/320 on a voltage system and not just by itself.
!
Attention!
• Before checking insulation and voltage, disconnect the monitoring device
RN 5897/320 from the power source!
• In one voltage system only one insulation monitor can be used.This has
to be observed when interconnecting two separate systems..
• Device terminals PE1 and PE2 must always be connected via separate
lines to different terminal points of the protective-conductor system.
• The device must not be operated without PE1/PE2 connection!
nfo
Attention!
• The main measuring circuit can be connected with its terminals L1(+) and
L2(-) both to the DC and also AC side of a mixed network; it is done most
practically where the primary incoming power supply takes place e.g.
with battery networks with connected inverters on the DC side, with
Generators/Transformers with connected Rectifiers or inverters on
the AC-side. To monitor a 3NAC system the device can be connected
single pole, (L(+) and L(-) are bridged, to the neutral of the 3p4w sy-
stem. The 3 phases have a low-Ωic (approx. 3 – 5 Ω) connection via
the transformer windings so also insulation failures of the not directly
connected phases are detected. Via the rotary switch "UN" the correct
type of network needs to be selected (see „Connection Examples“).
• If a monitored AC system includes galvanically connected DC circuits
(e.g. via a rectifier), an insulation failure on the DC side can only be
detected correctly, when a current of min 10 mA can flow via the semi-
conductor connections.
• If a monitored DC system includes galvanically connected AC circuits
(e.g. via an inverter), an insulation failure on the AC side can only be
detected correctly, when a current of min 10 mA can flow via the semi-
conductor connections.
• The insulation monitor RN 5897/320 can only be used together with
a coupling device.
Connection
Coupling device
Auxiliary
voltage
M12107_a
Indicator relay
alarm and pre-alarm
Protective
conductor
External
control input

