HKC HQ Series Instruction manual

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev0 Page 1 / 21 Valve Automation Leader HKC
Quarter-turn Electric Actuator
HQ-Series (XC-Series)
Installation, Operation & Maintenance Manual
Address :
26, Emtibeui 28-ro, Siheung-si, Gyeonggi-do, (15119) Republic of Korea
Tel : +82-31-488-8266, Fax : +82-31-488-8269, Home page : www.hkcon.co.kr, email : hkcon@hkcon.co.kr

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 2 / 21 Valve Automation Leader HKC
Contents
1. INTRODUCTION ............................................................................................................. 3
1.1. Purpose ............................................................................................................................................... 3
1.2. Safety Notices .................................................................................................................................... 3
2. PRODUCT IDENTIFICATION ......................................................................................... 3
2.1. Product Identification....................................................................................................................... 3
2.2. Initial inspection ................................................................................................................................ 4
2.3. Storage ................................................................................................................................................ 4
3. GENERAL INFORMATION AND FEATURES............................................................... 5
3.1. General ................................................................................................................................................ 5
3.2. External Parts for Standard Models .............................................................................................. 7
3.3. Internal Parts for Standard Models ............................................................................................... 7
4. INSTALLATION INSTRUCTION .................................................................................... 7
4.1. Pre-Installation for ............................................................................................................................ 7
4.2. Actuator Mounting ........................................................................................................................... 8
4.3. Limit Switch Setting .......................................................................................................................... 9
4.4. Torque Switch Setting ....................................................................................................................10
4.5. Counter-Clockwise to Close Setting ............................................................................................10
4.6. Mechanical Travel Stop Adjustment............................................................................................10
4.7. Setting potentiometer (Replacing and setting) ........................................................................10
4.8. Current Position Transmitter – CPT (Optional) .........................................................................11
4.9. [Proportional Control Unit (PCU) .................................................................................................11
4.10. [AC/DC Multi-Board........................................................................................................................12
5. WIRING .......................................................................................................................... 13
5.1. Electrical Connections and Preliminary Test ..............................................................................13
6. MAINTENANCE ............................................................................................................ 14
6.1. Maintenance .....................................................................................................................................14
6.2. Tools ..................................................................................................................................................14
7. TROUBLE SHOOTING .................................................................................................. 14
7.1. The actuator does not respond ....................................................................................................14
7.2. The actuator is supplied with power but does not operate ..................................................15
7.3. Actuator runs erratically ................................................................................................................15
7.4. Optional Equipment(s) ...................................................................................................................15
8. INSTALLATION AND MAINTENANCE TIPS ............................................................ 15
APPENDIXⅠ. HQ(XE)-SERIES CODING SYSTEM ........................................................... 17
APPENDIX II: WIRING DIAGRAM ..................................................................................... 18
APPENDIX III: GROUNDING .............................................................................................. 21

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 3 / 21 Valve Automation Leader HKC
1. Introduction
1.1. Purpose
This Installation and operating manual explains how to install, operate and maintain HQ electric actuators.
1.2. Safety Notices
Safety notices in this manual outline precaution the user must take to reduce the risk of personal injury
and damage to the equipment. The user(s) must read these instructions before the installation, operation
or maintenance of HQ-series electric actuators.
DANGER : Refers to personal safety. Alerts the user to danger or harm. The hazard or
unsafe practice will result in severe injury or death.
WARNING : Refers to personal safety. Alerts the user to potential danger.
Failure to follow warning notices could result in personal injury or death.
CAUTION :
Directs the user
’
s attention to general precautions that, if not
followed, could r
e-
sult in personal injury and/or equipment damage.
Notes: Highlighted information is critical to the user’s understanding of the actuator’s instal-
l
a
tion and operation.
