Fleck 5600SE User manual

MODEL 5600SE
Downflow Brining
Service Manual

Page 2
Job Number ___________________________________
Model Number ________________________________
Water Test ____________________________________
Capacity Of Unit ________________________ Max. _____________ Per Regeneration
Mineral Tank Size: Diameter ___________________ Height _____________________
Under Bedding ____________________________ Amount _______________________
Type Of Media ____________________________ Cubic Feet _____________________
Brine Tank Size ________________________________
Salt Setting Per Regeneration ________________________________
Valve Programming
Treated Water Capacity ______________________________ (Gallons / Liters)
Regeneration Day Override _______________________________ (Max. Days Between
Regen.)
Regeneration Time ________________________________ ( A.M. ) ( P.M. )
Notes:
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
MODEL 5600SE Downflow
Job Specification Sheet

Page 3
MODEL 5600SE Downflow
General Residential Installation Check List
WATER PRESSURE: A minimum of 25 pounds of water pressure is required for regeneration valve to operate
effectively.
ELECTRICAL FACILITIES: An uninterrupted alternating current (A/C) supply is required. Please make sure your
voltage supply is compatible with your unit before installation.
EXISTING PLUMBING: Condition of existing plumbing should be free from lime and iron buildup. Piping that is
built up heavily with lime and/or iron should be replaced. If piping is clogged with iron, a separate iron filter unit
should be installed ahead of the water softener.
LOCATION OF SOFTENER AND-DRAIN: The softener should be located close to a clean working drain and con-
nected according to local plumbing codes.
BY-PASS VALVES: Always provide for the installation of a by-pass valve if unit is not equipped with one.
CAUTION: Water pressure is not to exceed 120 p.s.i., water temperature is not to exceed 110°F, and the unit
cannot be subjected to freezing conditions.
Valve Installation And Start-Up Procedures
01. Place the softener tank where you want to install the unit, making sure the tank is level and on a firm base.
02. During cold weather it is recommended that the installer warm the valve up to room temperature before oper-
ating.
03. All plumbing should be done in accordance with local plumbing codes. The pipe size for the drain should be a
minimum of 1/2”. Backwash flow rates in excess of 7 gpm or length in excess of 20’ require 3/4” drain line.
04. The 1” distributor tube (1.050 O.D.) should be cut flush with top of each tank. Note:-Only use silicone lubri-
cant.
05. Lubricate the distributor o-ring seal and tank “o” ring seal. Place the main control valve on tank.
06. Solder joints near the drain must be done prior to connecting the Drain Line Flow Control fitting (DLFC). Leave
at least 6” between the DLFC and solder joints when soldering pipes that are connected on the DLFC. Failure
to do this could cause interior damage to DLFC.
07. Teflon tape is the only sealant to be used on the drain fitting.
08. Make sure that the floor is clean beneath the salt storage tank and that it is level.
09. Place approximately 1” of water above the grid plate. If a grid is not utilized, fill to the top of the air check in
the salt tank. Do not add salt to the brine tank at this time.
10. On units with a by-pass, place in by-pass position. Turn on the main water supply. Open a cold soft water tap
nearby and let run a few minutes or until the system is free from foreign material (usually solder) that may
have resulted from the installation. Once clean, close the water tap.
11. Place the by-pass in service position and let water flow into the mineral tank. When water flow stops, slowly
open a cold water tap nearby and let run until the air is purged from the unit. Then close tap.
12. Plug the valve into an approved power source. Once the valve is powered it will drive to the Service Position.

1
2
12:00
Regeneration Display
12:05
Page 4
MODEL 5600SE Downflow
Control Start-Up Procedures
Extra Cycle Button
Program Mode Indicator:
Program Mode Entered - Dot On
Extra Cycle Button
Service
Program
Flow
P.M.
Step 1 - Backwash
Step 2 - Brine / Rinse
Step 3 - Rapid Rinse
Step 4 - Brine Refill
Regeneration Display
Service
Program
Flow
P.M.
Step 1 - Backwash
Step 2 - Brine / Rinse
Step 3 - Rapid Rinse
Step 4 - Brine Refill
Service Indicator:
Valve In Service - Dot On
Extra Cycle Tonight - Flashing Dot
Set Up Button
Flow Indicator:
Flashing Dot With Water Flow
P.M. Indicator
1. Push and hold for 5 seconds both the Up and Down Set Buttons to enter Programming Mode.
2. Push the Extra Cycle Button once per display until all have been viewed and this mode is exited
and normal operation is resumed.
Push either the Up or Down Set Button once to adjust Time Of Day Display by one digit.
Push and hold either Up or Down Set Button to adjust Time Of Day Display by several digits.
Set Time Of Day
Enter Control Programming Mode

