G-403-P02 USER’S MANUAL PAGE 5
PPUH „GECO” Sp. z o.o. Edition II RELEASE DATE 2006-09-04
4. WIRING SYSTEM AND RULES OF CONNECTION
1. The boiler house should be equipped with the 230V/50Hz wiring system, in accordance
with applicable regulations.
2. Irrespective of the wiring system kind, the plug-in sockets should be equipped with the
protective terminal. The application of the socket without the protective terminal
connected is a shock hazard!
3. The controller should be connected to the separate power supply line, protected by means of
the 2-4A rapid fuse and the residual current circuit breaker, with activation current 20 mA
maximum. The connection of any other equipment to this line is not allowed!
4. The clamp conductor joints used are certified for continuous load of 16 A. As the fine
thread and special metal sheets preventing conductors cutting have been applied, a perfect
contact is achieved with slight screwing of the conductor. Applying larger force may lead to
breaking the thread.
5. The power supply cables must be firmly attached along their entire length and should not
catch the water coat or the outlet to the chimney.
6. Following the connection of the unit to the power supply, the unit may be energized
irrespective of switching on or off by means of the pushbutton, therefore any repairs
may be performed only when the voltage is disconnected from the fuse!
5. G-403-P02 OPERATION AND ADJUSTMENT METHODS
5.1. Temperature measurement
The controller measures the temperature within the range of 0 degree Centigrade to 100 degree
Centigrade. The temperature is displayed with the delay of one second. Where the malfunction
occurs to the temperature sensor, or temperature value is found beyond the above-mentioned range
and the equipment is not found in the mode of 60 second-waiting for power supply voltage
stabilization following power failure, the controller reports the malfunction to the sensor. This
causes both the deactivation of all activated equipment, i.e. fan, feeding screw and pump, and
switching to the manual operation mode, the following symbols being then displayed:
AL1 symbol, if the flow water temperature sensor has got broken,
AL2 symbol, if the feeding screw sensor has got broken,
AL3 symbol, if the malfunction has occurred to the boiler inlet water temperature sensor or the
feeding screw coupling cotter pin has got broken.
The occurrence of the temperature exactly equal to 100 degrees Celsius will cause the display to
show 00o.
5.2. Exceeding the allowable temperature of the fuel in the feeding screw
The controller has been equipped with the sensor reporting that the allowable temperature of
fuel in the feeding screw has been exceeded. The controller operates owing to the measurement of
the feeding screw pipe temperature. If the temperature in question reaches the level of 98 degrees
Centigrade, the controller reports the AL6 alarm, deactivating the fan and activating the continuous
operation of the feeding screw for the period of 10 minutes so that the burning fuel may be removed
from the feeder and the furnace may be put down.
When the manual operation mode is activated, the feeding screw temperature is not checked,
therefore the malfunction to the feeding screw temperature sensor launches the AL2 alarms.