Note
HQ and XC shown below are same Actuators (Hereafter referred to as HQ)
HQ-008(XC-690), HQ-010(XC-860), HQ-015(XC-1350), HQ-020(XC-1700)
HQ-030(XC-2640), HQ-050(XC-4400), HQ-080(XC-6900), HQ-120(XC-10500),
HQ-200(XC-17500), HQ-300(XC-25690)
2. Product Identification
2.1. Product Identification
[The actuator name plate is located on the enclosure cover. The name plate contains the following: --- 20
Rev0]
2.1.1. Marking
① [General
HQ logo (trade mark), Model, Electrical power supply, Type, Rated current, Torque,
Serial No., Operating time (seconds) and Option. ----- 20 Rev0]
② [Flameproof for CSA, IECEx/ATEX, KCs, and EAC ------ 20 Rev0]

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 4 / 21 Valve Automation Leader HKC
2.1.2. Applied Standard
① IEC60079-0:2011(Ed.6 +IS01), EN60079-0:2012+A11
② IEC60079-1:2014-06 (Ed.7), EN60079-1:2014
③ IEC60079-31:2013(Ed.2), EN60079-31:2014
④ CAN/CSA C22.2 No. 139-13 / UL 429 seventh ed. ---- 17 Rev0]
2.1.3. Certification
① [IECEx: for HQ-008 ~ HQ-300 with LCU, IECEx DEK 16.0042X
Ex db IIB T4 Gb, Ta -20℃ to +60℃, Ex tb IIIC 135℃ Db
② ATEX: for HQ-008 ~ HQ-300 with LCU, DEKRA 16ATEX0083 X, CE 0344
II 2 G Ex db IIB T4 Gb, Ta -20℃ to +60℃, II 2 D Ex tb IIIC 135℃ Db ----- 18 Rev0]
③ [KCs Ex d IIB T4, -20℃ ~ +60℃:
for HQ-008/010, 제 2020-BO-0016 호, for HQ-015/020, 제 2020-BO-0017 호,
for HQ-030~060, 제 2020-BO-0018 호, for HQ-080~300, 제 2020-BO-0019 호
KCs Ex tD A21 IP6X T135℃, -20℃ ~ +60℃:
for HQ-008/010, 제 2020-BO-0012 호, for HQ-015/020, 제 2020-BO-0013 호,
for HQ-030~060, 제 2020-BO-0014 호, for HQ-080~300, 제 2020-BO-0015 호 – 20 Rev0]
④ CSA: for HQ-008 ~ HQ-300, 249581 (except HQ-060) Hazardous location
Class I, Division 1, Group C, D, T4 Ex d IIB Gb T4
Class I, Zone 1, AEx d IIB Gb T4
[Ambient Temperature -20℃ to +60℃ --- 21 r0], Enclosure rating : Type 4, 4X, 6, IP66, IP67
Cable entry : 2 x NPT 3/4” Female
⑤ CSA: for HQ-008 ~ HQ-300, 249581 (except HQ-060) Ordinary location
Note :
Sealing devices must be used and shall be fitted directly at enclosure wall when using conduit.
Cable glands shall be suitable for the environment and shall be certified as flameproof if used in
Zone 1 application.
Cable glands and conduit to be installed minimum 6 full threads and the length of thread is min-
imum 8mm.
Temperature of cable entry is maximum 90℃. Heat resistance wire is recommended when you in-
stall.
Ex d certified cable glands suitable for 90℃ must be used.
Users should confirm all information about dimensions of flamepath with the manufacturer
All information about the material and the allowance of LCU fasteners. [However LCU is not apply
to CSA items. --- 17 rev1]
Fasteners with yield strength ≥ 210MPa (stainless steel)
Bolts type : M5*0.8, M6*1, M8*1.25, M10*1.5, M12*1.75 (Tolerance Fit 6g)
Cable connection : Refers to the Appendix Ⅱ (Wiring Diagram)
For cable entries or conduit entries that are not used, user or installer shall close by certified
blanking elements (stopping plugs) so that the flameproof properties of the enclosure are main-
tained.
