DSE DSE705 User manual

COMPLEX SOLUTIONS
MADE SIMPLE
DEEP SEA ELECTRONICS PLC
DSE705
ATS CONTROL MODULE
OPERATING MANUAL

705 ATS controller operators manual
- 2 - 057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR
Deep Sea Electronics Plc
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND
Sales Tel: +44 (0) 1723 890099
Sales Fax: +44 (0) 1723 893303
E-mail: [email protected]
Website: www.deepseaplc.com
DSE Model 704 Control System Operators Manual
© Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying
or storing in any medium by electronic means or other) without the written permission of the copyright holder
except in accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be
addressed to Deep Sea Electronics Plc at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.

705 ATS controller operators manual
057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR - 3 -
TABLE OF CONTENTS
1 INTRODUCTION...................................................................................4
2 DESCRIPTION OF OPERATION..........................................................4
2.1MANUAL RUN ON LOAD.................................................................................4
2.2MANUAL RUN OFF LOAD...............................................................................4
2.3AUTOMATIC MODE OF OPERATION.............................................................5
3 CONFIGURATION INSTRUCTIONS.....................................................6
4 CONFIGURATION TABLES.................................................................7
5 TERMINAL DESCRIPTION................................................................... 9
6 SPECIFICATION.................................................................................10
7 SOLID STATE OUTPUTS...................................................................11
7.1TYPICAL CONNECTIONS..............................................................................11
8 DIMENSIONS......................................................................................12
9 TYPICAL CONNECTIONS..................................................................12

705 ATS controller operators manual
- 4 - 057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR
1 INTRODUCTION
The 705 is a configurable Automatic Transfer Switch control module, and is designed to work in
conjunction with generator control modules that will accept a remote start input. It monitors the
incoming AC mains supply (1 or 3 phases) for under voltage. If the voltage falls out of limits the
module will issue a start command to the generating set controller. Once the set is available and
producing an output within limits the ATS module will control the transfer devices and switch the
load from the mains to the generating set. Should the mains supply return to within limits the
module will command a return to the mains supply and shut down the generator after a suitable
cooling run. Various timing sequences are used to prevent nuisance starting and supply breaks.
Configuration is via the front panel. No other equipment such as a computer or programming lead
is required.
2 DESCRIPTION OF OPERATION
2.1 MANUAL RUN ON LOAD
To initiate a start sequence in Manual Run On Load, press the pushbutton, and the start
sequence is initiated.
The start/run output is activated.
Once the unit detects the alternator frequency of 45Hz, the Warm Up timer is initiated, allowing the
engine to stabilise before accepting the load.
The load will be transferred to the generator.
The module will continue to run in this mode until another mode is selected.
If the generator should fail and the mains (utility) are available, the load is transferred back to the
mains (utility).
NOTE: - If at any time the Close To Neutral Position input is activated, the switching
device that is closed will be opened. (Load shedding). The switching device will not be re-
closed until this input is removed. All other operations are unaffected.
2.2 MANUAL RUN OFF LOAD
To initiate a start sequence in Manual Run Off Load, press the pushbutton, and the start
sequence is initiated.
The start/run output is activated.
The generator will be run off load and no further action is taken.
If during this time the mains (utility) should fail, the load will be transferred to the generator.
However, the unit will NOT return the load to the mains (utility). The load will stay with the
generator until another mode is selected.
NOTE: - If at any time the Close To Neutral Position input is activated, the switching
device that is closed will be opened. (Load shedding). The switching device will not be re-
closed until this input is removed. All other operations are unaffected.

705 ATS controller operators manual
057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR - 5 -
2.3 AUTOMATIC MODE OF OPERATION
This mode is activated by pressing the pushbutton. An LED indicator beside the button
confirms this action.
Whether the start sequence is initiated by mains (utility) failure, or by remote start input, the
following sequence id followed:
To allow for short term mains supply transient conditions or false remote start signals, the Mains
Fail Delay timer is initiated. After this delay the start/Run output is activated.
Once the unit detects the alternator frequency of 45Hz, the Warm Up timer is initiated, allowing the
engine to stabilise before accepting the load.
If the remote start is being used and has been configured to Remote start is on load, or the mains
has failed, the load will be transferred to the generator.
On the return of the mains supply, (or removal of the Remote Start signal if the set was started by
remote signal), the Mains Return delay timer is initiated. Once it has timed out, the load is
transferred back to the mains (utility). The Cooling timer is then initiated, allowing the engine a
cooling down period off load before shutting down. Once the Cooling timer expires the Start/Run
output is de-activated.
If the mains should fail (or a Remote Start signal is re-activated) whilst the generator is Cooling
down, the load will be immediately transferred to the generator.
If the generator should fail, i.e. frequency falls below 20Hz the unit will switch back to the mains,
even if the mains is not available.
NOTE: - If at any time the Close To Neutral Position input is activated, the switching
device that is closed will be opened. (Load shedding). The switching device will not be re-
closed until this input is removed. All other operations are unaffected.

