
20 80991C_MHW_GF_VEDO SL_09-2017_ENG
To upload the application program onto the Integrated Con-
troller and Operator Panel, proceed as follows:
1. Connect the controller to a PC using a crossover Ether-
net cable.
2. Open the Network screen of the set-up program, di-
sable the DHCP and manually set an IP address, e.g.:
192.168.010.002.
3. Run the GF Project LX program on the PC.
4. Click the Open code prj ... button.
5. Select the required PLC program from the list that opens
(the le extension is .PPJS) and click the Open button.
6. Select -> Settings from the Communication menu.
7. Select the GDB protocol in the Device Link Manager
Cong window that opens.
8. Click the Properties button. The Gdb Cong. Win-
dow opens. Select the TCP/IP protocol from the Port
dropdown menu and enter the IP address indicated at
step 2 of the procedure in the IP address box.
9. Click the OK button and then press OK again.
10. Check the connection. Select -> Connect from the
Connection menu. The PC connects to the controller.
In the bottom right window the following words appear:
CONNECT, in green, NO CODE in yellow. If
DIFFERENT CODE appears, this means that there is
already an application program, dierent from the one
you are trying to upload, on the controller. If the word
CONNECT does not appear, this means that communi-
cation related settings are incorrect. In particular, verify
the IP address.
Uploading the application program
System Message / Fault
This screen shows useful information in the case of malfun-
ctions.
Reset after watchdog signal indicates whether the con-
troller restarts automatically after the program has been blo-
cked.
Last Fault indicates when the last malfunction occurred.
Fault address indicates the address of the application pro-
gram code which manifested the malfunction.
PLC Loaded shows and signals the correct upload of the
PLC software.
HMI Loaded shows and signals the correct upload of the
application program.
The HOME button in the top left corner allows a return to
the Main Menu while the BACK button returns to the Infor-
mation screen.
11. Upload the application onto the controller, selecting ->
Download Code from the Communication menu. Click
the Yes button in the warning message that opens. The
transfer starts and is highlighted on a progress bar.
12. At the end of the transfer, a window opens and asks you
to restart the system. Click Ye s.
13. In the bottom left corner of the Output panel there is a
list of the results of the actions performed; the message
SOURCE OK appears in the window at the bottom.
14. Click the Open GF Project LX page button and wait
for the page editor to open.
15. Open the page application, selecting the OPEN page
menu.
16. Select the page required (the le extension is PAJX)
from the list and click the Open button.
17. Select -> Communication settings from the Project
menu.
18. Select the GDB protocol in the Device Link Manager
Cong window that opens.
19. Click the Properties button. The Gdb Cong. Win-
dow opens. Select the TCP/IP protocol from the Port
dropdown menu and enter the IP address indicated at
step 2 of the procedure in the IP address box.
20. Click the OK button and then press OK again.
21. Transfer the program, selecting -> Download Project
from the Project menu.
22. In the bottom left corner of the Output panel there is a
list of the results of the actions performed; and the rst
page of the program uploaded appears on the screen of
the Integrated Controller and Operator Panel.
23. Remove the Ethernet cable.
To upload a new program onto a controller that has already
been programmed, follow the same procedure.