DSE DSE4420 MKII Service manual

OUTPUT SOURCE LIST
0 Not used
1 RESERVED 3
2 Arm safety on alarms
3 Audible alarm
4 Battery over volts warning
5 Battery under volts warning
6 Can ECU data fail
7 Can ECU
error
8 Can ECU fail
9 Can ECU
power
10 Can ECU stop
11 Charge alternator shutdown
12 Charge alternator warning
13 Close gen output
14 Close gen output pulse
15 Close mains output
16 Close mains output pulse
17 Combined mains failure
18 Common alarm
19
Common electrical trip
20 Common shutdown
21 Common warning
22 RESERVED
23 RESERVED
24 RESERVED
25 RESERVED
26 RESERVED
27 RESERVED
28 RESERVED
29 Emergency stop
30 Energise to stop
31 RESERVED
32 RESERVED
33
Fuel relay
34 Gas choke on
35 Gas ignition
36 Generator available
37 Generator over voltage shutdown
38 RESERVED
39 RESERVED
40 Loss of magnetic pickup signal
41
Low fuel level
42 RESERVED
43 RESERVED
44 RESERVED
45 RESERVED
46 RESERVED
47 Open gen output
48 Open gen output pulse
49 Open mains output
50 Open mains output pulse
51 RESERVED
52 RESERVED
53
Preheat duringpreheat timer
54
Preheat until end of crank
55
Preheat until end of safety timer
56
Preheat until end of warming timer
57 Smoke limiting
58
Start relay
59 RESERVED
60 RESERVED
61 Waiting for manual restore
62 Flexible sender High Shutdown
63 Flexible sender High Warning
64 Flexible sender Low Warning
65 Flexible sender Low Shutdown
44xx
–
02 (CAN option) only
44xx
–
01 (Magnetic pickup option) only
TYPICAL WIRING DIAGRAM
053-079 ISS 5
D E E P S E A E L E C T R O N I C S
DSE4420 INSTALLATION INSTRUCTIONS
This instruction sheet is for DSE4420 MKII controllers only.
For DSE4420 controllers below version 2 use DSE publication
053-056
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR
Ensure the engine is at rest and the module is in stop mode by
pressing the stop/reset button.
Press the stop/reset and down buttons simultaneously.
The configuration icon is displayed, along with the first
configurable parameter.
EDITING A PARAMETER
Press to select the required ‘page’ as detailed in the
configuration tables.
Press (+) to select the next parameter or (-) to select the
previous parameter within the current page.
When viewing the parameter to be changed, press the button.
The value begins to flash.
Press (+) or (-) to adjust the value to the required setting.
Press the save the current value, the value ceases flashing.
Press and hold the button to exit the editor, the configuration
icon will be removed from the display.
NOTE: - pressing and holding the + / - buttons will give auto-
repeat functionality. Large values can be changed quicker by holding
the buttons for a prolonged period. For instance large timers
increment in 1 second steps to 1 minute, then in 30 second steps to
1 hour, then in 30 minute steps.
DIMENSIONS AND MOUNTING
For flat surface mounting in a Type 1 enclosure to meet UL
requirements.
DIMENSIONS
180mm x 116mm x 42mm
(7.1” x 4.6” x 1.7”)
PANEL CUTOUT
154mm x 98mm
(6” x 3.9”)
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
Web: www.deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) :
Tel: 1 866 636 9703
Web: www.deepseausa.com
DSE4420
http://bestgenerator.spb.ru/?page_id=6765