3
Service
Program
Flow
P.M.
833
Page 5
MODEL 5600SE Downflow
Control Start-Up Procedures, Continued
Depending on current control programming, option setting displays that are not required to be
set will not be viewed.
Set Control Programming
1. The first option setting display that appears in the Program Mode is Treated Water Capacity.Using the
Set Up or Down Buttons, set the amount of treated water that can flow through theunit before a regeneration
is required. For Example
2. Push the Extra Cycle Button. The second option setting display that appears is Regeneration Time.
Using the Set Up or Down Buttons, set the desired time of day when a regeneration can occur, if required.
For Example:
650 Gallons Capacity
2:00 A.M. Regeneration Time
3. Push the Extra Cycle Button. The third option setting display that appears is Regeneration Day Over-
ride. Using the Set Up or Down Buttons, set the maximum number of days before a regeneration cycle
must occur. For Example:
Regenerate Every
7 Days Minimum
4. Control programming is now complete. Push the Extra Cycle Button. This will exit the control from
the Programming Mode, and resume Normal Operation.
A - -7
Service
Program
Flow
P.M.
Service
Program
Flow
P.M.
2:00
Service
Program
Flow
P.M.
650
Set Up Button
Set Down Button
Program Mode Indicator:
Program Mode Entered - Dot On
Extra Cycle Button
Step 1 - Backwash
Step 2 - Brine / Rinse
Step 3 - Rapid Rinse
Step 4 - Brine Refill
Regeneration Display

4
5
8 :0 0
1- - -
2- - -
3- - -
4- - -
- - - -
1 - - -
2 -5 8
3 - - 8
2 -1 1
8 :0 0
Service
Program
Flow
P.M.
Service
Program P.M.
Flow
Service
Program P.M.
Flow
Service
Program P.M.
Flow
Service
Program P.M.
Flow
Page 6
MODEL 5600SE Downflow
Control Start-Up Procedures, Continued
Service
Program
Flow
P.M.
Set Control Programming
Extra Cycle Button
Step 1 - Backwash
Step 2 - Brine / Rinse
Step 3 - Rapid Rinse
Step 4 - Brine Refill
Regeneration Display
When starting an Extra Cycle, you will have one or two options:
1. Press and Release the Extra Cycle Button:
-With Immediate Regeneration controls the control will go into regeneration cycle immediately.
- With Delayed Regeneration controls the Service Arrow will begin to flash immediately and a
regeneration will occur at the preset regeneration time (i.e. 2:00 a.m.)
2. Press and Hold for 5 seconds the Extra Cycle Button:
- With Delayed Regeneration controls this will force the control to go into regeneration cycle immediately.
Regeneration Cycle Displays
The following series of displays appear when the control enters a regeneration cycle:
Then
Then
Then
Then
Then
Valve Driving To
Regen. Step #1
Valve Driving To
Regen. Step #4
Less Than 59 Min.
Remain In Regen.
Step #2
Regen Complete.
Valve Driving
To Service
Less Than 9 Min.
Remain In Regen.
Step #1
Less Than 9 Min.
Remain In Regen.
Step #3
Less Than 12 Min.
Remain In Regen.
Step #4
Valve Has
Returned
To Service
Valve Driving To
Regen. Step #3
Valve Driving To
Regen. Step #2
Service
Program
Flow
P.M.
Service
Program P.M.
Flow
Service
Program P.M.
Flow
Service
Program P.M.
Flow
Service
Program P.M.
Flow

