Econ 1205 User manual

Installation & Operation Manual
Proven Quality since 1892
ECON storm valves Fig. 1205,1207,1208,1209 www.eriks.com
Rev. 0
Content
1. ERIKS operating companies
2. Product description
3. Requirements for maintenance staff
4. Transport and storage
5. Function
6. Application
7. Installation
8. Maintenance
9. Service and repair
10. Troubleshooting
11. Removal
1. ERIKS operating companies
ECON storm valves are being delivered by several ERIKS operating companies on a worldwide
basis. In this manual these will be referred to as ‘ERIKS’, the individual terms of delivery of the
ERIKS operating company having executed the order are applicable.
2. Product description
The ECON storm valves are designed according to the information in our latest catalogue or see
our website www.eriks.com and should be used in accordance with the applicable pressure-
temperature rating as stated on this website. ECON storm valves are provided with casted
markings according to EN 19. The marking makes the identification of the valve easier and
contains:
- size (DN)
- pressure rating class
- body material marking
- arrow, indicating the medium flow direction
- charge number
- ECON logo
3. Requirements for maintenance staff
The staff assigned to assembly, operating and maintenance tasks should be qualified to carry out
such jobs and in any circumstance, ensure personal safety.
4. Transport and storage
Transport and storage should always be carried out with the discs completely closed and the valve
should be protected against external forces, influence and destruction. The valves should be
stored in an unpolluted space and should also be protected against all atmospheric
circumstances. There should be taken care of the temperature and humidity in the room, in order
to prevent condensate formation.
5. Function
ECON storm valves also known as scupper valves are provided in angle and straight type and
without or with locking device. The storm valves are self-closing valves under the waterline of
ships. Important is their non-return function, allowing the media to be discharged but at the same
time preventing seawater from entering the system.
6. Application
ECON storm valves are used aboard ships for discharge of sanitary pipelines, grey water and
septic tanks and usually places shipside.
The installation designer is responsible for the storm valve selection, suitable for the working
conditions. The valves are unsuitable, without written permission of an ERIKS company, to apply
for hazardous media as referred into Regulation (EC) No 1272/2008.

Installation & Operation Manual
Proven Quality since 1892
ECON storm valves Fig. 1205,1207,1208,1209 www.eriks.com
Rev. 0
7. Installation
During the assembly of the ECON storm valves, the following rules should be observed:
- make sure before an assembly that the valves were not damaged during the transport or
storage.
- make sure that the applied valves are suitable for the working conditions, medium used in
the system and the right system connections, according to pressure and temperature
limits.
- the angle type storm valve Fig.1205 and straight type storm valve Fig.1208 are standard
without locking device. For the storm valve with locking device we have Fig.1207 angle
type and Fig. 1209 straight type. Storm valves can only be installed with the discharge
medium form above.
- by turning the locking device down you can block the disc from getting open, this can be
useful when the ship is in dock or when there is a heavy storm.
- during fitting, the proper flow direction has to be considered.
- the interior of the valve and pipeline must be free from foreign particles.
- the valve should be assembled in the pipeline in closed position, for a correct functioning,
the valve must be stress free mounted between the flanges, supports must be arranged to
prevent any additional stress, caused by the weight of the valve or the pipeline.
- bolted joints on the pipeline must not cause additional stress resulted from excessive
tightening, user shall select proper bolts and gaskets according the working temperature,
working pressure and medium.
- before startup, especially after repairs carried out, flash out the pipeline.
- after installation it is necessary to check the valve operation and tightness of all
connections. A tightness test should be carried out.
Fig. 1205 Fig.1207

Installation & Operation Manual
Proven Quality since 1892
ECON storm valves Fig. 1205,1207,1208,1209 www.eriks.com
Rev. 0
Fig. 1208 Fig.1209
- for operating on distance we can supply a Hydraulic/Pneumatic SOS actuator, see underneath
on the left side Fig.1207X
- afterwards is also available a standard locking device see underneath on the right side
Fig.1207X

Installation & Operation Manual
Proven Quality since 1892
ECON storm valves Fig. 1205,1207,1208,1209 www.eriks.com
Rev. 0
8. Maintenance
Before starting any service jobs, make sure that the medium supply to the pipeline is cut off,
pressure was decreased to ambient pressure, the pipeline is completely cleaned and ventilated
and the plant is cooled down. Always keep safety instructions in mind and take all personal safety
precautions.
During maintenance, the following rules should be observed:
- always keep personal safety precautions in mind and always use appropriate protection
e.g. clothing, masks, gloves etc.
- be alert that the temperature still can be very high or low and can cause burns.
- check the valve on all possible leaking possibilities.
- check if all bolts and nuts, are still fastened.
- check if the discs still open and close in a proper manner.
- the thickness of the body must be checked to ensure safety operation at an interval of at
least three months.
9. Service and repair
All service and repair jobs should be carried out by authorized staff, using suitable tools and user
shall use valve gasket, bolt and nut of the same size and material as the original one.
- weld repair and drilling of the valve is forbidden.
- it is forbidden to replace the bolt, nut or packing when the valve is under pressure.
- tighten the hexagon nut in the therefor standard order.
- after replacement of the gasket, bolts or nuts, it is necessary to check the valve operation
and tightness of all connections. A tightness test should be carried out.
- after installation, the valve should be checked and maintained periodically at least every
3 months, depending on the medium.
10. Troubleshooting
It is essential that the safety regulations are observed when identifying the fault.
Problem
Possible cause
Corrective measures
No flow
Valve is installed in the wrong
way
Arrow of flow direction has to
run in the same direction as the
flow itself
Little flow
Discs do not completely open
Check discs opening function
Piping system clogged
Check piping system
Leakage across valve seat
Discs not properly closed
Check discs opening function
Seat damaged by foreign
particles
Replace the disc gasket or
when necessary replace the
valve
Rattling/banging of the discs
Nominal diameter of the valve in
compliance to the flow rate is too
big.
Choose smaller nominal
diameter
High flow speed
Change the system
After a 90° bend in the pipe
Body broken and leaking
Broken because of freezing
Replace the valve and drain the
water in the winter when the
valve is not used

Installation & Operation Manual
Proven Quality since 1892
ECON storm valves Fig. 1205,1207,1208,1209 www.eriks.com
Rev. 0
11. Removal
All dismantled and rejected valves cannot be disposed with household waste. The valves are
made of materials which can be re-used and should be delivered to designated recycling centers.
General warning:
General note for products which may be used for seawater:
Although our products can be used in seawater systems it should always be noted that, in case of
installation in a piping system made of materials which are frequently used because of their excellent
seawater resistance (e.g. Cunifer), large potential differences may occur possibly causing corrosion
which could permanently damage the proper functioning and integrity of our product.
A combination of different materials should always be mentioned prior to the purchase of our products
in order for us to give the best possible advise on a safe functioning.
This manual suits for next models
3
Other Econ Control Unit manuals
Popular Control Unit manuals by other brands

Küschall
Küschall Mentor manual

LEGRAND
LEGRAND 4 121 71 instructions

Johnson Controls
Johnson Controls Mercury 3 Series Hardware installation

Spirax Sarco
Spirax Sarco M33 ISO Series Installation and maintenance instructions

Honeywell
Honeywell Hometronic HB 05 Mounting and operation instructions

Climax
Climax SCM-2ZW manual