CONFIGURATION PARAMETERS
–
MODULE (PAGE 1)
101 Contrast 000 (%) 106 Protected start
enable On (1), off (0)
102 Fast loading enabled On (1), o
ff (0)
107
RESERVED
103 RESERVED 108 Event log display
format On (1), off (0)
104 Lamp test at startup On (1), o
ff (0)
109
Start in auto On (1), o
ff (0)
105 Power save mode
enable On (1), off (0) 110
Diagnostic Trouble
Code string
(english only)
enable
On (1), off (0)
CONFIGURATION PARAMETERS
–
APPLICATION (PAGE 2) (CAN VERSION MODULE ONLY)
201
Alternate engine speed
On (1), off (0)
203 Can ECU
data fail action
0 (action)
202 Can ECU data fail enable
On (1), off (0)
204 Can ECU
data fail delay
0:00
CONFIGURATION PARAMETERS
–
INPUTS (PAGE 3)
301
Low oil pressure enable
On (1), off (0)
302
Low oil pressure trip
0.00 bar
303
High engine temperature trip
00 deg c
304
Digital input
A
source
0 (input source)
305
Digital input A
polarity
0 (polarity)
306
Digital input
A
action (if source = user config) 0 (action)
307
Digital input
A
arming (if source = user config) 0 (arming)
308
Digital input
A
activation delay (if source = user config) 0:00
309
Digital input B source
0 (input source)
310
Digital input B
polarity
0 (polarity)
311
Digital input B action (if source = user config) 0 (action)
312
Digital input B arming (if source = user config) 0 (arming)
313
Digital input B activation delay (if source = user config) 0:00
314
Digital input C
source 0
(input source)
315
Digital input C
polarity
0 (polarity)
316
Digital input C
action (if source = user config)
0 (action)
317
Digital input C
arming (if source = user config)
0 (arming)
318
Digital input C
activation delay (if source = user config)
0:00
319
Digital input D
source
0 (input source)
320
Digital input D
polarity
0 (polarity)
321
Digital input D
action (if source = user config)
0 (action)
322
Digital input D
arming (if source = user config)
0 (arming)
323
Digital input D
activation delay (if source = user config)
0:00
324
Analogue input A sensor type
0 (sensor type)
325
Analogue input A sensor selection (pressure senor l
ist)
0 (pressure sensor)
326
Analogue input
A
(set as digtal) source (oil pressure sender) 0
(input source)
327
Analogue input
A
(set as digital) polarity
0 (polarity)
328
Analogue input
A
(set as digital) action (if source = user config)
0 (action)
329
Analogue input
A
(set as digital) arming (if source = user config) 0 (arming)
330
Analogue input
A
(set as digital) activation delay
(if source = user config) 0:00
331
Analogue input B sensor type
0 (sensor type)
332
Analogue input B sensor selection (temperature
senor list)
0 (temp
sensor)
333
Analogue input B (set as digital) source (temperature sender)
0 (input source)
334
Analogue input B polarity (set as digital)
0 (polarity)
335
Analogue input B
(set as digital) action (if source = user config)
0 (action)
336
Analogue input B (set as digital) arming
(if source = user config)
0 (arming)
337
Analogue input B (set as digital) activation delay
(if source = user config) 0:00
338
Analogue input C sensor type
0 (sensor type)
339
Analogue input C sensor selection (pressure /
temp / percentage)
0 (sensor)
340
Analogue input C (set as digital) source (flexible sender)
0 (input source)
341
Analogue input C
(set as digital) polarity
0 (polarity)
342
Analogue input C (set as digital) action (if source = user config) 0 (action)
343
Analogue input C (set as digital) arming(if source = user config) 0 (arming)
344
Analogue input C (set as digital) activation delay
(if source = user config) 0:00
345
Oil pressure sender open circuit alarm
On (1), off (0)
346
Temperature sender open circuit alarm
On (1), off (0)
CONFIGURATION PARAMETERS
–
OUTPUTS (PAGE 4)
401
Digital output
A
source
0 (output source)
402
Digital output
A
polarity
0 (output source polarity)
403
Digital output B source
0 (output
source)
404
Digital output B
polarity
0 (output source polarity)
405
Digital output C
source
0 (output source)
406
Digital output C
polarity
0 (output source polarity)
407
Digital output D
source
0 (output source)
408
Digital output D
polarity
0 (output source polarity)
409
Digital output E source
0 (output source)
410
Digital output E polarity
0 (output source polarity)
411
Digital output F source
0 (output source)
412
Digital output F polarity
0 (output source polarity)