705 ATS controller operators manual
- 6 - 057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR
3 CONFIGURATION INSTRUCTIONS
♦With the unit in Auto mode, Configuration Mode is selected by operation of a small
switch on the rear, left-hand edge of the PCB. This is partially hidden to prevent accidental
operation.
♦Once Configuration Mode is selected, the ‘Auto’ LED will commence rapid flashing, and all
normal operation is suspended.
♦The Run On Load pushbutton can be used to select the LED ‘code’ that corresponds to
the required function. The 5 left-hand LED’s will form the code. See configuration table over
leaf.
♦The Run Off Load pushbutton will allow the user to change the associated value. The 3
right-hand LED’s inform the user of the current setting for the chosen function. See
configuration table over leaf.
♦When the required parameters are displayed, pressing the Auto button will save
the new setting, and the process is repeated for each function change.
♦When configuration is complete, the Configuration Mode Selector Switch should be returned
to the ‘Normal’ position.
Parameter Value
Normal
Configuration

705 ATS controller operators manual
057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR - 7 -
4 CONFIGURATION TABLES
FUNCTIONS AND CONFIGURATION TABLE
Function {{{{{{{{Value (Default in Bold)
Start Delay {{{O{{{{0 Seconds
{{O5 Seconds
{O{10 Seconds
{O O 15 Seconds
O{{20 Seconds
O{O30 Seconds
O O {60 Seconds
OOO180 Seconds
Used to give a delay between mains failure and starting the engine. Used to prevent the generating from starting on
brown outs (dips) or short mains outages.
Mains Return Delay {{{O O {{{0 Seconds
{{O5 Seconds
{O{10 Seconds
{O O 15 Seconds
O{{20 Seconds
O{O30 Seconds
O O {60 Seconds
OOO180 Seconds
Used to give a delay between the mains returning and the system switching the load back to the mains. Used to ensure
that the mains is steady before this action is executed.
Warm Up Timer {{O{O{{{0 Seconds
{{O5 Seconds
{O{10 Seconds
{O O 15 Seconds
O{{20 Seconds
O{O30 Seconds
O O {60 Seconds
OOO180 Seconds
Delay between the engine being available for use, and the closure of the generator load-switching device to allow time
for the engine to warm before being loaded.
Cooling Timer {{OO{{{{0 Seconds
{{O5 Seconds
{O{10 Seconds
{O O 15 Seconds
O{{20 Seconds
O{O30 Seconds
O O {60 Seconds
OOO180 Seconds
Delay between opening the generator load-switching device and stopping the engine to allow time for the engine to
cool down before being stopped. This is particularly useful when used in conjunction with turbo-charged engines.
Remote Start Input
Type {OOO{{{{Remote Start
{{OSimulate Mains
Programmable input can be configured to one of the following.
♦Remote start – If the input is active the generator will be started, and stopped if the input is deactive. Mains fail is
allways active.
♦Simulated mains – If the input is active the generator will not start in the event of a mains failure. E.G. if the
generator is supporting a non 24 hour operation, a 24 hour timer can be used to prevent a mains failure from
starting the generator and taking load.