Always ground the enclosure in accordance with local electric codes. The most effective enclosure
grounding method is a direct connection to earth ground with minimal impedance. Methods for
grounding the enclosure include:
Internal ground connection: The internal ground is located in the terminal block #1. Refer to the
enclosed wiring diagram.
External ground connection: The ground lug is located on the centre of cable entries.
For more information, refers to the Appendix Ⅲ (Grounding)
[Stainless steel name plate for the flame proof and dust ignition proof type shall be permanently
attached by rivets or screw on the cover. ----- 20 Rev0]
2.2. Initial inspection
When the user receipts the actuator, inspect the condition of the product and ensure the name plate com-
paring with order sheet.
2.2.1 Remove packing wrap or wooden box carefully. Inspect the product for any physical damage that
may have occurred during shipment.
2.2.2 Check the product specification with product ordered. If a wrong product has been shipped, imme-
diately report to our coordinator.
2.3. Storage

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 5 / 21 Valve Automation Leader HKC
Actuators must be stored in clean, cool and dry area. The unit shall be stored with the cover installed and
the conduit openings sealed. Storage must be off the floor, covered with a sealed dust protector.
When actuators are stored outdoor, they must be stored off the ground, high enough to prevent being
immersed in water or buried in snow.
3. General Information and Features
3.1. General
HKC HQ(XC) series electric actuators are designed for the operation of industrial valves, e.g. butterfly valves
and ball valves. Torque ranges of actuators are from 80Nm to 3,000Nm (690 In-Lbs to 25,900 In-Lbs), cur-
rently ten models are available
3.1.1. Flameproof (CSA Approval)
HKC A-T
Controls
Input Power
Full Load
Current(A)
Locked Rotor
Current(A)
Operating
time(sec.)
50/60Hz
Max.
Bore
size
Max. output
Torque, Nm (in-lbs)
Duty cycle
IEC60034-1 (S4 %)
Weight
kg
Type
Type ac 50/60 Hz
or dc
ac 50/60 Hz
or dc 90° mm On-Off Modulation
On-Off
Modula-
tion
HQ-008
XC-690
110 V ac 1.1 / 1.2 1.3 / 1.4 23 / 20 Ø 20
80 (690) 65 (550) 40 40 7.4
220 V ac 0.6 / 0.6 0.7 / 0.7 23 / 20 80 (690) 65 (550) 40 40
24V dc, ac/dc
5.0 12.8 17 70 (620) 65 (560) 30 30
12V dc, ac/dc
13.5 21.7 11 40 (350) 35 (315) 30 30
HQ-010
XC-860
110 V ac 1.1 / 1.2 1.3 / 1.4 23 / 20 Ø 20
100 (860) 80 (680) 40 40 7.4
220 V ac 0.6 / 0.6 0.7 / 0.7 23 / 20 90 (790) 72 (630) 40 40
24V dc, ac/dc
6.3 12.8 20 80 (700) 72 (630) 30 30
12V dc, ac/dc
13.5 21.7 18 50 (440) 45 (400) 30 30
HQ-015
XC-1350
110 V ac 1.9 / 2.0 2.4 / 2.5 25 / 21 Ø 22
150 (1,350)
130 (1150) 70 40 16.6
220 V ac 0.9 / 1.0 1.1 / 1.2 28 / 23 150 (1,350)
130 (1150) 35 40
24V dc, ac/dc
6.0 16.9 22 150 (1,350)
130 (1150) 40 40
HQ-020
XC-1700
110 V ac 2.2 / 2.3 2.4 / 2.5 25 / 21 Ø 22
200 (1,700)
160 (1360) 70 40 16.6
220 V ac 1.0 / 1.1 1.1 / 1.2 28 / 23 180 (1,590)