CONFIGURATION PARAMETERS
–
TIMERS (PAGE 5)
501
Mains transient delay
507 Smoke limiting off
513
Failed to stop delay
502
Start delay
508 Safety on delay
514
Generator transient delay
503
Preheat timer
509 Warm up time 515
Power save mode delay
504 Crank time 510 Return delay 516
Transfer time
505 Crank rest time 511 Cooling time 517
Breaker trip pulse
506 Smoke limiting 512 Ets solenoid hold
518
Breaker close pulse
= 44xx – 02 (CAN) option only = 44xx –01 (Magnetic pickup) option only
CONFIGURATION PARAMETERS
–
GENERATOR (PAGE 6)
601
Alternator fitted
On (1), off (0)
609 Under frequency enable
On (1), off (0)
602 Alternator poles 0
610 Under frequnecy
level
0.0 H
z
603 Reserved enable
611 Loading freq
unecy
0.0 H
z
604 Reserved
612 Nominal frequnecy
0.0 H
z
605 Under voltage enabled
On (1), off (0)
613 Over frequecny enable
On (1), off (0)
606 Under v
oltage level
0 V
614 Over frequency
trip
0.0 H
z
607 Loading voltage
0 V
615 AC system AC system
608 Over voltage level
0 V
(see table below)
CONFIGURATION PARAMETERS
–
MAINS (PAGE 7)
701 AC system AC system
(see
table)
709
Over voltage level 0 V
702
Mains failure detection
On (1), off (0)
710
Under frequency enable
On (1), off (0)
703 Immediate mains dropout
On (1), off (0)
711
Under frequency level
0.0 H
z
704 Under voltage enable On (1), off (0
)
712
Under frequency return 0.0 Hz
705 U
nder voltage level
0
V
0
713
Over frequency enable
On (1), off (0)
706 Under voltage return 0
V
714
Over frequency return
0 H
z
707 Over voltage enable On (1), off (0
)
715
Over frequency level 0.0 H
z
708 Over voltage return 0
V
CONFIGURATION PARAMETERS
–
ENGINE (Page 8)
801 Magnetic pickup fitted On (1), off (0) 818 Low battery volts trip 00.0 V
802 Flywheel teeth 000 819 Low battery volts return 00.0 V
803 Start Attempts 0 820
Low battery volts delay
0:00:00
804 RESERVED 821 High battery volts
enable On (1),
off (0)
805 RESERVED 822 High battery volts
return 00.0 V
806
Gas choke timer
(Gas engine only) 0:00 823 High battery volts
warning 00.0 V
807
Gas on delay
(Gas engine only) 0:00 824 High battery volts
warning delay 00.0 V
808
Gas ignition off delay
(Gas engine only) 0:00 825 Charge alt shutdown
enable On (1),
off (0)
809 Crank disconnect on Oil
pressure enable On (1), off (0) 826 Charge alt shutdown
trip 00.0 V
810 Check oil pressure prior
to starting On (1), off (0) 827 Charge alt shutdown
trip delay 0:00:00
811 Crank disconnect on Oil
threshold 0.00 Bar 828 Charge alt warning trip
enable On (1),
off (0)
812 Crank disconnect on
frequency 0.0Hz 829 Charge alt warning trip 00.0 V
813 Crank disconnect on
Engine Speed 000 rpm 830 Charge alt warning trip
delay 0:00:00
814 Under speed enable On (1), off (0) 831
Low battery star
t
Arming On (1),
off (0)
815 Under speed trip 0000 rpm 832
Low battery start
Threshold 00.0 V
816 Over speed trip 0000 rpm 833
Low battery start
Delay 0:00:00
817 Low battery volts
enable On (1), off (0) 834
Low battery start
Run time 0:00:00
CONFIGURATION PARAMETERS
–
ALTERNATIVE CONFIGURATION (PAGE 9)
901
Alt config
–
Default configuration
Main(1), alternative(0)
902
Alt config
–
Enable configuration
On (1), off (0)
903
Alt config
- Al
ternative engine speed
On (1), off (0)
904
Alt
config - Under voltage shutdown enable
On (1), off (0)
905
Alt config
- Under voltage trip
On (1), off (0)
906
Alt config
- Loading voltage
0 v
907
Alt config
- Over voltage trip level 0 v
908
Alt config
- Under frequency enabled
On (1), off (0)
909
Alt config
- Under frequency trip level
0.0 hz
910
Alt config
- Loading frequency
0.0 hz
911
Alt config
- Nominal frequency
0.0 hz
912
Alt config
- Over frequency enabled
On (1), off (0)
913
Alt config
- Over frequency trip level
0.0 hz
914
Alt config
-
AC system
0 (AC system)
915
Alt config
- Mains failure detection
On (1), off (0)
916
Alt config
- Immediate mains dropout
On (1), off (0)
917
Alt config
- Mains under volt enable
On (1), off (0)
918
Alt config
- Mains under volt trip
0 V
919
Alt config
- Mains under volt return
0 V
920
Alt config
- Mains over volt enable
On (1), off (0)
921
Alt config
- Mains over volt return
0 V
922
Alt config
- Mains over volt trip
0 V
923
Alt config
- Mains under frequency enable
On (1),
off (0)
924
Alt config
- Mains under frequency trip
0.0 Hz
925 Alt config -