705 ATS controller operators manual
- 8 - 057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR
FUNCTIONS AND CONFIGURATION TABLE
Function {{{{{{{{Value (Default in Bold)
Remote Start
Function {OOO O {{{Remote Start Is Off load
{{ORemote Start Is On
Load
The remote start input can be configured to one of the following.
♦Remote start is off load – The generator will start and run off load when the remote start input is active.
♦Remote start is on load – The generator will start, and the load transferred to the generator when the remote start
is active.
Auxiliary Output 1
Function
O{{O{{{{Not used
{{OMains Failure
{O{Generator Available
{OOGenerator On Load
O{{Mains On Load
O{OSystem in Auto
OO{Close to neutral Position
Programmable output can be configured to one of the following.
♦Mains Failure. - The output is energised after the delay mains fail timer has elapsed and stays energised until the
delay mains return timer has elapsed.
♦Generator Available. - The output is energised after the warm up timer has elapsed and generator voltage is
sensed.
♦Generator On Load. - The output is energised when the unit has switched over to generator supply.
♦Mains On Load. - The output is energised when the unit has switched over to mains supply.
♦System in auto. - The output is energised when the unit is in automatic mode.
♦Close to Neutral Position. - The output is energised when the close to neutral position input is active.
Auxiliary Output 2
Function
O{{OO{{{Not used
{{OMains Failure
{O{Generator Available
{OOGenerator On Load
O{{Mains On Load
O{OSystem in Auto
OO{Close to neutral Position
Programmable output can be configured to one of the following.
♦Mains Failure. - The output is energised after the delay mains fail timer has elapsed and stays energised until the
delay mains return timer has elapsed.
♦Generator Available. - The output is energised after the warm up timer has elapsed and generator voltage is
sensed.
♦Generator On Load. - The output is energised when the unit has switched over to generator supply.
♦Mains On Load. - The output is energised when the unit has switched over to mains supply.
♦System in auto. - The output is energised when the unit is in automatic mode.
♦Close to Neutral Position. - The output is energised when the close to neutral position input is active.
Mains Under
Voltage
(Trip / Return)
O{O{{{{{60V / 70V
{{O70V / 80V
{O{80V / 90V
{OO90V / 100V
O{{120V / 140V
O{O140V / 160V
OO{160V / 180V
OOO180V /200V
If for example 180V/200V is selected the generator will be started and the load transferred if any phase falls below
180V with respect to the neutral for the duration of the delay start timer. The load will be transferred back to mains
when the mains voltage returns to 200V or higher for the duration of the mains return timer. (The system must be in
Auto)

705 ATS controller operators manual
057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR - 9 -
5 TERMINAL DESCRIPTION
PIN
No DESCRIPTION CABLE
SIZE NOTES
1 DC Plant Supply Input
(-ve) 1.0mm Connected to plant battery negative
2 DC Plant Supply Input
(+ve) 1.0mm Connected to plant battery positive
(Recommended Fuse 2A)
3 Remote Start Output 1.0mm Remote Start Input to all DSE modules.
4 Auxiliary Output relay 1 1.0mm Configurable output.
5 Auxiliary Output relay 2 1.0mm Configurable output.
6 NOT USED DO NOT CONNECT
7 NOT USED DO NOT CONNECT
8 NOT USED DO NOT CONNECT
9 NOT USED DO NOT CONNECT
10 NOT USED DO NOT CONNECT
11 Close To Neutral. (Mains &
Generator Off Load) 0.5mm Switch to negative.
12 Remote Start Input 0.5mm Switch to negative.
13 Mains loading Relay
Normally Open contact 1.0mm Used to close the mains
contactor / breaker
14 Generator loading Relay
Normally Open contact 1.0mm Used to close the generator
contactor / breaker
15 Functional Earth 1.0mm Connect to a good clean earth point
16 Mains L1
Voltage Monitoring Input 1.0mm Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
17 Mains L2
Voltage Monitoring Input 1.0mm Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
18 Mains L3
Voltage Monitoring Input 1.0mm Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
19 Mains N
Voltage Monitoring Input 1.0mm Connect to Mains N supply (AC)
20 Alternator Input L1 1.0mm Do not connect if not used. (2A Fuse)
21 Alternator Input N 1.0mm Do not connect if not used.
NOTE: - For single-phase mains monitoring the neutral should be connected to terminal
19, L1 should be connected to terminals 16,17 and 18.
NOTE: - For two phase mains monitoring the L2 should be connected to terminal 19, L1
should be connected to terminals 16,17 and 18. The voltage between the two phases must
not exceed 305 Volts.
NOTE: - All the outputs are solid state, rated at 1.2 Amps 8 Volts to 35 Volts DC, and
switch to battery negative when active.

705 ATS controller operators manual
- 10 - 057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR
6 SPECIFICATION
DC Supply: 8 Volts to 35 Volts DC Continuous.
Cranking Dropouts: Able to survive 0 Volts for 50 mS, providing supply was at
least 10 V before dropout and supply recovers to 5 Volts.
This is achieved without the need for internal batteries.
Max. Current: Operating 50mA
Standby 10mA
Alternator Input Range: 75 Volts (ph-N) to 277 Volts (ph-N) AC (+20%)
Mains Input Range 15 – 277 Volts (ph-N) AC (+20%)
Alternator Input Frequency: 50 - 60 Hz at rated engine speed
(Minimum: 75V AC Ph-N)
Generator available 45Hz
Generator failed 20Hz
Mains Input Frequency 50 – 60 Hz
Start Output: 1.2 Amp DC at supply voltage.
Fuel Output: 1.2 Amp DC at supply voltage.
Auxiliary Outputs: 1.2 Amp DC at supply voltage.
Dimensions: 125mm x 165mm x 28 mm
Charge Fail: 12 Volts = 8 Volts CF 24 Volts = 16 Volts CF
Operating Temperature Range: -30°C to + 700C
Applicable Standards
Compliant with BS EN 60950 Low Voltage Directive
Compliant with BS EN 50081-2: 1992 EMC Directive
Compliant with BS EN 61000-6-4: 2000 EMC Directive
Compliance to European Legislation
Registered Component for USA & Canada
Deep Sea Electronics plc reserve the right to change specification without notice.