145 (1270) 35 40
24V dc, ac/dc
7.4 16.9 22 160 (1,410)
145 (1270) 40 40
HQ-030
XC-2640
110 V ac 2.0 / 2.3 3.0 / 2.9 31 / 26 Ø 35
300 (2,640)
240 (2110) 70 40 22
220 V ac 1.3 / 1.3 1.5 / 1.4 31 / 26 260 (2,300)
220 (1900) 40 40
24V dc, ac/dc
8.9 30.8 32 240 (2,120)
220 (1900) 35 30
HQ-050
XC-4400
110 V ac 3.8 / 4.5 4.9 / 5.0 35 / 29 Ø 35
450 (3,980)
360 (3180) 30 30 23
220 V ac 1.5 / 1.9 2.5 / 2.4 35 / 29 450 (3,980)
360 (3180) 30 30
HQ-080
XC-6900
110 V ac 5.0 / 5.1 7.4 / 7.3 37 / 31 Ø 45
800 (6,900)
640 (5520) 30 30 29
220 V ac 2.2 / 2.4 3.9 / 3.8 41 / 34 800 (6,900)
640 (5520) 30 30
HQ-120
XC-10500
110 V ac 5.4 / 5.4 7.4 / 7.3 37 / 31 Ø 45
1,100 (9,600)
880 (7680) 30 30 29
220 V ac 3.3 / 3.4 3.9 / 3.8 41 / 34 940 (8,300)
750 (6640) 30 30
HQ-200
XC-17500
110 V ac 5.7 / 5.8 7.4 / 7.3 112 / 93 Ø 65
2,000 (17,500)
1600 (14000)
30 30 75
220 V ac 2.2 / 2.4 3.9 / 3.8 112 / 93 2,000 (17,500)
1600 (14000)
30 30
HQ-300
XC-25900
110 V ac 6.3 / 6.3 7.4 / 7.3 112 / 93 Ø 65
3,000 (25,900)
2400 (20720)
30 30 75
220 V ac 3.3 / 3.4 3.9 / 3.8 112 / 93 3,000 (25,900)
2400 (20720)
30 30
[Notes : Refer to CSA C of C ---- 19 Rev.0]
3.1.2. HQ(XE) Explosion proof Technical Data (Standard)
Enclosure Rated
Weatherproof IP66, IP67, NEMA 4, 4X
&
6
Enclosure
High grade aluminium alloy,
Anti
-
corrosion coated
Power Supply
1
1
0
/
220
Vac
1 P
h 50/60Hz,
12 / 24 V ac/dc 50/60Hz [with ACDM-200 ac/dc card of HKC---17 rev1]
Duty type 1) S4 30%~70% / S2 30min (IEC 60034-1)
Motor Squirrel caged induction motor
Limit Switches
2 x open/close SPDT, 250
V
ac
1
6
A rating
Auxiliary Limit Switches
2 x open/close SPDT, 250 Vac 16A rating (except HQ-008/010)-17 Rev0]
Torque Switches
Open/close SPDT, 250V
ac
10A
r
ating (except HQ
-
008
/010
)
-
17 Rev0]
Stall Protection
Built
–
in thermal protection
Travel Angle
90 degree +/
-
10%
Indicator Continuous position indicator
Manual Override Declutchable manual override
Self-Locking By means of worm gear
Mechanical Travel Stops
2 x external adjustable mechanical travel stops
Cable
Entries
2 x NPT 3/4
”
for Ex db

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 6 / 21 Valve Automation Leader HKC
Lubrication
Grease moly EP
Ambient Temperature
-
20
℃
~ +
6
0
℃
(except on CPT)
External Coating
Dry powder polyester
3.1.3. HQ(XE) Optional Technical Data (Optional)
EXD
Flame
proof
enclosure (Ex db II B T4 Gb IP67)
WTA
Watertight enclosure (IP68 10m / 72hr)
PIU
Potentiometer unit (0~1KΩ)
PCU
Proportional control unit (with DHC
-
100 ac, DMC
-
102 dc card of Peaktronics)
---
17 rev1]
ATS
Additional torque switches (SPDT X 2
ea,
250V
ac,
16A Rating)
CPT
Current position transmitter(output 4~20mA
dc
)
ALS
Additional limit switches (SPDT X 2
ea,
250 V
ac,
16A Rating)
LPA
Lever plate actuator
ADCM
ac/dc conversion card (12V: HQ 008/010, 24V: HQ 008~030)
---
17 Rev0]
3.1.4. Duty Cycle *1
[Duty cycle data were indicated Clause 3.1.1 Standard Technical Data.----- 15 Rev.1]
Exceeding the actuator’s rated duty cycle may cause thermal overload.
