4.2 Communication objects
The Main menu makes the following communication objects visible (see Diag. 4.2.):
Diag. 4.2
¾4.2.1 HVAC mode input
Here you can configure the remote control of the device operating mode (HVAC mode) by bus
command. When this communication object receives a telegram with the operating mode information
that is to be set, the device sets the operating mode according to the command received, indicated by a
pilot light on the display.
If the device has been configured in stand alone mode, it is still possible to modify the operating mode
using the local navigation menu on the device, which does nothing more than replicate the command
reception event on the communication object in question to modify, with each pressing, the operating
mode.
The enabled flags are C (communication), W (written by bus), R (read by bus), T (transmission) and U
(actualize the value).
The standard format of the object is 20.102 DPT_HVACMode, the size of the object is 1 byte and the
commands it receives are operating mode commands: Economy/Precomfort/Comfort/Off.
¾4.2.2 Window status
Here you can enable the remote control of the device OFF operating mode (or HVAC mode) by bus
command, when a windows is open. When this object receives a telegram with a "1" logic value (window
open), the device instantly switches to OFF mode, indicated by a pilot light on the display, given the
enabling of this object has a higher priority than any other HVAC setting; vice versa, when this object
receives a "0" logic value (windows closed), the device instantly disables the OFF operating mode and
the new operating mode is enabled automatically by the device according to the last command received
(HVAC mode or scene) or the HVAC mode installed before windows status activation.
The enabled flags are C (communication), W (written by bus).
The standard format of the object is 1.019 DPT_Window_Door, the size of the object is 1 bit and the
commands it receives are windows status open/close.
¾4.2.3 Scene
Using this communication object, the device is able to receive the execute and store scene commands
from the bus.
On receiving a store scene command, through a bus telegram to the communication object in question,
please remember that the device memorises the HVAC mode, operating type and any temporary forced
setpoint.
The enabled flags are C (communication), W (written by bus).
The standard format of the object is 18.001 DPT_SceneControl, the size of the object is 1 byte and the
commands it receives are execute/store scene.
¾4.2.4 Operating type input
Here you can configure the remote control of the device function type by bus command. When this
object receives a telegram with a "1" logic value, the device sets the operating type to HEATING,
indicated by a pilot light on the display, maintaining the same operating mode as before; vice versa,
when this object receives a telegram with a "0" logic value, the device sets the operating type to AIR
CONDITIONING, indicated by a pilot light on the display, maintaining the same operating mode as
before. In any case, it is however possible to modify the operating type using the local navigation menu
on the device.
The enabled flags are C (communication), W (written by bus).
The standard format of the object is 1.100 DPT_Heat/Cool, the size of the object is 1 bit and the
commands it receives are operating type commands: Heating/Air conditioning.