16 Application, Installation & Commissioning Doc. version 2
3.9 Remote Inputs FIRECLASS Prescient III
3.9.2 Gas Trapped (GAS TRAPPED)
This is a fully monitored input, providing open & short
circuit fault monitoring. The EOL device is a 10 kΩ resis-
tor, activated by a 680 Ω resistor. Activation illuminates
the HOGE DRUK VERZAMELLEIDING LED and raises
the general fault condition.
The inserts can then be cut out and inserted into the dis-
play board.
3.9.3 Auto/Manual Lock-Off Switch
(AUTO/MANUAL)
The Auto/Manual input is fully monitored for open &
short circuit faults. The End-Of-Line device is a 10kΩ
resistor, activated by a 4.7 Ω resistor. In the active state
the panel is placed in Manual Only mode and the yellow
Handbediening LED on the display board pulses.
Operation of the AUTO & HAND button on the display
board has no effect while the input is active. The input
allows for the connection of Auto/Manual Lock-Off
switches on SLUs. Door Lock switches may also be
connected via terminals on the SLUs. The total number
of Auto/Manual switches & Door Lock switches that
can be connected is 14. This allows for 7 SLUs, each
with an auto/manual Keyswitch and a door lock switch
fitted. See the FIRECLASS Prescient SLU installation
manual for more details.
3.9.4 Low Pressure Fault (GAS LOW)
This is a fully monitored input, providing open & short
circuit fault monitoring. The EOL device is a 10 kΩ resis-
tor, activated by a 680 Ω resistor. Activation illuminates
the LAGE DRUK GASCILLINDERS LED and raises the
general fault condition. An open or short circuit fault is
indicated by the Blussturing Storing LED on the
display and a Gas Low Fault LED on the motherboard.
The input is configurable for normally open or normally
closed operation via a DIL switch on the motherboard.
3.9.5 Extinguishing Isolation Valve
Status (ISO. VALVE)
This is a fully monitored input, providing open & short
circuit fault monitoring. The EOL device is a 10 kΩ resis-
tor, giving a AFSLUITER ONJUIST indication. An open
or short circuit fault is indicated by the Blussturing
Storing LED on the display and a Isolation Valve Fault
LED on the motherboard. Three states are possible on
the input:
1 Valve Closed:
Activated by a 680 Ω resistor, flashing the Valve Closed
LED on the display board & pulsing the internal buzzer.
2 Valve Open:
Activated by a 2.2 Ω resistor, no indication is given on
the panel as this is the healthy state for the input.
3 Valve Abnormal:
Activated by the 10 kΩ EOL resistor, flashing the
AFSLUITER ONJUIST LED on the display board & rais-
ing a general fault indication. A 2-second delay is applied
to the abnormal condition to avoid momentary activa-
tion during normal movement of the valve between
open and closed positions.
See Connection Diagram in section 8.3.2 for details.
3.9.6 Gas Released Pressure Switch
(GAS REL.)
This is a fully monitored input, providing open & short
circuit fault monitoring. The EOL device is a 10 kΩ resis-
tor. An open or short circuit fault is indicated by the
Blussturing Storing LED on the display and a Gas
Released Fault LED on the motherboard. The input
is activated by a 680 Ω resistor, illuminating the Blus-
sing Aktief LED on the display, the Extinguishing
sounder circuit, the Gas Released Signal & all three
shutdown outputs.
3.9.7 Emergency Hold (HOLD)
This is a fully monitored input, providing open & short
circuit fault monitoring. The EOL device is a 10 kΩ resis-
tor. An open or short circuit fault is indicated by the
Blussturing Storing LED on the display and a
Hold Fault LED on the motherboard. If a fault occurs
on the input during the Activated or Discharged condi-
tion then the fault indication is still given but the Uits-
tel Blussing LED is illuminated steady and the Hold
condition is established until the fault is removed. This
fault condition prevents the Extinguishant
release.
The input is activated by a 680 Ω resistor, illuminating
the Uitstel Blussing LED on the display and reset-
ting & holding the pre-discharge delay timer. The 2nd
Stage Relay is also de-energised.
Note
The healthy state for the input is VALVE
OPEN and therefore, if the input is not used,
the input should have a 2.2 Ω resistor fitted.
Note
If more than three Emergency Hold switches
connected to the Hold input are operated
simultaneously then a short circuit fault will
be detected. If this occurs while the Pre-dis-
charge timer is running, then the Timer will
still be reset and held until all switches are
released. Use only non-latching switches
which return to open contacts when the
switch is released.