506.05.21 en / 393A
General Data
Operating mode: Continuous operation
Temperature range
Operation: - 40 ... + 70 °C
Storage: - 40 ... + 70 °C
Altitude: ≤2000 m IEC 60664-1
Clearance and creepage
distances
Rated insulation voltage: 300 V
Overvoltage category: III
Rated impuls voltage /
pollution degree: IEC 60664-1
Measuring circuit L(+)/L(-) to
auxiliary voltage A1(+)/A2 and
indicator relay contacts K1, K2: 4 kV / 2
Auxiliary voltage A1(+)/A2 to
indicator relay contacts K1, K2: 4 kV / 2
Indicator relay contact K1 to
indicator relay contacts K2: 4 kV / 2
Insulation test voltage
Routine test: AC 2.5 kV; 1 s
EMC
Electrostatic discharge (ESD): 8 kV (air) IEC/EN 61000-4-2
HF irradiation:
80 MHz … 1 GHz: 20 V / m IEC/EN 61000-4-3
1 GHz … 2.7 GHz: 10 V / m IEC/EN 61000-4-3
Fast transients: 2 kV IEC/EN 61000-4-4
Surge voltage
Between
wires for power supply: 1 kV IEC/EN 61000-4-5
Between wire and ground: 2 kV IEC/EN 61000-4-5
HF-wire guided: 20 V IEC/EN 61000-4-6
Interference suppression: Limit value classe B EN 55011
Degree of protection
Housing: IP 40 IEC/EN 60529
Terminals: IP 20 IEC/EN 60529
Housing: Thermpolastic with V0 behaviour
according to UL subject 94
Vibration resistance: Amplitude 0.35 mm,
Frequency 10 ... 55 Hz, IEC/EN 60068-2-6
frequency 2 ... 13.2 Hz, 13.2 ... 100 Hz,
acceleration ±0.7 gn IEC/EN 60068-2-6
Shock resistance: 10 gn / 11 ms, 3 pulses IEC/EN 60068-2-27
Climate resistance: 40 / 070 / 04 IEC/EN 60068-1
Terminal designation: EN 50005
Wire connection DIN 46228-1/-2/-3/-4
Cross section: 0.5 ... 4 mm² (AWG 20 - 10) solid or
0.5 ... 4 mm² (AWG 20 - 10)
stranded wire without ferrules
0.5 ... 2.5 mm² (AWG 20 - 10)
stranded wire with ferrules
Stripping length: 6.5 mm
Wire fixing: Cross-head screw / M3 box terminals
Fixing torque: 0.5 Nm
Mounting: DIN rail IEC/EN 60715
Weight: Approx. 205 g
Dimensions
Width x height x depth: 52.2 x 90 x 71 mm
Meas. ciruit L1(+)/L2(-) to PE1/PE2 (with coupling device RL / RP 5898)
RL 5898 RP 5898
Nominal voltage UN:AC 0 ... 400 V AC 0 ... 690 V
DC 0 ... 500 V DC 0 ... 1000 V
Max. max. voltage range UN:AC 0 ... 440 V AC 0 ... 760 V
DC 0 ... 550 V DC 0 ... 1100 V
Frequency range: DC or 40 ... 1000 Hz
Max. line capacitance: 5 µF
Internal resistance (AC / DC): > 240 kΩ
Measuring voltage: Approx. ±90 V
Max. mesured current (RE= 0): < 0.40 mA
Response inaccuracy: ±15 % ±1.5 kΩ IEC 61557-8
Response value hysteresis: Approx. + 25 %; min. + 1 kΩ
On delay
At CE= 1µF,
response value ≤100 kΩ,
REof ∞to 0.5 * response value: ≤1 s
At CE= 1µF,
response value > 100 kΩ,
REof ∞to 0.5 * response value: < 2 s
Measuring time:
At CE= 1 … 5 µF < 5 s
Min. operate time: > 0.2 s
Response values
Pre-warning („RpA“):
kΩ: 20 50 100 300 500
Alarm („RA“)
kΩ: 1 10 30 50 100
Each adjustable via rotational switches
Response value broken
wire detection L1(+)/L2(-): > Approx. 500 kΩ
Response value broken
wire detection PE1/PE2: > Approx. 0.5 kΩ
Max. wire length
between insulation monitor
and coupling device: < 0.5 m
Auxiliary voltage input A1(+)/A2
Nom. Voltage Voltage range Frequency range
AC/DC 24 ... 60 V AC 19 ... 68 V 45 … 400 Hz; DC 48 % W*)
DC 16 ... 96 V W*)≤5 %
AC/DC 85 ... 230 V AC 68 ... 276 V 45 … 400 Hz; DC 48 % W*)
DC 67 ... 300 V W*)≤5 %
DC 12 ... 24 V DC 9.6 ... 30 V W*)≤5 %
*)W = Permitted residual ripple of auxiliary supply
Nominal consumption:
DC 12 V, 24 V, 48 V: Max. 3 W
AC 230 V: Max. 3.5 VA
Control input X1/X2 for external combined Test-/Reset-Taste
Current flow: Approx. 3 mA
No-load operation voltage
X1 to X2: Approx. 12 V
Permissible wire length: < 50 m
Activat. time t for test signal: 1.5 s < t < 10 s
Activat. time t for reset signal: t < 1.5 s
Activation time t for stop
of the measuring function: t > 10 s
Outputs
Indicator contact: 2 x 1 changeover contact for Alarm (K1)
and Pre-Alarm (K2)
energized or de-energized on trip
(programmable)
Thermal current Ith:4 A
Switching capacity
To AC 15:
NO contact: 5 A / AC 230 V IEC/EN 60947-5-1
NC contact: 2 A / AC 230 V IEC/EN 60947-5-1
To DC 13: 2 A / DC 24 V IEC/EN 60947-5-1
Electrical life
At 5 A, AC 230 V: 1 x 105switching cycles
Short circuit strength
Max. fuse rating: 4 A gG / gL IEC/EN 60947-5-1
Mechanical life: 50 x 106switching cycles
Technical Data Technical Data
Vibration and
shock resistance: Category 1, Class B IEC/EN 61373
Ambient temperature: OT1, OT2 compliant
Protective coating of the PCB: No
Classification to DIN EN 50155

606.05.21 en / 393A
Standard Types
RN 5897.12/320/61 DC 12 ... 24 V
Article number: 0068260
• Auxiliary voltage: DC 12 ... 24 V
RN 5897.12/320/61 AC/DC 24 … 60 V
Article number: 0068258
• Auxiliary voltage: AC/DC 24 … 60 V
RN 5897.12/320/61 AC/DC 85 … 230 V
Article number: 0068259
• Auxiliary voltage: AC/DC 85 … 230 V
• Outputs: 1 changeover contact for pre-warning
1 changeover contact for alarm
• Setting range pre-warning: 20 kΩ… 500 kΩ
• Setting range alarm: 1 kΩ… 100 kΩ
• With connection facility of a coupling device RL 5898 or RP 5898
• Max. line capacitance: 5 µF
• Energized or de-energized on trip
• Selection of type of network
• Width: 52.5 mm
Ordering Example for variants
RN 5897 .12
/020 /61 AC/DC 24 … 60 V 1 kΩ- 100 kΩ20 kΩ- 500 MΩ
Setting range Pre-warning
Setting range alarm
Auxiliary voltage
UL approval
Variant, if required
Contacts
Type
Meas. ciruit L1(+)/L2(-) to PE1/PE2 (with coupling device RL / RP 5898)
RL 5898 RP 5898
Max. voltage range UN:AC 0 ... 400 V AC 0 ... 600 V
DC 0 ... 500 V DC 0 ... 600 V
Output voltage at
L(+)/L(-), VSG1/VSG2: Max. AC / DC 230 V
Temperature range
Operation: - 30 ... + 60 °C
Switching capacity: Pilot duty C300, R300
5A 250Vac
2A 30Vdc
Wire connection: 60 °C / 75 °C copper conductors only
Torque 0.5 Nm
Test specification: ANSI/UL 60947-1, 5th Edition
ANSI/UL 60947-5-1, 3rd Edition
CAN/CSA-C22.2 No. 60947-1-13,
2nd Edition
CAN/CSA-C22.2 No. 60947-5-1-14,
1st Edition
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
UL-Data Accessories
Anschluss
Isolationswächter
Messkreis
M12053_a
RL 5898/61
Article number: 0068315
• Coupling device for RN 5897.12/320
• Extension of nominal voltage range UNto DC 500 V, AC 400 V
• Weight: Approx. 60 g
• Dimensions
- Width x height x depth: 35 x 90 x 71 mm
RP 5898/61
Article number: 0066944
• Coupling device for RN 5897.12/320
• Extension of nominal voltage range UNto DC 1000 V, AC 690 V
• Weight: Approx. 110 g
• Dimensions
- Width x height x depth: 70 x 90 x 71 mm
Anschluss
Isolationswächter
Messkreis
M11470_a
Switching capacity
To AC 15
NO contact: 3 A / AC 230 V
NC contact: 1 A / AC 230 V
nfo
Technical data that is not stated in the CCC-Data,can be found
in the technical data section.
CCC-Data