Note *1
Type of duty according to VDE 0530 / IEC 60034-1
Short
–
time duty S2
Intermittent duty S4
The operation time at a constant load is
short, so that thermal equilibrium is not
reached. The pause is long enough for the
machine to cool down to ambient tempera-
ture. The duration of the short –time opera-
tion is limited to 15min (10min, 30min)
The duty is a sequence of identical cycles which
consist of starting time, operation time with con-
stant load and rest period. The rest period allows
the machine to cool down so that thermal equilibri-
um is not reached. The relative on-time at S4-25%
or S4-50% is limited to 25% and 50% respectively.
3.1.5. Space Heater
Condensation in the actuator is possible due to wide fluctuation of the ambient temperature. The heat-
er integrated in the control unit prevents from this in general.
Ceramic housing with thermostat to prevent over heating with 60℃ set temperature
Heating element Self-regulating
Voltage ranges(HQ-008~010) 110 V ac 5W 4.5KΩJ
(based on control power) 220 V ac 5W 18KΩJ
24 V ac/dc ---17 R0] 5W 200ΩJ
12 V ac/dc ---17 R0] [5W 56ΩJ—21 r1]
Voltage ranges(HQ-015~300) 110 V ac 10W 2KΩJ
(based on control power) 220 V ac 10W 8KΩJ
24 V ac/dc (015~030 only) ---17 R0] 10W 100ΩJ
3.1.6. Hand wheel and Declutching
HQ actuators are provided a declutchable manual override system.
① In order to manually operate the actuator, pull the manual override
engagement lever towards the hand wheel until it remains in position.
② Turn the handwheel until the valve reaches the required position
③ Turn clockwise to close and counter-clockwise to open
Note ;
The override engagement lever returns automatically to auto
position when the actuator is operated electrically.
3.1.7. Lubrication
HQ is a totally enclosed unit with a permanently lubricated gear train (Moly EP Grease). Once installed
lubrication should not be required. However, periodic preventative maintenance will extend the operat-
ing life of the actuator.

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 7 / 21 Valve Automation Leader HKC
3.2. External Parts for Standard Models
3.2.1. HQ-008(XC-690) ~ HQ-120(XC-10500)
3.2.2. HQ-200(XC-17500) ~ HQ-300(XC-25900) (Actuator + Gear Box)
3.3. Internal Parts for Standard Models
Note ;
HQ-008(XC-690)~010(XC-860) does not contain torque switch assembly
4. Installation Instruction
4.1. Pre-Installation for
4.1.1. Use in general service
Verify the actuators nameplate to ensure correct model number, torque output, operating speed, volt-
age and enclosure type before installation or use.
It is important to verify that the torque output of the actuator is appropriate for the torque require-
ments of the valve and that the duty cycle of the actuator is appropriate for the intended application.
HQ- 008(XC-690)~300(XC-25900)
Limit Switch
Assembly
Capacitor
Motor
Terminal
Block
Torque Switch
Assembly
Window & Indicator
Top Cover
Body
Hand Wheel
Cable
Entries
Base
Lever Mechanical
Travel Stoop
Window &
Indicator
Top Cover
Body
Hand
W
heel
Conduit
Entries
Base
Lever
Gear Box
Mechanical
Travel Stop

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 8 / 21 Valve Automation Leader HKC
4.1.2. using in potentially explosive atmosphere
Model
HQ
-
. . .