705 ATS controller operators manual
057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR - 11 -
7 SOLID STATE OUTPUTS
DSE’s utilisation of Solid State Outputs gives many advantages, the main points being:
♦No Moving Parts
♦Fully Overload / Short Circuit Protected.
♦Smaller dimensions hence lighter, thinner and cheaper than conventional relays.
♦Less power required making them far more reliable.
The main difference from conventional outputs is that solid state outputs switch to negative (–ve)
when active. This type of output is normally used with an automotive or plug in relay.
7.1 TYPICAL CONNECTIONS
Battery positive
Solid state output from DSE
module E.g. Terminal 4 of 705 –
A
uxiliary Output 1
E.g. System in Auto
Lamp (Positive)
* Observe polarity when relays
fitted with integral diodes!
*
A
D
BC
A
B
C
D
Solid State Output
from DSE Module Pin Automotive
relay Pin 8 Pin Plug in relay Function
3 86 7 Fuel Output
85 2 To Positive supply via fuse
30 1 To Positive supply via fuse
87 3 To Fuel Solenoid
Example of relay pins connected to DSE solid state output to drive a fuel solenoid.
See overleaf for overall typical wiring diagram
NOTE: - The Close Mains Relay should be NORMALLY CLOSED when de-energised for fail
safe reasons. Should the DC supply fail the mains will always be available. The output from the
DSE solid state output when energised will OPEN the relay therefore isolating the mains supply.

705 ATS controller operators manual
- 12 - 057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR
8 DIMENSIONS
Dimensions:
165mm x 125mm x 29mm
(6.5” x 4.9” x 1.2”)
Panel cut-out:
149mm x 109mm
(5.9” x 4.3”)
Mounting Method:
4 x 4.2mm diameter holes suitable for M4
screws.
9 TYPICAL CONNECTIONS
NOTES :
The remote start inputs of all DSE modules can be connected directly to the start/run output (terminal 3)
of the 705 ATS controller, providing that the DC supplies are common to each module.
Wiring of remote start relay above is shown for connection to an engine controller requiring a battery negative signal
to start the set (such as DSE controllers). Modules with different input requirements may need alternative wiring details.
If in doubt, consult the manufacturer of your engine control unit.
F 2A
SSOSSOSSO
SSO = Solid state outputs
= External 'Automotive' or 'Plug-in' type relays
3
1 2 4 5 7
2021
Auxiliary Outputs
+
8 9 11
10 12
+
Battery
F2A
+ +
Start/Run output
N
L1
L2
L3 Alternator Output
Load
Mechanical Interlock
N
L1
L2
L3
Mains / Utility supply
14
SSO
Close Gen output
+
GM
Electrical Interlock
13
SSO
Close mains output
FUSES 2A
Remote Start
Normally closedNormally open
16 17 18 19
Close mains relayClose gen relay
+
*
NOTE
* Close mains relay must be normally closed
to ensure fail safe operation
Remote start relay
(see note)
Not connected
Not connected
Not connected
Not connected
Close to neutral pos'n
To'remote start' input of
engine controller (see note)
15
6
Not connected
Terminals suitable for 22-16 awg (0.6mm
2
-1.3mm
2
)field wiring
Tightening Torque = 0.8N-m (7lb-in)

705 ATS controller operators manual
057-043 705 Operating Instructions Issue 1.1 18/06/2007 JR - 13 -
<< This page is intentionally blank >>
Table of contents
Other DSE Controllers manuals
Popular Controllers manuals by other brands

Show Tec
Show Tec Lite-12 user guide

Kieback&Peter
Kieback&Peter MD15-FTL-315 user manual

Burger & Brown
Burger & Brown SMARTFLOW WDT2-S3-P3 operating instructions

Light Symphony
Light Symphony LS30505SCC instructions

Procom
Procom ECON-A operating instructions

Keyautomation
Keyautomation 900CT-101 instruction manual