PL2200C
12
Output charts water PL2200C
*1) Recommended outlet air temperature for good comfort and optimized output.
*2) Nominal output at given supply and return water temperature.
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PL2210CW max 1200 6,9 60,2 0,09 7, 3 6,9 35,0 0,08 7, 2
min 700 4,0 49,7 0,03 1,4 5,0 39,2 0,06 4,1
PL2215CW max 1800 10,4 56,1 0,11 6,2 11,1 36,2 0,14 9,6
min 1000 5,8 45,5 0,04 1,2 7, 8 40,8 0,10 5,1
PL2220CW max 2400 13,9 57,9 0,14 6,2 14,4 35,7 0,18 7, 9
min 1400 8,1 47,9 0,06 1,2 10,5 40,0 0,13 4,5
Supply water temperature: 90 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 90/70 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PL2210CW max 1200 6,9 57,8 0,05 3,1 8,5 38,8 0,10 10,2
min 700 4,0 48,1 0,02 0,8 6,2 44,1 0,08 5,8
PL2215CW max 1800 10,4 53,1 0,07 2,9 13,6 40,2 0,17 13,5
min 1000 5,8 43,3 0,03 0,7 9,5 45,9 0,12 7, 0
PL2220CW max 2400 13,9 55,4 0,10 2,7 1 7, 7 39,7 0,22 11,1
min 1400 8,1 46,2 0,05 0,7 12,8 45,0 0,16 6,3
Supply water temperature: 110 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 110/80 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PL2210CW max 1200 6,9 53,7 0,03 1,1 10,4 43,5 0,09 6,9
min 700 4,0 45,4 0,02 0,4 7, 6 50,0 0,06 3,9
PL2215CW max 1800 10,4 48,1 0,04 1,1 16,7 45,3 0,14 9,2
min 1000 5,8 39,8 0,02 0,3 11,7 52,3 0,10 4,8
PL2220CW max 2400 13,9 51,1 0,06 1,0 21,7 44,6 0,18 7, 5
min 1400 8,1 43,4 0,03 0,3 15,8 51,2 0,13 4,2
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PL2210CW max 1200 6,9 62,5 0,23 43,1 5,3 31,0 0,07 4,6
min 700 4,0 51,7 0,05 3,3 3,9 34,3 0,05 2,7
PL2215CW max 1800 10,4 59,3 0,24 26,7 8,7 32,2 0,11 6,3
min 1000 5,8 48,0 0,06 2,6 6,0 35,8 0,07 3,3
PL2220CW max 2400 13,9 60,5 0,35 28,5 11,1 31,6 0,14 5,1
min 1400 8,1 50,0 0,10 2,9 8,1 35,0 0,10 2,9