3
.
0
. . .
0
1)
Type of
protection
[
CSA
Class I,
Division
1, Group C, D, T4
,
Ex d IIB
Gb
T4
,
Class I, Zone 1, AEx d IIB Gb T4 ---17 Rev1]
Ambient
Temperature
-
20 ℃ ~ +60 ℃
If remained openings on the enclosure after installation for use in potentially explosive atmosphere,
the hole shall be blanked with a certified blanking element suitable for protection of Ex db IIC or
Ex tb IIIC respectively. ----- 17 Rev0]
Danger: Installation, commissioning, maintenance, repairs and modification work must only
be performed by qualified personnel with extensive knowledge on how to work on explo-
sion-proof electrical equipment.
Note :
1) Further information should be used of the HQ electric actuator catalogue.
Refer to the Cl.2.2 Initial inspection of this manual.
Warning :
Read this installation and maintenance manual carefully and completely before attempting to in-
stall, operate, or troubleshoot the HKC actuator.
4.2. Actuator Mounting
Note : Prior to mounting the part-turn actuator must be checked for any damage.
Damaged parts must be replaced by original spare parts.
4.2.1. Mounting is most easily done with the valve shaft pointing vertically upward. But mounting is also
possible in any other position; the actuator may be mounted in any position.
4.2.2. The HQ-series electric actuators are supplied with a female drive output. The ISO5211 bolt patterns
are provided for actuator mounting. The actuator drive bush is removable for ease of machining. It
is mandatory for the actuator to be firmly secured to a sturdy mounting bracket or directly mount-
ed to the valves’ ISO mounting pad. High tensile bolts or studs with spring locking washers must be
used.
4.2.3. The valve output shaft must be in lined with the actuator output drive to avoid side-loading the
shaft. To avoid backlash, flexibility in the mounting bracket or mounting should not be allowed.
CAUTION:
Do not attempt to work on your HKC actuator without first shutting off the incoming
power.
Do not attach ropes or hooks to the hand wheel for the purpose of lifting by hoist
4.2.4. Actuator Mounting Base Details (ISO 5211)
4-M8 Tap, Dp 12
P.C.D Ø70
(ISO 5211 F07)
HQ-008/010
HQ-015/020
4-M10 Tap, Dp 15
P.C.D Ø102 (F10)
4-M8 Tap, Dp 12
P.C.D Ø70 (F07)
HQ
-
030/050/060
4
-
M12 Tap, Dp 18
P.C.D Ø125 (F12)
4
-
M10 Tap, Dp 15
P.C.D Ø102
(F10)

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 9 / 21 Valve Automation Leader HKC
4.2.5. Actuator Drive Bushing
4.3. Limit Switch Setting
4.3.1. Manually rotate the hand wheel of the actuator to fully closed position
4.3.2. Using a hex wrench, loosen the set screw in the CLOSE limit switch cam
4.3.3. Rotate the CLOSE cam towards CW limit switch level until the switch ‘clicks’ (see Figure 1)
4.3.4. Tighten the set screw with the hex wrench
4.3.5. Manually rotate the hand wheel of the actuator to opened position
4.3.6. Using the hex wrench, loosen the set screw in the OPEN limit switch cam
4.3.7. Rotate the OPEN cam towards CCW limit switch level until the switch ‘clicks’ (see Figure 2)
4.3.8. Tighten the set screw with the hex wrench
Danger :
HAZARDOUS VOLTAGE. Make sure all incoming power is disconnected before setting the limit
switch
HQ
-
008/010
HQ
-
015/020
H
Q
-
030/050
HQ
-
080/120
4
-
M12 Tap, Dp 18
P.C.D Ø125 (F12)
4
-
M16 Tap, Dp 24
P.C.D Ø140 (F14)
HQ
-
080/120
4
-
M20 Tap, Dp 30
P.C.D Ø165 (F16)
HQ-200/300
Figure
2
:
Open
Cam Setting
Lower
Switch
Upper Switch
Figure 1: Close Cam
Setting

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 10 / 21 Valve Automation Leader HKC
4.4. Torque Switch Setting
4.4.1. Torque spring, which detects the variation of torque during the operation, is installed to prevent
damaging the valve and actuator under overload condition. Once the actuator is under overload,
the torque switch trips, and the actuator stops immediately.
