
HL Series Electric Linear Actuator
Installation Operation & Maintenance Manual
Doc No. : HumG-HL-21 Rev2 Page 4 / 26 Valve Automation Leader, HKC
2.1.2. Applied Standard
① [IEC60079-0:2017(Ed.7.0 +IS01, EN60079-0:2012 +A11-2013
② IEC60079-1:2014 (Ed.7), EN60079-1:2014
③ IEC60079-31:2013(Ed.2), EN60079-31:2014 -------------- 20 Rev0]
2.1.3. Certification
① [IECEx: for HL-05kN ~ HL-25kN, IECEx EPS 18.0123X
Ex db IIB T4 Gb, Ex tb IIIC 135’C Db, Ta -20℃ to +60℃,
② ATEX: for HL-05kN ~ HL-25kN, EPS 18 ATEX 1 246 X, CE 0344
II 2 G Ex db IIB T4 Gb, II 2 D Ex tb IIIC 135’C Db, Ta -20℃ to +60℃
③ KCs(KOSHA) for standard type HL-05/07kN with LCU Unit, 10-AV2BO-XXXX,
for standard type HL-10/12/15kN with LCU Unit, 10-AV2BO-XXXX,
for standard type HL-18/20/25kN with LCU Unit, 10-AV2BO-XXXX,
Ex d IIB T4, -20℃ ~ +60℃
KCs(KOSHA) for standard type HL-05/07kN with LCU Unit, 10-AV2BO-XXXX,
for standard type HL-10/12/15kN with LCU Unit, 10-AV2BO-XXXX,
for standard type HL-18/20/25kN with LCU Unit, 10-AV2BO-XXXX,
Ex tD A21 IP6X T135℃
④ EAC: 1Ex d IIB T4 Gb X, -60℃ ~ +60℃ ----------------------------- 20 Rev.0]
⑤ [CCC: Ex d IIB T4 Gb, Ex tD A21 IP6X T135℃, CNEX 2021 3123 0700 0206 ------- 21 rev1]
Notes :
Sealing devices must be used and shall be fitted directly at enclosure wall when using conduit.
Cable glands shall be suitable for the environment and shall be certified as flameproof if used in Zone
1 application.
Cable glands and conduit to be installed minimum 6 full threads and the length of thread is minimum
8mm.
Temperature of cable entry is maximum 100℃. Heat resistance wire is recommended when you install.
Ex db and/or Ex tb certified cable glands suitable for 100℃ must be used.
Users should confirm all information about dimensions of flamepath with the manufacturer
All information about the material and the allowance of LCU fasteners
- Fasteners with yield stress≥ 210MPa (stainless steel)
- [Bolts type : M6*1.25, M8*1.25, M10*1.5, M12*1.75 (Tolerance Fit 6g) ---- 20 Rev0]
Cable connection : Refers to the Appendix Ⅱ (Wiring Diagram)
For cable entries or conduit entries that are not used, user or installer shall close by certified blanking
elements(stopping plugs) so that the flameproof properties of the enclosure are maintained.
Always ground the enclosure in accordance with local electric codes. The most effective enclosure
grounding method is a direct connection to earth ground with minimal impedance. Methods for
grounding the enclosure include:
- Internal ground connection : The internal ground is located in the terminal block #1. Refer to the
enclosed wiring diagram.
- External ground connection : The ground lug is located on the centre of cable entries.
- For more information, refer to the Appendix Ⅲ (Grounding)
[Stainless steel name plate for the flame proof and dust ignition proof type shall be permanently attached
by rivets on the cover. ----- 20 Rev0]
2.2. Initial inspection
When the user receives the actuators, inspect the condition of the product and ensure the name plate
comparing with order sheet.
2.2.1. Remove packing wrap or wooden box carefully. Inspect the product for any physical damage that
may have occurred during shipment.
2.2.2. Check the product specification with product ordered. If an wrong product have been shipped,
immediately inform to our coordinator.
2.3. Storage
Actuators must be stored in a clean, cool and dray area. The unit should be stored with the cover
installed and the cable entry openings sealed. Storage must be off the floor, covered with a sealed dust
protector. When actuators are to be stored outdoor, they must be stored off the ground, high enough to
prevent from being immersed in water or buried in snow.