5
6
7
1 - - 8
Service
Program
Flow
P.M.
Fast Cycle Valve Thru Regeneration
Extra Cycle Button
Step 1 - Backwash
Step 2 - Brine / Rinse
Step 3 - Rapid Rinse
Step 4 - Brine Refill
Regeneration Display
Final Set-Up
The following series of displays appear when the control enters a regeneration cycle:
Page 7
A. Once the valve reaches Regen Step #1 let water run to drain for about 5 minutes.
Next, manually step the valve through a regen cycle checking valve operation in each step:
B. Push the Extra Cycle Button once to advance the valve to Regen Step #2.
C. Push the Extra Cycle Button once to advance the valve to Regen Step #3. (Optional)
D. Push the Extra Cycle Button once to advance the valve to Regen Step #4. (Optional)
E. Push the Extra Cycle Button once more to advance the valve back to Service.
With proper valve operation verified:
A. Add water to the top of the air check. Manually step the valve to the Brine Draw Posi-
tion and allow the valve to draw water from the brine tank until it stops. Note: The air
check will check at approximately the midpoint of the screened intake area.
B. Next, manually step the valve to the Brine Refill Position and allow the valve to return
to Service automatically.
C. With the valve in Service, check that there is about 1.0” of water above the grid in the
brine tank, if used.
D. Fill the brine tank with salt.
E. Set-Up is now finished, the control can now be left to run automatically.
MODEL 5600SE Downflow
Control Start-Up Procedures, Continued

1 - - 5
Service
Program P.M.
Flow
- - - -
8 3 3
Service
Program P.M.
Flow
Service
Program P.M.
Flow
Page 8
MODEL 5600SE Downflow
Control Operation
Timeclock Regeneration Valves
In normal operation the Time Of Day Display will be viewed at all times. The control will operate normally until the
number of days since the last regeneration reaches the Regeneration Day Override setting. Once this occurs, a
regeneration cycle will then be initiated at the preset Regeneration Time.
Flow Meter Equipped Valves
In normal operation the Time Of Day Display will alternate being viewed with a Volume Remaining Display. This
display will be in gallons. As treated water is used, the Volume Remaining Display will count down from a maxi-
mum value to zero or (----). Once this occurs a regeneration cycle will then be initiated immediately or delayed to
the set Regeneration Time. Water flow through the valve is indicated by the Flow Dot that will flash in a direct
relationship to flow rate. For Example:
833 Gallons Of Treated
Water Remaining
0 Gallons Of Treated
Water Remaining
Immediate Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value a regeneration cycle will be initiated im-
mediately. This event occurs regardless of the Volume Remaining display having reached zero gallons.
Delayed Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value a regeneration cycle will be initiated at
the preset Regeneration Time. This event occurs regardless of the Volume Remaining display having reached
zero gallons.
Control Operation During Regeneration
In Regeneration the control will display a special Regeneration Display. In this display the control will show the
current regeneration step number the valve is advancing to, or has reached, and the time remaining in that step.
The step number displayed will flash until the valve has completed driving to this regeneration step position. Once
all regeneration steps have been completed the valve will return to Service and resume normal operation.
For Example:
Pushing the Extra Cycle Button during a regeneration cycle will immediately advance the valve to the next cycle
stepposition and resume normal step timing.
Control Operation During Programming
The control will only enter the Program Mode with the valve in Service. While in the Program Mode the control
will continue to operate normally monitoring water usage and keeping all displays up to date. Control program-
ming is stored in memory permanently, without the need for battery backup power.
Control Operation During A Power Failure
During a power failure all control displays and programming will be stored for use upon power re-application. The
control will retain these values for years, if necessary, without loss. The control will be fully inoperative and any
calls for regeneration will be delayed. The control will upon power re-application resume normal operation from
the point were it was interrupted. An indication that a power outage has occurred will be an inaccurate time of day
display.
Less Than 6 Minutes
Remaining In Regen
Step #1

Page 9
Service
Position
Backwash
Position
(Regeneration Cycle Step #1)
MODEL 5600SE Downflow
Water Conditioner Flow Diagrams (downflow brining)
Using Black Cycle Cam (P/N 17438)

Page 10
Brine/Slow Rinse
Position
(Regeneration Cycle Step #2)
Rapid Rinse
Position
(Regeneration Cycle Step #3)
MODEL 5600SE Downflow
Water Conditioner Flow Diagrams (downflow brining)
Using Black Cycle Cam (P/N 17438), Continued

