System 3000
Motion detector top unit 1.10 m Komfort BT, Motion detector top unit 2.20 m
Komfort BT
Settings for switch and dimming inserts
Parameters Setting options, default set-
ting
Explanation
EnOcean switch MAC address
Name
Single rocker
Left rocker
Right rocker
The Bluetooth wall transmitter must be con-
nected to the device in order to be able to op-
erate it. Enter the MAC address of the
Bluetooth wall transmitter here, select the
device button to be used for operation and as-
sign a name. Up to 8 Bluetooth wall transmit-
ters can be connected to the device.
Operating mode Automatic mode
Timer OFF
Timer ON
Continuous OFF
Continuous ON
Default setting: automatic
mode
Automatic: The load is switched depending on
motion and brightness.
Continuous OFF or ON: The load is perman-
ently switched off or on.
Timer OFF or ON: The load is switched off or
on for the specified time. Afterwards, the
device is in automatic mode again.
Setting timer OFF 0.5 - 5 hours
Default setting: 2 h
Time for which the load remains switched off
when the "Timer OFF" function is activated.
Setting timer ON 0.5 - 5 hours
Default setting: 2 h
Time for which the load remains switched on
when the "Timer ON" function is activated.
Run-on time 10 s ... 60 min
Default setting: 2 min
The load remains switched on for this time,
even if no more motion is detected or the am-
bient light is bright enough.
Dynamic self-
learning run-on
time
On, Off
Default setting: Off
Dynamic self-learning run-on time On:
The device automatically determines a run-on
time within specified limits and dynamically
from detected motion. In so doing, the run-on
time is increased if presence continues or de-
creased if absence is detected. The maximum
run-on time is the set run-on time. The
shortest run-on time is 10 seconds. For run-on
times from 5 minutes, the brief presence de-
tection function is also active.
Brightness
threshold
Motion detector: 5… 500 lx
Default setting: 10 lx
The load is switched on if the brightness value
falls below this value and if motion is detected.
Using the current
brightness
The current brightness can
be stored in a range of 5 to
500 lx.
Sets the brightness threshold parameter in the
app to the current brightness.
Sensor sensitivity 0, 25, 50, 75, 100%
Default setting: 100%
Individually adjust the sensitivity in 5 steps for
the left and the right sensor.
To restrict the detection field, switch off indi-
vidual sensors. To do this, set the sensitivity to
0%.
Reduced basic
sensitivity
On, Off
Default setting: Off
Reduced basic sensitivity On:
Reduced basic sensitivity for use in environ-
ments with interference sources.
12 / 16
32599722 10865948 13.07.2022