F15 - Backup 1 operating mode:
[,,,0]Backup 1 working independently from backup 2.
[,,,1]Backup 1 disabled when backup 2 is active.
NOTE: Programmed in 1, if the two backup systems are in condition to be switched on, backup 1 is
switched off and the controller displays the message [Aa2,], except when backup 1 is with manual
activation or when backup 1 is operating in the antifreeze (F31).
F16 - Backup 1 temperature setpoint:
Temperature to switch off backup 1.
F17 - Backup 1 operation hysteresis:
Temperature to switch backup 1 on again.
Exemple:
[,F16]= 30,0 °C
[,F17]= 1,0°C
Backup 1 switches off at 30° C and switches on again at 29° C (30-1=29).
IMPORTANT: Backup 1 is linked to an event schedule (acts in accordance with user-defined times
up to eight daily events). That is why the times must be programmed for this backup system to work
properly. If the clock of the controller is not programmed (message [ECLO]), MICROSOL II e
plus assumes a momentary disconnection until the clock is reprogrammed.
F18 - Minimum setpoint allowed to the end user (backup 1):
Avoids regulation of excessively low setpoint temperatures by mistake.
F19 - Maximum setpoint allowed to the end user (backup 1):
Avoids regulation of excessively high setpoint temperatures by mistake.
F20 - Backup 1 manual activation time:
Time for which MICROSOL II e plus will remain independent from the event schedule if the user
activates backup 1 manually. After this time, backup 1 returns to automatic mode.
F21 - Backup 2 operating mode:
[,,,0]Refrigeration thermostat.
[,,,1]Heating thermostat.
[,,,2]Refrigeration thermostat linked to the event schedule.
[,,,3]Heating thermostat linked to the event schedule.
[,,,4]Cyclical timer with initial state on.
[,,,5]Cyclical timer with initial state on and linked to the event schedule.
[,,,6]Refrigeration thermostat for dissipation of excess temperature in the water tank.
[,,,7]Heating thermostat of the keg with recirculation.
[,,,8]Heating thermostat of the keg with recirculation linked to the event schedule.
[,,,9]Event output independent from thermostats.
When the thermostat mode is selected for the keg heating, the backup systems are controlled by
different sensors. Backup 2 is controlled by sensor 3 while backup 1 is controlled by sensor 3. For this,
sensor 3 must be enabled in function [,F34].
In the other thermostat functions, both backup systems are controlled by the same sensor. If sensor 3 is
disabled (F34=OFF), both backup systems are controlled by sensor 2 or otherwise controlled by sensor
3, if it is enabled.
NOTE: If the controller's clock is not programmed (message [ECLO]) and the operating mode of
backup 2 is linked to the event schedule, MICROSOL II e plus assumes a momentary
disconnection until the clock is reprogrammed.
F22 - Backup 2 temperature setpoint:
This is the maximum desired temperature in the swimming pool (or thermal tank), as well as in function
[,F13].
F23 - Backup 2 operation hysteresis:
It is the temperature difference (hysteresis) between switching the heating (or refrigeration) of the
thermostat ON and OFF of backup 2.
Exemple: One wants to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the
cooling is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0), in the heating mode the
output is switched off at 3° C and is switched on again at 4.0° (1.0 - 4), as per the charts below:
Temperature [°C]
Cooling
Temperature [°C]
Heating
Setpoint
Setpoint + Hysteresis
Time [S]
Relay Off
Relay On
4°C
5°C Setpoint
Setpoint + Hysteresis
Time [S]
3°C
4°C
Relay Off
Relay On
F24 - Minimum setpoint allowed to the end user (backup 2):
Avoids regulation of excessively low setpoint temperatures by mistake.
F25 - Maximum setpoint allowed to the end user (backup 2):
Avoids regulation of excessively high setpoint temperatures by mistake.
F26 - Backup 2 manual activation time:
Time for which MICROSOL II e plus will remain independent from the event schedule if the user
activates backup 2 manually. After this time, backup 1 returns to automatic mode.
F27 - Cyclical timer on time / Recirculation* (Scan Time):
It allows the adjustment of the time for which the controller will remain with output AUX 2 on when
backup 2 is configured in cyclical timer mode (F21 = 4 or 5).
If the operating mode of backup 2 is heating thermostat of the keg with recirculation (F21 = 7 or 8), this is
the time for which the controller will keep the water circulation active to regulate the temperature of the
water in the keg.
Note: The recirculation can be disabled by adjusting it with the minimum value 0 [No,,], On the other
hand, the minimum on time for the cyclic timer is 1 minute.
F28 - Cyclical timer off time / Intervals* between scans:
It allows the adjustment of the time for which the controller will remain with output AUX 2 off when
backup 2 is configured in cyclical timer mode (F21 = 4 or 5).
Functions F27 and F28 are used when the user configures backup 2 to filter the swimming pool. In this
case, backup 2 will cycle in accordance with the times programmed in F27 (on time) and F28 (off time). If
the operating mode of backup 2 is heating thermostat of the keg with recirculation, this is the time
interval between the last and the next temperature scan. If the temperature to switch on the backup is
reached the scan cycle is restarted.
Note: The interval between scans can be disabled by adjusting it with the minimum value 0 [No,,].