Page 11
MODEL 5600SE Downflow
Water Conditioner Flow Diagrams (downflow brining)
Using Black Cycle Cam (P/N 17438), Continued
Brine Tank
Fill Position
(Regeneration Cycle Step #4)
Service
Position

Page 12
MODEL 5600SE Downflow
Control Valve Assembly
51B

Page 13
Item No. Quantity Part No. Description
* 1 2 13255 Adapter Clip
2 5 13242 Seal
3 1 .....61400-12 Valve Body Assembly - 1” dist.
1.....61400-11 Valve Body Assembly - 13/16” Dist.
4 1 13304 “O” Ring - Distributor Tube - 1”
110244 “O” Ring - Distributor Tube - 13/16”
5 1 12281 “O” Ring - Top of Tank
6Not Assigned
7 4 14241 Spacer
8 1 17218 Piston (Used with Black Cycle Cam)
9 1 13306 Piston Pin
10 1 13001-04 Piston Rod Assembly
11 1 14309 Piston Retainer
12 1 13446-40 End Plug Assembly - Green
14 2 13315 Screw - Injector Mounting
*15 2 19228 Adapter Coupling
*16 4 13305 “O” Ring - Adapter Coupling
*17 2 13314 Screw - Adapter Coupling
18 1 12638 “O” Ring - Drain
19 2 13301 “O” Ring - Injector
20 2 13302 “O” Ring - Brine Spacer
21 1 13303 “O” Ring - Injector Cover
22 1 13163 Injector Body
23 1 10913 Injector Nozzle - Specify Size
24 1 10914 Injector Throat - Specify Size
25 1 10227 Injector Screen
26 1 13166 Injector Cover
27 1 13172 Brine Valve Stem
28 1 12626 Brine Valve Seat
29 1 13165 Brine Valve Cap
30 1 13167 Brine Valve Spacer
31 1 12550 Quad Ring
32 1 11973 Spring - Brine Valve
33 1 16098 Washer - Brine Valve
34 1 11981-01 Retaining Ring
35 1 10329 B.L.F.C. Fitting Nut 3/8”
36 1 10330 B.L.F.C. Ferrule 3/8”
37 1 10332 B.L.F.C. Tube Insert 3/8”
38 1 B.L.F.C. Button - Specify Size
39 1 12977 “O” Ring - B.L.F.C.
40 1 13245 B.L.F.C. Button Retainer
41 1 13244 B.L.F.C. Fitting
42 1 D.L.F.C. Button - Specify Size
43 1 13173 D.L.F.C. Button Retainer
44 1 12767 Screen - Brine Line
45 1 15348 “O” Ring - D.L.F.C.
46 1 13497 Air Disperser
47 1 13546 End Plug Retainer
48 3 12112 Screw
49 1 13363 Washer
50 1 13296 Screw
51A 113398 Yoke, Brass, 1” NPT
113708 Yoke, Brass, 3/4” NPT
51B 118706 Yoke, Plastic, 1” NPT
118706-02 Yoke, Plastic, 3/4” NPT
52 1 13308 Drain Hose Barb
* Not used with meter controls.
MODEL 5600SE Downflow
Control Valve Assembly Part List

Page 14
MODEL 5600SE Downflow
Valve Powerhead Assembly

Page 15
Item No. Quantity Part No. Description
1 1 26001-02 Drive Housing, Black
2 2 12473 Screw, Drive Mount
3 1 19474 Wire Harness, Power
4 1 13299 Spring Washer
5 1 13017 Idler Gear
6 2 19080 Spring, Detent
7 2 13300 Ball, Detent
8 1 25005 Main Drive Gear & Shaft (Downflow Brining - Black)
9 1 23045 Drive Gear
10 1 13175 Motor Mounting Plate
11 1 16944 Drive Motor 2RPM 24V 50/60Hz
12 3 11384 Screw, Motor
13 1 13229 Back Plate
14 5 13296 Screw, Component
15 1 12037 Washer
16 1 18722 Cam, Brine Valve
17 1 19674 Transformer, 24V 9.6VA (Optional)
18 1 13547 Strain Relief
19 1 19079 Washer, Friction
20 1 17438 Cycle Cam (Downflow Brining - Black)
21 1 10302 Insulator
22 2 17876 Screw, Microswitch
23 1 60755-021 Front Panel Assembly (Backwash First Label, Black)
24 2 13898 Screw, Front Panel
25 2 10218 Microswitch
26 1 15151 Screw, Cycle Cam
27 4 12681 Wire Nut, Grey (Not Shown)
MODEL 5600SE Downflow
Valve Powerhead Assembly, Continued

