13
Output charts water AGS5500/AGR5500 WL
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 31 40 0,19 1,3 47 43 0,58 9,8
min 2500 14 33 0,07 0,2 28 51 0,35 3,7
AGx5520WL max 8250 49 34 0,26 2,4 78 46 0,95 27,3
min 3750 21 26 0,09 0,4 47 55 0,57 10,4
AGx5525WL max 11000 64 34 0,34 4,4 100 45 1,22 49,1
min 5000 29 26 0,13 0,8 61 54 0,74 18,7
AGx5530WL max 13750 78 36 0,44 4,9 124 45 1,51 43,2
min 6250 35 29 0,17 0,9 73 52 0,89 16,6
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 32 44 0,30 2,9 37 38 0,45 6,2
min 2500 14 35 0,10 0,4 22 44 0,27 2,4
AGx5520WL max 8250 48 38 0,36 4,5 62 40 0,75 1 7, 7
min 3750 22 28 0,13 0,7 37 47 0,46 6,8
AGx5525WL max 11000 63 38 0,47 8,2 80 39 0,97 31,8
min 5000 29 28 0,17 1,3 49 47 0,59 12,3
AGx5530WL max 13750 81 41 0,67 10,6 98 39 1,19 28,9
min 6250 36 32 0,23 1,6 58 45 0,70 11,2
*1) Recommended outlet air temperature for good comfort and optimized output.
*2) Nominal output at given supply and return water temperature.
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 33 48 0,63 11,9 27 32 0,32 3,4
min 2500 15 37 0,16 0,9 16 37 0,19 1,3
AGx5520WL max 8250 48 42 0,67 14,4 46 34 0,55 10,1
min 3750 21 31 0,18 1,2 28 40 0,34 4,0
AGx5525WL max 11000 65 45 1,06 38,2 59 34 0,72 18,1
min 5000 30 32 0,26 2,7 36 39 0,44 7, 2
AGx5530WL max 13750 81 45 1,30 35,0 71 33 0,87 1 7, 0
min 6250 36 35 0,35 3,4 42 38 0,51 6,7
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 32 48 1,14 37,4 21 29 0,26 2,2
min 2500 14 38 0,21 1,5 13 33 0,15 0,9
AGx5520WL max 8250 49 46 1,31 52,4 37 31 0,45 7, 0
min 3750 21 32 0,23 2,0 23 36 0,28 2,8
AGx5525WL max 11000 62 46 1,68 94,3 49 31 0,59 12,6
min 5000 29 34 0,33 4,2 30 36 0,36 5,1
AGx5530WL max 13750 78 46 2,10 83,9 58 30 0,70 12,0
min 6250 37 37 0,49 6,4 34 34 0,42 4,8