manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Growatt
  6. •
  7. Batteries Pack
  8. •
  9. Growatt SYN 100-XH-30 User manual

Growatt SYN 100-XH-30 User manual

1 2 3 4 5 6 7
2
1
Screw torque
Power grid terminals
26.5 to 31 in*lbs
Ground terminal
13 in*lbs
3
SYN 100-XH-30
Grid
Grid
PE NL3 L2 L1 L1 L2 L3 N
PE
L1 L 2 L3 N L 1 L 2 L 3 N L1 L 2 L3 N L 1 L2 L3 N
GRID BYPASS INV ERT ER LOAD
2.4 Required tools
No.
Name
Size
No.
Name
Size
1
Flat-blade
screwdriver
Φ2&5 mm
2
Hammer
/
3
Allen wrench
Φ5 mm
4
Phillips
screwdriver
Φ5 mm
5
Electric drill
Φ6 mm
6
Wire stripper
/
7
Pliers
/
3.
Recommended cable specifications
Please prepare suitable cables for the connection of the SYN box following the recommended specifications, and the stripped length of the
cables is 10 mm.
Cable
Cable outer
diameter
Cable length
Grid input cable
4-6 AWG
10 m
Inverter input cable
6-8 AWG
20 m
Load output cable
6-8 AWG
20 m
Communication cable
22-26 AWG
20 m
4-6 AWG
10 m
L
10 mm
10 m
4-6 AWG
4-6 AWG
N
10 mm
10 m
PE
10 mm
Grid AC cable
20 m
6-8 AWG L
10 mm
20 m
6-8 AWG
6-8 AWG
N
10 mm
20 m
PE
10 mm
Load and lnverter AC cable
20 m
20m
22-26 AWG
22-26 AWG
L
10 mm
N
10 mm
Communication cable
3.1 Wiring instructions
3.1.1 Connecting SYN 100-XH-30 to the Grid
1. Remove the two screws on the upper cover of the SYN 100-XH-30 to open the upper cover, and do
not remove the cover inside the machine.
2. Twist the plastic cover printed with "Grid" counterclockwise, remove the five waterproof plugs, and
reserve five holes.
3. Route the five power grid cables (L1/L2/L3/N/PE) through the five holes and connect them to the
power grid input terminals and the ground copper bar. Screw torques for tightening the power grid
terminals and ground terminals are shown in the following table.
4. Finally, fasten the plastic cover clockwise. The wiring method is shown in Figure 3.
Note: PE cables need to be crimped with the O-type
terminal in the accessory bag, as shown in
Figure 2.
Connecting to the Grid
3.1.2 Connecting SYN 100-XH-30 to the Inverter
When connecting the SYN 100-XH-30 to the XH Inverter, you need to connect the AC power cables and the communication cables.
1.
2.
SYN 100-XH-30 Quick Guide
Overview
Installation
System overview 2.2 Installation requirements
2.1 Electrical parameters
1. Choose a suitable installation position. The SYN 100-XH-30 can be mounted on a solid wall, a stud
frame or a pole and keep it free from direct sunlight.
2. To ensure heat dissipation, please maintain at least a 300 mm clearance between the SYN 100-XH-
30 and other objects.
3. Place the mounting bracket against the wall/pole and mark the drilling hole positions.
4. Drill holes and mount the bracket. Ensure that the bracket is securely installed.
5. Install the SYN 100-XH-30 onto the mounting bracket.
1 2 3 4 5 67 8 9
10KTL
Normal Loads
Critical Loads
Inverter
Battery
Meter
Backup
Box
CT
Communication cable
Power cable
≤15°
≥300
≥300
≥300
≥500
21.1
5.3
28.1
365.0
486.3
92.5
8.0
7.1
134.7
120.2
Note:
1. The critical load power depends on the power rating
of the inverter and battery.
2. The off-grid function is only available when the XH
inverter is paired with the APX battery system and
the backup box.
Model name
SYN 100-XH-30
Nominal grid
voltage
3W/N/PE
230/400 a.c.V
Range of grid
voltage
312~485 a.c.V
Max. grid
current
125 a.c.A
Max.
continuous
grid current
90 a.c.A
Nominal grid
frequency
50/60Hz
Range of grid
frequency
45~65Hz
Max.
continuous
inverter input
current
58 a.c.A
Max. backup
output current
58 a.c.A
