Technical Support Line +44 (0) 2392 739412 TR2 / TR4
© 2009 Elmdene International Ltd PAK200481_01A May 2009
Environmental
Temperature - operating -10 to +40 OC 95% RH non-condensing
Temperature - storage -20 to +80OC
Connections
DOOR + and - Switched _24v to door retainer magnet
Control Contact Open circuit = PSU output ON
Short circuit = PSU output OFF
Ext Supply + and - Apply +24vdc to switch OFF PSU output
Indicators
Green LED Mains Present
Amber LED Output fuse blown
Installation
This unit is only suitable for installation as permanently connected equipment and must be
used with DC appliances only. The PSU is NOT SUITABLE for external installation. The PSU
should be installed according to all relevant safety regulations applicable to the application.
This unit must be fed from a mains power source having a separate (approved) disconnect
device and fitted with a fuse or other over-current protection device rated at 3A maximum.
Ensure that the disconnect device used has appropriate earth fault protection to the applicable
standard.
1) Fix to wall or other support structure in correct orientation i.e. with hinge on left hand
side, using screws of sufficient size and length through the mounting holes.
2) PSU should be mounted no further than 10cm from the control and indicating
equipment, close coupled by conduit.
3) Knock-outs are provided in the case for mating with external trunking or conduit.
4) Mains input cable must be to the applicable standard with a 3A or greater current
capacity, i.e. 0.5mm2nominal conductor area, having a minimum operating voltage of
300/500 Vac.
5) The low voltage output cable must be sized to carry the rated load current to the
devices connected to the PSU.
6) Mains input and low voltage output cables should be routed to use different entry / exit
case holes. Bushes should be used to protect cable sheaths from chamfer. Ensure that
these bushings are correctly sized (i.e. close fitting with respect to cable sizing). Note
that the bushes should meet a minimum flammability specification of UL94 HB.
7) The Mains input cable should be securely fastened in position using a cable tie through
the saddle provided.
Commissioning
1) With no other connections made to the PSU, connect the mains input wires to the
terminal block, ensuring that the mains isolator (disconnect device) is open.
Fasten wiring in place with cable tie to saddle. Note: Equipment must be earthed.
2) Apply mains input. Ensure that the green Mains LED illuminates and that 24vdc
nominla is present at the DOOR connections.
3) Remove mains power. Make connections to door retainer and control inputs according
to the option selected below.
4) Re-apply mains power. Activate control input and verify that power is removed from
door release electro-magnet.
5) Close cover and secure using fastening screws provided