Issue 1 – November 2006 3
INTENDED USE
•For remote indication or recording of gas levels.
•Not for control of counter-measures against risk of explosion. The 4-20mA output
module is not included in the scope of the Regard 3900 ATEX EC-type
examination.
The module must be mounted within the Regard 3900 control unit enclosure. Up to
four modules can be installed if there is space in the enclosure.
•Do not mount the module outside the 3900 enclosure.
•Do not extend the 3900 ribbon cable or use a longer ribbon cable, in order to
install output modules remote from the input module(s).
The module can be used in Regard 3910 systems. Do not exceed 2m ribbon cable
length.
The Regard 3900 4-20mA output module will not work with Regard 3800.
DESCRIPTION
The module has eight outputs, electrically isolated from the Regard 3900 system.
Each output is a current source and will only work when connected to a passive load.
Each output has two terminals:
+ output
– module 0V
The module’s 0V is isolated from the Regard 3900 system 0V.
Each output supplies a 4..20mA signal proportional to the gas level for its
corresponding input channel. The module’s outputs correspond to channels 1-8 or
channels 9-16 of the Regard 3900 system, depending on the position of the
Channels link on the 4-20mA output module.
The output of inactive channels is 0mA.