2.3 Installation steps
(1) Front panel (2) LED indicator (3) Screw for front panel (4) Mounting bracket
(9) Waterproof plugs
(5)Grid wiring port
(6) Inverter wiring port (7) Load wiring port (8) COM wiring port
Dimensions (Unit: mm)
Unit: mm
30.5 82
164
12
16
1 2 3 4 5 6 7
2
1
Screw torque
Power grid terminals
26.5 to 31 in*lbs
Ground terminal
13 in*lbs
3
SYN 100-XH-30
Grid
Grid
PE NL3 L2 L1 L1 L2 L3 N
PE
L1 L 2 L3 N L 1 L 2 L 3 N L1 L 2 L3 N L 1 L2 L3 N
GRID BYPASS INV ERT ER LOAD
2.4 Required tools
No.
Name
Size
No.
Name
Size
1
Flat-blade
screwdriver
Φ2&5 mm
2
Hammer
/
3
Allen wrench
Φ5 mm
4
Phillips
screwdriver
Φ5 mm
5
Electric drill
Φ6 mm
6
Wire stripper
/
7
Pliers
/
3.
Recommended cable specifications
Please prepare suitable cables for the connection of the SYN box following the recommended specifications, and the stripped length of the
cables is 10 mm.
Cable
Cable outer
diameter
Cable length
Grid input cable
4-6 AWG
10 m
Inverter input cable
6-8 AWG
20 m
Load output cable
6-8 AWG
20 m
Communication cable
22-26 AWG
20 m
4-6 AWG
10 m
L
10 mm
10 m
4-6 AWG
4-6 AWG
N
10 mm
10 m
PE
10 mm
Grid AC cable
20 m
6-8 AWG L
10 mm
20 m
6-8 AWG
6-8 AWG
N
10 mm
20 m
PE
10 mm
Load and lnverter AC cable
20 m
20m
22-26 AWG
22-26 AWG
L
10 mm
N
10 mm
Communication cable
3.1 Wiring instructions
3.1.1 Connecting SYN 100-XH-30 to the Grid
1. Remove the two screws on the upper cover of the SYN 100-XH-30 to open the upper cover, and do
not remove the cover inside the machine.
2. Twist the plastic cover printed with "Grid" counterclockwise, remove the five waterproof plugs, and
reserve five holes.
3. Route the five power grid cables (L1/L2/L3/N/PE) through the five holes and connect them to the
power grid input terminals and the ground copper bar. Screw torques for tightening the power grid
terminals and ground terminals are shown in the following table.
4. Finally, fasten the plastic cover clockwise. The wiring method is shown in Figure 3.
Note: PE cables need to be crimped with the O-type
terminal in the accessory bag, as shown in
Figure 2.
Connecting to the Grid
3.1.2 Connecting SYN 100-XH-30 to the Inverter
When connecting the SYN 100-XH-30 to the XH Inverter, you need to connect the AC power cables and the communication cables.
1.
2.
SYN 100-XH-30 Quick Guide
Overview
Installation
System overview 2.2 Installation requirements
2.1 Electrical parameters
1. Choose a suitable installation position. The SYN 100-XH-30 can be mounted on a solid wall, a stud
frame or a pole and keep it free from direct sunlight.
2. To ensure heat dissipation, please maintain at least a 300 mm clearance between the SYN 100-XH-
30 and other objects.
3. Place the mounting bracket against the wall/pole and mark the drilling hole positions.
4. Drill holes and mount the bracket. Ensure that the bracket is securely installed.
5. Install the SYN 100-XH-30 onto the mounting bracket.
1 2 3 4 5 67 8 9
10KTL
Normal Loads
Critical Loads
Inverter
Battery
Meter
Backup
Box
CT
Communication cable
Power cable
≤15°
≥300
≥300
≥300
≥500
21.1
5.3
28.1
365.0
486.3
92.5
8.0
7.1
134.7
120.2
Note:
1. The critical load power depends on the power rating
of the inverter and battery.
2. The off-grid function is only available when the XH
inverter is paired with the APX battery system and
the backup box.
Model name
SYN 100-XH-30
Nominal grid
voltage
3W/N/PE
230/400 a.c.V
Range of grid
voltage
312~485 a.c.V
Max. grid
current
125 a.c.A
Max.
continuous
grid current
90 a.c.A
Nominal grid
frequency
50/60Hz
Range of grid
frequency