Page 16
Parts List
Item No. Quantity Part No. Description
1 2 13314 Screw, Hex Washer, 8-18 x 5/8
2 2 19569 Clip, Flow Meter
3 1 19797 Meter Body Assembly, 3/4” Turbine
4 4 13305 O Ring, -119
5 1 19791-01 Harness Assembly, Flow Meter
6 1 14613 Flow Straightener (Not Shown)
MODEL 5600SE Downflow
3/4” Turbine Meter Assembly

Page 17
Parts List
Item No. Quantity Part No. Description
1 1 19723 By-Pass Valve Body, Plastic
2 1 11183 O Ring, -015
3 1 19724 Cap, By-Pass
4 2 17512 Screw, Hex Washer Head, #6-24 x 3
5 2 17820 Plug, By-Pass
6 4 18661 O Ring, -218
7 2 18662 Retaining Ring
8 2 18660 O Ring
9 2 13305 O Ring, -119
10 2 13255 Clip, Mounting
11 2 13314 Screw, Hex Washer Head, 8-18 x 5/8
12A 118706 Yoke, Plastic, 1" NPT
118706-02 Yoke, Plastic, 3/4" NPT
12B 113708 Yoke, Brass, 3/4" NPT
113708NP Yoke, 3/4" NPT Nickel Plated
113398 Yoke, Brass, 1" NPT
113398NP Yoke, 1" NPT Nickel Plated
MODEL 5600SE Downflow
By-Pass Valve Assembly, Plastic

Page 18
Parts List
Item No. Quantity Part No. Description
1 1 17290 By-Pass Valve Body, 3/4"
117290NP By-Pass Valve Body, 3/4" Nickel Plate
113399 By-Pass Valve Body, 1"
113399NP By-Pass Valve Body, 1", Nickel Plate
2 1 11726 Seal, By-Pass
3 1 11972 Plug, By-Pass
4 1 11978 Side Cover
5 1 13604-01 Label
6 8 15727 Screw
7 1 11986 Side Cover
8 1 11979 Lever, By-Pass
9 1 11989 Screw, Hex Head, 1/4-14
MODEL 5600SE Downflow
By-Pass Valve Assembly, Brass

9
7
6
5
8
1
2
3
7
6
5
4
12
12
10
Page 19
Parts List
Item No. Quantity Part No. Description
1 1 60027-00 2300 Safety Brine Valve Body
2 1 10138 Ball, 3/8"
3 1 11566 Bull Stop
4 1 10328 Elbow, 1/4 x 1/4 T
5 2 10332 Insert, 3/8
6 2 10330 Sleeve, 3/8
7 2 10329 Tube Nut, 3/8
8 1 10186 Nut, Hex, 10-32, Nylon
9 1 60002 #500 Air Check
10 1 10149 Float Rod, 30"
11 1 10700 Float Assembly, Blue/White
12 4 10150 Grommet
MODEL 5600SE Downflow
2300 Safety Brine Valve

BLACK
ORANGE
PURPLE
BLACK
RIBBED
SMOOTH
WHITE
BLUE
YELLOW
WHITE
RED
BLACK
GREEN
HCAM
VDM
N.O.
N.C.
C
SW 1
C
SW 2
N.D.
N.O.
Page 20
CB1 - 5600SE Circuit Board
VDM - Valve Drive Motor
EM - Electronic Flow Meter (Optional)
SW1 - Homing Switch
SW2 - Step Switch
HCAM - Homing Cam
DFSCAM - Downflow Step Cam
MODEL 5600SE Downflow
Valve Wiring Diagram
Other manuals for 5600SE
1
Table of contents
Other Fleck Control Unit manuals