On the other hand, the minimum off time for the cyclical timer is 1 minute.
F29 - Event schedule linking mode:
This function allows the user to configure whether backup 2 must work in conjunction with backup 1 or
not. If backup 2 is programmed as linked to the schedule of (F21=2, 3, 5, or 8), this function will serve to
inform the events (times) for which the backup systems will be activated.
[,,,0]Aux 1 linked to events 1,2,3,4,5,6,7 e 8.
Aux 2 linked to events 1,2,3,4,5,6,7 e 8.
[,,,1]Aux 1 linked to event 1.
Aux 2 linked to events 2,3,4,5,6,7 e 8.
[,,,2]Aux 1 linked to events 1,2.
Aux 2 linked to events 3,4,5,6,7e 8.
[,,,3]Aux 1 linked to events 1,2,3.
Aux 2 linked to events 4,5,6,7e 8.
[,,,4]Aux 1 linked to events 1,2,3,4.
Aux 2 linked to events 5,6,7e 8.
[,,,5]Aux 1 linked to events 1,2,3,4,5.
Aux 2 linked to events 6,7e 8.
[,,,6]Aux 1 linked to events 1,2,3,4,5,6.
Aux 2 linked to events 7e 8.
[,,,7]Aux 1 linked to events 1,2,3,4,5,6,7.
Aux 2 linked to event 8.
F30 - Temperature to switch off the cooling in* vacation mode (S3):
This aims to cool the thermal tank during the night when Vacation mode is active, whenever the sensor 3
temperature is higher than the value adjusted in this parameter and the temperature difference between
the solar panel (S1) and the tank (S2) reaches -4.0ºC (fixed). Then the pump is switched on using the
solar panel as a radiator to cool the water in the swimming pool. When the differential (T1-T2) drops
below -2.0ºC (fixed) or the backup temperature (S3) drops below the temperature of this parameter, the
pump is switched off. The hysteresis of this control is fixed and defined as 2.0ºC.
F31 - Output of backup 1 associated to the antifreeze (S1):
When enabled it aims to ensure a minimum temperature in the thermal tank for when the antifreeze
function ([,F08])is required.
The output of backup 1 is activated whenever the backup's temperature is below the adjustment of
[,F08] (antifreeze temperature) + [,F09] (antifreeze hysteresis). The hysteresis of this control is
fixed and defined as 2.0ºC. For example, if adjusted [,F08]=[,,8.0]and [,F09]=[,20.0],the
output of backup 1 will switch on when sensor 3 temperature is below 28.0°C and switch off when it is
above 30.0°C.
Note: This function switches the backup output on independently of backup 1 mode, vacation mode, or
event schedule.
F32 - Sensor 1 indication offset:
It allows for the compensation of possible deviations in the temperature reading caused by the
replacement of the sensor or changes in the cable length.
F33 - Sensor 2 indication offset:
It allows the compensation of possible deviations in the temperature reading caused by the
replacement of the sensor or changes in the cable length.
F34 - Sensor 3 indication offset:
It allows for the compensation of possible deviations in the temperature reading caused by the
replacement of the sensor or changes in the cable length. Sensor 3 may be disabled by adjusting this
function to the maximum value [Off,]. After sensor 3 is disabled, backup systems 1 and 2 will be
controlled by sensor 2 (tank / swimming pool).
F35 - Linking of sensor S3 to the automatic mode (If sensor 3 is enabled):
[no,,]Circulation pump operating in automatic mode and not linked to sensor 3. With this mode the
pump is activated only by the temperature differential (S1-S2).
[yes,]Circulation pump operating in automatic mode and linked to sensor 3. With this mode the
pump is activated by the temperature differential and when the temperature at sensor 1 is higher than
that at sensor 3.
NOTE: When the value of this function is [yes,] it will return to [no] when sensor 3 is disabled
[no,,].
F36 - Maximum time the backup 1 output remains on without reaching the setpoint:
Is the maximum time the output of backup 1 will remain on without reaching the setpoint. When this time
is exceeded the visual alarm [gAs,]is activated and the thermostat output remains off according to
the time defined in F37. Functions F36 and F37 serves as protections for the gas-fired backup so that in
case of system failure (flame out for instance), the water circulation is interrupted and the heater is
switched off to protect it. This function can be disabled by adjusting it to the minimum value 0 [no,,].
F37 - Backup 1 output off time in state of alarm for not reaching the setpoint:
It allows adjusting the time for which the controller will keep the backup 1 output off while in state of
alarm for not reaching the setpoint. If the setpoint is reached during this time the alarm is switched off. If
the setpoint is not reached after this time has elapsed, new checks are performed during the time
defined in F36.
F38 - Digital input operating mode:
[Off,]Off
[,,,1]Activate / deactivate manual pump operation (NO switch)
[,,,2]Activate / deactivate manual pump operation (NF switch)
[,,,3]Activate / deactivate manual backup 1 operation (NO switch)
[,,,4]Activate / deactivate manual backup 1 operation (NF switch)
[,,,5]Activate / deactivate manual backup 2 operation (NO switch)
[,,,6]Activate / deactivate manual backup 2 operation (NF switch)
[,,,7]Activate / deactivate vacation mode (NO switch)
[,,,8]Activate / deactivate vacation mode (NF switch)