Mains under frequency return
0.0 Hz
926 Alt config -
Mains over frequency enable
On (1), off (0)
927 Alt config -
Mains over frequency return
0.0 Hz
928 Alt config
-
Mains over frequency trip
0.0 Hz
929 Alt config
–
Alternative
under speed shutdown enable
On (1), off (0)
930 Alt config
–
A
lternative under speed shutdown trip
0000 RPM
931 Alt config
–
A
lternative
over
speed shutdown trip
0000 RPM
Output source list overleaf...
CONFIGURATION PARAMETERS
–
FLEXIBLE SENSOR (PAGE 10)
1001
Flexible sensor alarm arming 0 (Arming)
1002
Flexible sensor - Low
alarm
enable
0 (Action)
1003
Flexible sensor - Low
alarm
trip (units depend
upon
sensor type)
0 % /
0.00 bar
/ 0 °C
1004
Flexible sensor - High
alarm
enable
0 (Action)
1005
Flexible sensor - High
alarm
trip (units depend
upon sensor type)
0 % /
0.00 bar
/ 0 °C
1006
Flexible sensor - Low warning
enable
On (1), Off (0)
1007
Flexible sensor - Low warning
trip (units depend upon
sensor type)
0 % /
0.00 bar
/ 0 °C
1008
Flexible sensor
–
High warning enable
On (1), Off (0)
1009
Flexible sensor
–
High warning trip (units depend
upon
sensor type)
0 % /
0.00 bar
/ 0 °C
CONFIGURATION PARAMETERS
–
SCHEDULER (Page 11)
1101
Enable scheduler On (1), o
ff (0)
1104
Day
0 (Day, 1
=Monday)
1102
On or off load
On (1), o
ff (0)
1105 Duration 0:00:00
1103
Start time 0:00:00
CONFIGURATION PARAMETERS
–
TIME AND DAY (Page 12)
1201
Time of day
0:00 1202
Day of week
0 (Day, 1
=Monday)
Parameters with multiple choices use the following identification tables for the parameter values :
INPUT SOURCE LIST
0 User Configured 8 Emergency Stop
16 Oil Pressure Switch
1 Alarm Mute
9
External Panel Lock
17 Remote
Start Off Load
2 Alarm Reset 10
RESERVED 18
Remote Start On Load
3
Alternative Configuration
11
Generator load inhibit
19 Simulate mains available
4 Auto restor inhibit
12
Lamp Test
20 Smoke Limiting
5
Auto start inhibit
13
Low Fuel Level Switch
21 Close Gen / Open Mains
6 Auxilary mains fail
14
RESERVED 22 Open Gen / Close Mains
7 Coolant Temperature Switch 15
Mains load inhibt
INPUT ACTION LIST
INPUT ARMING LIST
Index
Action
Index Arming
0 Electrical Trip
0 Always
1 Shutdown
1 From Safety On
2 Warning
2 From Starting
3
Never
INPUT POLARITY LIST
Index
Action
OUTPUT POLARITY LIST
0 Close to Activate
Index Arming
1 Open to Activate
0 Energise
1 De-energise
CAN DATA FAIL ACTION
Index
Action
CAN DATA FAIL ARMING
0 None
Index Arming
1 Shutdown
0 From Safety On
2 Warning always latched
1 From Starting
FLEXIBLE SENSOR ALARM ACTION LIST
AC SYSTEM
Index
Action
Index Type
0 None
0 2 phase 3 wire (L1-
L2)
1 Shutdown
1 2 phase 3 wire (L1-
L3)
2 Electrical Trip
2 3 phase 3 wire
3 3 phase 4 wire
FLEXIBLE SENSOR TYPE
4
3 phase 4 wire (Delta)
Index Type
5 Single phase 2 wire
0 None
1 Digital Input
2
Percentage sensor
3
Pressure sensor
4
Temperature sensor
SENSOR
SELECTIONS
FOR PERCENTAGE
SENSOR
SELECTIONS FOR
OIL PRESSURE
SENSOR SELECTIONS FOR
COOLANT TEMPERATURE
0
Not used
0 Not used
0 Not used
1
D
ig closed for alarm
1
Dig closed for alarm
1
Dig closed for alarm
2
Dig open for alarm
2 Dig open for
alarm
2
Dig open for alarm
3
VDO ohm (10-
180)
3 VDO
5 bar
3 VDO
120 °C
4
VDO tube (90-
0)
4 VDO
10 bar
4 Datacon high
5
Us ohm (240-
33)
5
Datacon 5 bar
5 Datacon low
6
GM
ohm (0-
90)
6
Datacon 10 bar
6 Murphy
7
GM
ohm (0-
30)
7
Datacon 7 bar
7 Cummins
8
Ford (73
-
10)
8
Murphy 7 bar
8 P
T
100
9
User defined
9 CMB812
9 Veglia
10 Veglia
10 Beru
Dig = Digital Switch
11 User defined
11 User defined
http://bestgenerator.spb.ru/?page_id=6765
Other DSE Controllers manuals
Popular Controllers manuals by other brands

ProMinent
ProMinent DCM 5 Series quick start guide

NovaStar
NovaStar C1 user manual

Beijer Electronics
Beijer Electronics EXTER K20m installation manual

Siemens
Siemens OZS164 series installation instructions

IRIS
IRIS Energy Smart ES2H40HD045V Installation, operation and troubleshooting instructions

Eurotherm
Eurotherm 7000 Series user manual

Mitsubishi
Mitsubishi MELSEC iQ-R series user manual

Kohzu Precision
Kohzu Precision KOSMOS series user manual

Parker
Parker ACR9000 installation guide

LightProcessor
LightProcessor PARADIME Installation and operating manual

LEGRAND
LEGRAND 0 648 84L quick start guide

Johnson Controls
Johnson Controls Hitachi C4IRK01 Operation manual