Vac
Earth
11
12
24
33
34
44
A0
ACOM
0Vdc
24Vdc
AI
N
L
Description Default Programmable Required rating
group 1 relay
common
relay N/C fault yes 230Vac 1A AC15,
30Vdc 0.5A Resistive
relay N/O fault yes 230Vac 1A AC15,
30Vdc 0.5A Resistive
group 2 relay
common
relay N/O running yes 230Vac 1A AC15,
30Vdc 0.5A Resistive
relay N/O end of
start yes 230Vac 1A AC15,
30Vdc 0.5A Resistive
analog
output 0-10V yes 0 to 10V 10mA /
4-20mA
analog 0V 0V
analog input 0-10V Yes 0 to 10V 10mA /
4-20mA
control
supply SEE TABLE 1 , US#3
control
supply SEE TABLE 1, US#3
Required rating Programmable Default Description
#1 Group 1 input
common
#1 SEE TABLE 1, UCyes start/
stop
opto-coupled
input
#1 SEE TABLE 1, UCyes None opto-coupled
input
group 2 input
common
SEE TABLE 1 ,UCyes reset opto-coupled
input
not used
3 x PTC in series
(130°C) OFF thermistor
3 x PTC in series
(130°C) OFF thermistor
signal ground
#3 SEE TABLE 1 UScontrol supply
#3 SEE TABLE 1 UScontrol supply
*24Vdc Specication
24Vdc 60W
Residual ripple 100mV
Spikes/switching Peaks 240mV
Turn On/O response
No overshoot of V out
Overvoltage voltage protection output
voltage must be clamped to <30Vdc
SGY-101 to SGY-305 Control Power Consumption 60W
SGY-307 to SGY-309 Control Power Consumption 120W
Wiring connection
Model No (s):
SGY-101-4-01 to SGY-305-4-01
SGY-307-4-02 / SGY-309-4-02
SGY-307-4-03 / SGY-309-4-03
US(+10% -15%)
110 - 230Vac or 24Vdc
110Vac
230Vac
UC (+10% -15%) Notes
110Vac or 230Vac or
24Vdc.
230Vac factory default.
230Vac défaut d’usine.
#4
The system can have either a 110/230Vac
mains or 24Vdc input NOT both.
Le système peut avoir soit une alimentation
principale de 110/230 Vac ou de 24 Vdc, mais
en aucun cas les deux simultanement.
Table 1:- Interface Control Voltages, 2 Amp supply (continuous).
Representative of terminal label. See TABLE 1, USfor AC
supply rating as marked on actual Synergy model.
Vac
#1 The programmed digital input setting on D1COM, D1-1I, D1-2I must correspond to the voltage applied to these terminals to avoid risk of damage to the equipment.
An d’éviter d’endommager l’équipement, le réglage de l’entrée numérique programmé sur D1COM, D1-1I, D1-2I doit correspondre à la tension appliquée à ces bornes.
#2 The programmed digital input setting on D2COM, D2-1I must correspond to the voltage applied to these terminals to avoid risk of damage to the equipment.
An d’éviter d’endommager l’équipement, le réglage de l’entrée numérique programmé sur D2COM, D2-1I doit correspondre à la tension appliquée à ces bornes.
#3 The control supply can be 110 to 230Vac applied to the N, L terminals or 24Vdc applied to the 0Vdc, 24V input terminals. The correct voltage as specied must only be applied to one of these
supply inputs to avoid risk of damage to the equipment.
L’alimentation contrôle peut être 110 ā 230 Vca, appliquée aux bornes N et L, ou 24 Vcc, appliquée aux bornes d’entrée de 0 Vcc, 24 V. An d’éviter d’endommager l’équipement, la tension
appropriée selon les indications ne doit être appliquée qu’à une entrée d’alimentation.
#4 Refer to Synergy Programming Manual MAN-SGY-001 for factory default settings.
Référer au la Manuel de Programmation Synergy MAN-SGY-001 pour des paramètres par défaut d’usine