4.4.2. The torque switches are set by manufacturer on the production site. If re-setting is necessary, please
contact the HKC service representative before setting the torque switch.
CAUTION:
Do not reset torque switch to a setting higher than the maximum setting stated by
the manufacturer.
4.5. Counter-Clockwise to Close Setting
Standard actuators are normally set to clockwise rotation to close. However, the rotation can be reversed
to counter-clockwise to close by simply reconfiguring the wiring as follows:
4.5.1. Reverse wiring in the main terminal block: 9 & 10 as well as 11 & 12.
4.5.2. Adjust the visual indicator to suit the counter-clockwise rotation.
If a PCU card is installed, [please refer to DHC-100 for ac or DMC-102A for dc PCU manual of Peak-
tronics Co. --- 17 rev1]
4.6. Mechanical Travel Stop Adjustment
4.6.1. Loosen both (open and close) travel stopper bolt nuts by 3-4 threads.
4.6.2. By turning the hand wheel, manually operate the actuator so that it is in close position until it
makes a contact with the closed limit switch.
4.6.3. Tighten the close travel stopper bolt until it contacts the 2nd worm wheel (in this position the close
travel stopper bolt should not be able to travel any further).
4.6.4. Loosen back the close travel stopper bolt by on turn and tighten the close travel stopper bolt nut.
4.6.5. Repeat the same operation for setting of the open travel stopper bolt.
4.7. Setting potentiometer (Replacing and setting)
The potentiometer has been calibrated at factory. However, if re-calibration is required, proceed as fol-
lows:
4.7.1. Manually rotate the hand wheel of the actuator to fully closed position.
4.7.2. While measuring the resistance between P1 (orange) and P2 (grey), gently rotate the Potentiometer
Gear until it reaches between 80 - 120 Ω (100 Ω preferred).
4.7.3. Engage the Potentiometer Gear into the Point Shaft Gear and use an L-wrench to tighten the screw.
Travel stopper
bolt for Close
Travel stopper
bolt for Open
Point Shaft Gear
Potentiometer
Gear
Point Shaft
Potentiometer
JP-30B (1KΩ±0.5%)
Limit
Switch
Assembly
P1
—
1
7
Rev
0
]
P2
[
P
3

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 11 / 21 Valve Automation Leader HKC
[Anti-vibration type(OKM) General type--16Rev1]
4.8. Current Position Transmitter – CPT (Optional)
The potentiometer is used for the actuator signal feedback. It reads a resistance value corresponds to the
current position of the actuator and transfers to CPT card. The CPT indicates the current position of the
actuator throughout the stroke by a 4 ~ 20mA output signal.
4.8.1. Standard Features
Model
CPT
Power
220(110)
V
ac
, 50/60Hz
,
2VA
m
ax
Output Signal
4~20mA
dc
Output Impedance
750Ω
m
ax
Resolution
Min 1/1000
Position Conversion Accuracy
±
0.5 ~
±
1.5%
Ambient Temperature
-
20
℃
to +70
℃
Ambient Humidity
90% RH
m
ax (Non
-
condensing)
Dielectric Strength
1 sec at (Rated Vac x 2 + 1000) x1.2
(
from
Input to power ground
)
Insulation Resistance
Above 500
V
dc
30MΩ
Vibration
10g, 0~34Hz
4.8.2. Calibration of Zero and Span – CPT
The settings of Zero and Span have
been calibrated at the factory. How-
ever, if re-calibration is required, pro-
ceed as follows:
[Delete “①” --- 16Rev1]
① Apply power (or use the manual
override) to drive the actuator to its
fully closed position (clockwise ro-
tation).