706.05.21 en / 393A
Accessories
Flush mounting kit
Order reference: KU 4087-150/0056598
For universal use with:
·R-series devices of
17.5 to 105 mm width
·Easy mounting

806.05.21 en / 393A
L1
Ungrounded mains
3N AC 400V/230V 40...1000Hz
L2
L3
N
RN5897/020
X1
external combined
test/reset button
X2 11PE1 12PE2 14 21 22 24
M11964
*2)
A1(+) A2
UH
*1)
UN
PE
Setting of type of network
3N AC
:
L(+)VSG1 L(-) VSG2
*1) Auxiliary voltage UH(A1(+)/A2) ) can also be sourced from the monitored voltage system.
The voltage range of the auxiliary supply has to be taken into account.
*2) Control input X1/X2 for external combined Test-/Reset-button with Stop of the measuring function:
• Control 1.5 s < t < 10 s: Test function
• Control < 1.5 s: Reset function
• Control > 10 s: Stop of measuring function
Connection Examples
VSG1
VSG1
L(+)
L(+)
L(-)
L(-)
PE
RN5897/320
X1
External combined
test/reset button
VSG2
VSG2
X2 11PE1 12PE2 14 21 22 24
M12110
*2)
A1(+) A2
UH
*1)
L1
L2
L3 UN
L1(+) L2(-)
Setting of type of network:
AC
External coupling device:
ON
RL5898
RP5898
Ungrounded mains
RL5898: 3 AC 0...440V 40...1000Hz
RP5898: 3 AC 0...760V 40...1000Hz
VSG1
VSG1
L(+)
L(+)
L(-)
L(-)
PE
RN5897/320
X1
External combined
test/reset button
VSG2
VSG2
X2 11PE1 12PE2 14 21 22 24
M12116
*2)
A1(+) A2
UH
*1)
L+
L-
UN
L1(+) L2(-)
Setting of type of network:
DC
External coupling device:
ON
RL5898
RP5898
Ungrounded DC network
RL5898: DC 0...550V
RP5898: DC 0...1100V
L1
L2
VSG1
VSG1
L1(+)
L(+)
L(+)
L(-)
L(-)
PE
RN5897/320
X1
External combined
test/reset button
VSG2
VSG2
L2(-)
X2 11PE1 12PE2 14 21 22 24
M12113
*2)
A1(+) A2
UH
*1)
UN
Setting of type of network:
DC
External coupling device:
ON
RL5898
RP5898
Single phase mains, isolated from earth
RL5898: AC 0...440V 40...1000Hz
RP5898: AC 0...760V 40...1000Hz
E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen
dold-relays
@dold.com • www.dold.com
• Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356
This manual suits for next models
1
Table of contents
Other DOLD Measuring Instrument manuals

DOLD
DOLD SAFEMASTER S UH 6932 User manual

DOLD
DOLD BH 5922 User manual

DOLD
DOLD RN 5897/240 User manual

DOLD
DOLD VARIMETER RCM IL 5882 User manual

DOLD
DOLD SAFEMASTER S LH 5946 User manual

DOLD
DOLD IP 5883 User manual

DOLD
DOLD SAFEMASTER S UH 5947 User manual

DOLD
DOLD VARIMETER IMD RN 5897/300 User manual

DOLD
DOLD VARIMETER RCM User manual

DOLD
DOLD VARIMETER IMD RN 5897/011 User manual