4Operation
Overview
4.1 Loop Resistance Measurement Mode
with the PROFiTEST0100S-II with
Suppression of RCCB Triggering
➭Connect the PROFiTESTDC-II to the system
under test:
The “Mains” lamp lights up green. The display
value is equal to or close to 0.
➭If the polarity lamp lights up, reverse the poles
at the mains connection.
➭Connect the PROFiTEST0100S-II via the
earthing contact outlet at the
PROFiTESTDC-II mains plug. Select posi-
tive half-wave for the RLoop range (loop resis-
tance).
➭Set the selector switch to the IFposition
and the slide switch to “undelayed”.
➭Press the “START” key at the
PROFiTESTDC-II.
The “Active” lamp lights up.
➭The “Measuring” lamp lights up after approxi-
mately 4 to 5 s.
The RCCB is disabled (disabling of the RCCB
lasts for approximately 30 s).
Magnetizing current is displayed in mA.
➭Measure loop resistance with the
PROFiTEST0100S-II with the rotary switch
in the “RLoop” position after “positive half-
wave to earth” has been selected in the
menu.
➭After the measurement has been completed,
wait until the “Measuring” lamp has gone out,
followed by the “Active” lamp about 6 s later.
Disconnect the instrument from the system.
Attention!
!The RCCB is disabled during operation and
measurement.
The RCCB must be tripped after measure-
ment with the PROFiTESTDC-II in order
to test for proper functioning.
Either activate the test button at the
RCCB, or perform a tripping test with the
PROFiTEST0100S-II.
Important Notes
If the “RLoop > max.” lamp lights up, loop resis-
tance is greater than approximately 8 Ω. Correct
measurement is impossible in this case. The fact
that the lamp may flicker during measurement is
of no consequence.
If the “Temperature” lamp lights up, disconnect
the PROFiTESTDC-II from the mains and allow it
to cool.
4.2 Tripping Test Operating Mode
for DC Components in AC-DC Sensitive RCCBs
4.2.1 With Rising DC Residual Current
and Measurement of Tripping Current
for Undelayed RCCBs
➭Connect the PROFiTESTDC-II to the system
under test:
The “Mains” lamp lights up green. The display
value is equal to or close to 0.
➭If the polarity lamp lights up, reverse the poles
at the mains connection.
➭Set the function selector switch to the IF
position and the slide swItch to “undelayed”.
➭Press the “START” key at the
PROFiTESTDC-II.
The “Active” lamp lights up.
Measurement Results:
a) Current rises until the RCD is tripped. Tripping
current is subsequently displayed for approxi-
mately 5 s.
or
b) If the RCD fails, current rises until saturation
current has been reached.
Saturation current is displayed in mA for
approximately 30 s, after which the displayed
current value again approaches 0.
Measurement RCCB Type Selector Switch Position Display
Loop Resistance Standard IFundelayed PROFiTEST0100S-II
Triggering Current AC-DC Sensitive IFundelayed PROFiTESTDC-II
Triggering Current AC-DC Sensitive, Delayed IFPROFiTESTDC-II
Time to Trip AC-DC Sensitive 10/30/100/300/500 mA PROFiTESTDC-II
S