45~65Hz
Max.
continuous
inverter input
current
58 a.c.A
Max. backup
output current
58 a.c.A
2.3 Installation steps
(1) Front panel (2) LED indicator (3) Screw for front panel (4) Mounting bracket
(9) Waterproof plugs
(5)Grid wiring port
(6) Inverter wiring port (7) Load wiring port (8) COM wiring port
Dimensions (Unit: mm)
Unit: mm
30.5 82
164
12
16
COM Port
XH Inverter
COM
SYN 100-XH-30
COM
Control Board
RS485 A
PIN 23
PIN 3
CN8
RS485 B
PIN 24
PIN 4
BOX.EN+
PIN 21
PIN 5
BOX.EN-
PIN 22
PIN 6
Screw torque
Inverter circuit breaker terminals
17.5 in*lbs
Ground terminal
13 in*lbs
Screw torque
Load breaker terminal
17.5 in*lbs
Ground terminal
13 in*lbs
Load
L1L2 L3 N
NL3 L2 L1 PE
PE
Backup Loads
SYN 100-XH-30
L1 L 2 L3 N L 1 L 2 L 3 N L1 L2 L3 N L1 L 2 L3 N
GRID BYPASS INV ERT ER LOAD
3.1.2.1 AC power cable connection:
3.1.2.2 Communication cable connection:
1. Twist the plastic cover printed with "Inverter" counterclockwise;
remove the five waterproof plugs, and reserve five holes.
2. Route the five cables of the inverter (L1/L2/L3/N/PE) through
the five holes, connect the cables to the inverter breaker terminals
(L1/L2/L3/N) and the ground copper bar. Screw torques for
tightening the inverter breaker terminals and ground terminals are
shown in the following table.
3. Finally, fasten the plastic cover clockwise. The wiring method is
shown below:
1. Twist the plastic cover printed with "COM" on the machine
counterclockwise; remove the waterproof plug, and reserve the
hole.
2. Route the two communication cables (A/B) (the twisted pair
cables are recommended) and the two BOX EN cables (EN+/EN-)
through the hole, connect them to the CN8 terminals on the control
board. Connect the other end of the cables to the COM terminals of
the inverter, and tighten the screws. The following table lists the
corresponding terminal pins. The wiring method is shown as follows:
3.1.3 Connecting SYN 100-XH-30 to the load
1. Twist the plastic cover printed with "Load" counterclockwise,
remove the five waterproof plugs, and reserve five holes.
2. Route the five load cables (L1/L2/L3/N/PE) through the five holes,
connect them to the load circuit breaker terminals (L1/L2/L3/N) and
the ground copper bar. Screw torques for tightening the load breaker
terminals and ground terminals are shown in the following table.
3. Finally, fasten the plastic cover clockwise. The wiring method is
shown to the right:
Connecting to the AC Loads
4. Indicator description
System state
Indicator status
Green
Red
On-grid Mode
On
Off
Back-up Mode
Blinking (On for 1s, and then Off for 1s)
Off
No communication with the inverter
Off
Blinking (on for 1s, and then Off for 1s)
System fault
Off
On
Firmware upgrade
When the upgrade starts, the yellow light is on or off for 10-20s, and then the yellow
light blinks at intervals of 2s (On for 1s and then Off for 1s).
5. System startup and shutdown operations
5.1 To start the system, please perform the following steps:
5.2 To shut down the system, please perform the following steps:
Shenzhen Growatt New Energy Co., Ltd.
4-13/F, Building A, Sino-German (Europe) Industrial Park,
Hangcheng Ave, Bao'an District, Shenzhen, China
+86 755 2747 1942
www.ginverter.com
T
E service@ginverter.com
W
7.
Service and contact
1. Disconnect the Inverter input breaker and the load input breaker on the SYN 100-XH-30 and then disconnect the power grid breaker.
2. Turn off the DC switch of the inverter.
3. Turn off the DC switch of the battery.
