Underload Smart Reset
If a motor Underload fault condition occurs, the most likely cause is
an overpumped or dry well. To allow the well to recover, the SubDrive
controller will wait 30 seconds to 5 minutes, determined by duration of
the previous run time, before restarting the motor. For example, the rst
time the fault occurs, the controller will wait 30 seconds before attempting
to restart the pump. If the system would then run for 1 minute and an
Underload fault recurs, the controller will wait 4 minutes before attempting
to restart the pump. This schedule allows for the minimum off-time possible
based on the recovery time of the well. 0 81 2 4 6 753
0
1
2
4
6
5
3
Off Time (Minutes)
Run Time (Minutes)
Figure 1: Smart Reset Well Recovery Time
Over Temperature Foldback
The SubDrive controller is designed for full power operation in ambient temperatures up to 50 °C as long as the input
voltage is kept at 230 VAC. Under extreme thermal conditions, the controller will reduce output power in an attempt to
avoid shutdown. Full pump output is restored when the controller temperature cools to a
safe level.
Before Getting Started
Generator Sizing for SubDrive/MonoDrive
Basic generator sizing for the Franklin Electric SubDrive/MonoDrive system is 1.5 times maximum input Watts
consumed by the drive, rounded up to the next normal sized generator.
Recommended minimum generator sizes:
SubDrive75 = 3500 Watts (3.5 kW)
SubDrive100 = 5700 Watts (6 kW)
SubDrive150 = 7000 Watts (7 kW)
NOTE: Not to be used on GFIC circuit Externally regulated generators Verify voltage, hertz and idle speed are
appropriate to supply drive.
Serious or fatal electrical shock may result from failure to connect the ground terminal to the motor, SubDrive/
MonoDrive controller, metal plumbing, or other metal near the motor or cable, using wire no smaller than motor
cable wires. To minimize risk of electrical shock, disconnect power before working on or around the SubDrive/
MonoDrive system. CAPACITORS INSIDE THE SUBDRIVE CONTROLLER CAN STILL HOLD LETHAL
VOLTAGE EVEN AFTER POWER HAS BEEN DISCONNECTED.
ALLOW 5 MINUTES FOR DANGEROUS INTERNAL VOLTAGE TO DISCHARGE BEFORE REMOVING
SUBDRIVE/MONODRIVE COVER.
Do not use motor in swimming areas.
This equipment should be installed by technically qualied personnel. Failure to install it in compliance with
national and local electrical codes and within Franklin Electric recommendations may result in electrical shock or
re hazard, unsatisfactory performance, or equipment failure. Installation information is available through pump
manufacturers and distributors, or directly from Franklin Electric at our toll-free number 1-800-348-2420.
Use SubDrive only with Franklin Electric 4-inch submersible motors as specied in this manual. Use of this unit
with any other Franklin Electric motor or with motors from other manufacturers may result in damage to both motor
and electronics.