4. Wait for a while and all the indicators of the inverter, the battery, and the SYN 100-XH-30 will go off, indicating that the system is
powered off completely.
6.
Transfer to the bypass mode manually
When the SYN 100-XH-30 fails, it cannot transfer to the bypass mode automatically. To ensure uninterrupted power supply to loads, it can be
switched to the bypass mode manually.
1. Shut down the entire system. For details, please refer to Section 5.2.
2. Use a Phillips screwdriver to loosen the limit switch screw on the power bypass switch.
3. Slide the firmware to one end of the inverter switch.
4. Tighten the screw on the limit switch with a torque of 10.5 in* lbs / 1.2 N*m. Turn on the power bypass switch. The operation instructions
are shown below.
5. Power on the entire system. For details, please refer to section 5.1.
To manually transfer to the bypass mode, please proceed as follows:
1. lf the inverter is connected to a battery, turn the DC SWITCH on the battery to ON.
2. Set the DC SWITCH on the left side of the inverter to ON.
3. Turn on the inverter input breaker of the SYN 100-XH-30.
4. Enable the Backup Box function via inverter settings. For details, please refer to the XH inverter manual.
5. Turn on the grid breaker.
6. If the SYN 100-XH-30 indicator light turns green after completing the preceding steps, it indicates that the SYN 100-XH-30 is functioning
properly.
7. If you cannot power on the system with the instructions provided above, please contact Growatt.
Bypass Inverter Load Bypass Inverter Load Bypass Inverter Load
GR-UM-312-A-01
Download
Manual
Growatt New Energy
Connecting the communication cables to the XH Inverter
PE
ON
OFF
Inverter
SYN 100-XH-30
L1 L2 L3 N L 1 L2 L3 N L1 L2 L 3 N L1 L 2 L3 N
GRID BYPASS INV ERT ER LOAD
Connecting the AC cables to the XH Inverter
L1L2 L3 N
Inverter
NL1 L2
PE L3
COM
SYN 100-XH-30
L1 L2 L 3 N L1 L2 L3 N L1 L2 L 3 N L1 L 2 L 3 N
GRID BYPASS INV ERT ER LOAD
BOX.EN-
BOX.EN+
B
A
CN8
Inverter
1
6
COM
COM Port
XH Inverter
COM
SYN 100-XH-30
COM
Control Board
RS485 A
PIN 23
PIN 3
CN8
RS485 B
PIN 24
PIN 4
BOX.EN+
PIN 21
PIN 5
BOX.EN-
PIN 22
PIN 6
Screw torque
Inverter circuit breaker terminals
17.5 in*lbs
Ground terminal
13 in*lbs
Screw torque
Load breaker terminal
17.5 in*lbs
Ground terminal
13 in*lbs
Load
L1L2 L3 N
NL3 L2 L1 PE
PE
Backup Loads
SYN 100-XH-30
L1 L 2 L3 N L 1 L 2 L 3 N L1 L2 L3 N L1 L 2 L3 N
GRID BYPASS INV ERT ER LOAD
3.1.2.1 AC power cable connection:
3.1.2.2 Communication cable connection:
1. Twist the plastic cover printed with "Inverter" counterclockwise;
remove the five waterproof plugs, and reserve five holes.
2. Route the five cables of the inverter (L1/L2/L3/N/PE) through
the five holes, connect the cables to the inverter breaker terminals
(L1/L2/L3/N) and the ground copper bar. Screw torques for
tightening the inverter breaker terminals and ground terminals are
shown in the following table.
3. Finally, fasten the plastic cover clockwise. The wiring method is
shown below:
1. Twist the plastic cover printed with "COM" on the machine
counterclockwise; remove the waterproof plug, and reserve the
hole.
2. Route the two communication cables (A/B) (the twisted pair
cables are recommended) and the two BOX EN cables (EN+/EN-)
through the hole, connect them to the CN8 terminals on the control
board. Connect the other end of the cables to the COM terminals of
the inverter, and tighten the screws. The following table lists the
corresponding terminal pins. The wiring method is shown as follows:
3.1.3 Connecting SYN 100-XH-30 to the load
1. Twist the plastic cover printed with "Load" counterclockwise,
remove the five waterproof plugs, and reserve five holes.
2. Route the five load cables (L1/L2/L3/N/PE) through the five holes,
connect them to the load circuit breaker terminals (L1/L2/L3/N) and
the ground copper bar. Screw torques for tightening the load breaker
terminals and ground terminals are shown in the following table.
3. Finally, fasten the plastic cover clockwise. The wiring method is
shown to the right:
Connecting to the AC Loads
4. Indicator description
System state
Indicator status
Green
Red
On-grid Mode
On
Off
Back-up Mode
Blinking (On for 1s, and then Off for 1s)
Off
No communication with the inverter
Off
Blinking (on for 1s, and then Off for 1s)
System fault
Off
On
Firmware upgrade
When the upgrade starts, the yellow light is on or off for 10-20s, and then the yellow
light blinks at intervals of 2s (On for 1s and then Off for 1s).
5. System startup and shutdown operations
5.1 To start the system, please perform the following steps:
5.2 To shut down the system, please perform the following steps:
Shenzhen Growatt New Energy Co., Ltd.
4-13/F, Building A, Sino-German (Europe) Industrial Park,
Hangcheng Ave, Bao'an District, Shenzhen, China
+86 755 2747 1942
www.ginverter.com
T
E service@ginverter.com
W
7.
Service and contact
1. Disconnect the Inverter input breaker and the load input breaker on the SYN 100-XH-30 and then disconnect the power grid breaker.
2. Turn off the DC switch of the inverter.
3. Turn off the DC switch of the battery.
4. Wait for a while and all the indicators of the inverter, the battery, and the SYN 100-XH-30 will go off, indicating that the system is
powered off completely.
6.
Transfer to the bypass mode manually
When the SYN 100-XH-30 fails, it cannot transfer to the bypass mode automatically. To ensure uninterrupted power supply to loads, it can be
switched to the bypass mode manually.
1. Shut down the entire system. For details, please refer to Section 5.2.
2. Use a Phillips screwdriver to loosen the limit switch screw on the power bypass switch.
3. Slide the firmware to one end of the inverter switch.
4. Tighten the screw on the limit switch with a torque of 10.5 in* lbs / 1.2 N*m. Turn on the power bypass switch. The operation instructions
are shown below.
5. Power on the entire system. For details, please refer to section 5.1.
To manually transfer to the bypass mode, please proceed as follows:
1. lf the inverter is connected to a battery, turn the DC SWITCH on the battery to ON.
2. Set the DC SWITCH on the left side of the inverter to ON.
3. Turn on the inverter input breaker of the SYN 100-XH-30.
4. Enable the Backup Box function via inverter settings. For details, please refer to the XH inverter manual.
5. Turn on the grid breaker.
6. If the SYN 100-XH-30 indicator light turns green after completing the preceding steps, it indicates that the SYN 100-XH-30 is functioning
properly.
7. If you cannot power on the system with the instructions provided above, please contact Growatt.
Bypass Inverter Load Bypass Inverter Load Bypass Inverter Load
GR-UM-312-A-01
Download
Manual
Growatt New Energy
Connecting the communication cables to the XH Inverter
PE
ON
OFF
Inverter
SYN 100-XH-30
L1 L2 L3 N L 1 L2 L3 N L1 L2 L 3 N L1 L 2 L3 N
GRID BYPASS INV ERT ER LOAD
Connecting the AC cables to the XH Inverter
L1L2 L3 N
Inverter
NL1 L2
PE L3
COM
SYN 100-XH-30
L1 L2 L 3 N L1 L2 L3 N L1 L2 L 3 N L1 L 2 L 3 N
GRID BYPASS INV ERT ER LOAD
BOX.EN-
BOX.EN+
B
A
CN8
Inverter
1
6
COM

Other Growatt Batteries Pack manuals

Growatt APX 5.0P-B1 User manual

Growatt

Growatt APX 5.0P-B1 User manual

Growatt WIT 28-55K-HU-US L2 User manual

Growatt

Growatt WIT 28-55K-HU-US L2 User manual

Growatt APX 5.0-30.0P-S0 User manual

Growatt

Growatt APX 5.0-30.0P-S0 User manual

Growatt APX 5.0P-S0-US User manual

Growatt

Growatt APX 5.0P-S0-US User manual

Growatt Future-H Series User manual

Growatt

Growatt Future-H Series User manual

Growatt ARK 2.5H-A1 User manual

Growatt

Growatt ARK 2.5H-A1 User manual

Growatt ARK 2.5H-A1 Operating and maintenance instructions

Growatt

Growatt ARK 2.5H-A1 Operating and maintenance instructions

Growatt Hope 3.3L-C1 User manual

Growatt

Growatt Hope 3.3L-C1 User manual

Growatt INFINITY 1300 User manual

Growatt

Growatt INFINITY 1300 User manual

Growatt ARK 2.5H-A1 User manual

Growatt

Growatt ARK 2.5H-A1 User manual

Growatt Hope 5.5L-A1 User manual

Growatt

Growatt Hope 5.5L-A1 User manual

Growatt APX 5.0-30.0P-S1 User manual

Growatt

Growatt APX 5.0-30.0P-S1 User manual

Popular Batteries Pack manuals by other brands

SUEX 71425 USER INSTRUCTION MANUAL AND WARNINGS

SUEX

SUEX 71425 USER INSTRUCTION MANUAL AND WARNINGS

FoxESS LV54 Quick installation guide

FoxESS

FoxESS LV54 Quick installation guide

Phonic BP-RG user manual

Phonic

Phonic BP-RG user manual

Crestron ST-BTPN Operation and installation guide

Crestron

Crestron ST-BTPN Operation and installation guide

Bebob B90CineHS user manual

Bebob

Bebob B90CineHS user manual

Fresh 'N Rebel 2PB12000 v1 001 manual

Fresh 'N Rebel

Fresh 'N Rebel 2PB12000 v1 001 manual

EnerSys PowerSafe OPzV Installation, operation & maintenance instructions

EnerSys

EnerSys PowerSafe OPzV Installation, operation & maintenance instructions

NocoXgrid XGB3 user guide

NocoXgrid

NocoXgrid XGB3 user guide

SEPLOS SUTEN-W user manual

SEPLOS

SEPLOS SUTEN-W user manual

ResMed Power Station II user guide

ResMed

ResMed Power Station II user guide

Panasonic CF-VZSU53W operating instructions

Panasonic

Panasonic CF-VZSU53W operating instructions

Pride Removable Battery Pack SilverStar operation instruction

Pride

Pride Removable Battery Pack SilverStar operation instruction

Syscom Video MR3000C user manual

Syscom Video

Syscom Video MR3000C user manual

Chloride ONEAC Installation

Chloride

Chloride ONEAC Installation

Bretford 1024 user guide

Bretford

Bretford 1024 user guide

National Instruments SCXI-1382 installation guide

National Instruments

National Instruments SCXI-1382 installation guide

ASL INTERCOM V2000 installation guide

ASL INTERCOM

ASL INTERCOM V2000 installation guide

Sunoptic Surgical SSL-2054BE Operator's manual

Sunoptic Surgical

Sunoptic Surgical SSL-2054BE Operator's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.