② When the actuator is in the fully
closed position, adjust the ZERO
dial on the CPT board until a read-
ing of 4mA is achieved.
③ Apply power (or use the manual
override) to drive the actuator to its fully
open position (counter-clockwise rota-
tion).
④ When the actuator is in the fully open position, adjust the SPAN dial on the CPT board until a
reading of 20mA is achieved.
4.9. [Proportional Control Unit (PCU)
PCUC – AC (HKC model) PCUC - DC (HKC model)
Notes : PCUC-AC or PCUC-DC PCU cards can be applicable to all of the CSA certified HQ series.
DMC-100 or DHC-100 PCU cards from Peaktronics are possible to use only HQ-020 Model for CSA
products. --- 21 rev0]

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 12 / 21 Valve Automation Leader HKC
CSA certified AC type shall be applied DHC-100 PCU card. For more details about DMC or
DHC PCU card installation and operation, please refer to Peaktronics IOM Manual.
Peaktronics PCU DHC-100 for ac Peaktronics PCU DMC-102 for dc
PCU DHC-100 Digital High Resolution Controller
Model
DHC
-
100 series
Power
DHC
-
100 117 V ac,
-
100A 234 V ac,
-
100B 24 V ac
Position
±
0.1
˚
with
quarter
turn actuators ranging from 2 to 120 sec
Duty rate
25% or more
Command type
4
-
20mA, 1
-
5 V, 0
-
5 V, 0
-
10 V
Operating temperature
0 to 60
℃
PCU DMC
-
102 DC Motor Controller
Model
DMC
-
102 series
Power
10 to 30 V dc, 10 A continuous, 60 A locked rotor
External command signal
4~20
mA, 0~5
V, 0~10
V
,
1~5
V, 2~10V
Operating temperature
0 to 60
℃
Storage
temperature
-
40 to 85
℃
Relative humidity
0 to 90% (
noncondensing
)
[You must never do any welding work while the actuator is connected with electrical line. If an elec-
trical shock occurs on the actuator, it makes a cause of serious damage to the microprocessor of the
actuator.--- 17 Rev1]
4.10. [AC/DC Multi-Board
4.10.1. General
① ACDM-200 series is an electronic motor converting module that can operate an actuator by 12 V
dc or 24 V dc motor with 12 V ac or 24 V ac capacitor starting type or split phase type motors.
② The converter module can operate 12 V dc or 24 V dc motor actuator just like an ac motor actua-
tor. One of characteristic of the converter module is a dynamic brake function. This function im-
proves precision by electrically braking without mechanical braking on valves due to slip by inertia.
There are 12 V and 24 V for this series.
4.10.2. Special characteristics
① ACDM-200 24V
Operating voltage
20 to 28 V ac
20 to 28 V dc
Operating current
Limit switch current and typical operating current
100 mA@24 V ac, 95 mA @24 V dc
Fuse type
ACDM-200 24 V : 10A (Bussman ABC-10 or Littelfuse 314010)
Dc motor output
Maximum load current
30A locked rotor for 3 seconds typical
Environmental applicable condition
Operating Temperature: -40 to 85 °C
Storage Temperature: -50 to 105°C
Relative Humidity: 0 to 90 % (at non-condensing)

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 13 / 21 Valve Automation Leader HKC
Vibration resistance: 15~55Hz double amplitude
② ACDM-200 12V
Operating voltage
10 to 14 V ac
10 to 14 V dc
Operating current
Limit switch current and typical operating current
50 mA@12 V ac, 45 mA @12 V dc
Fuse type
ACDM-200 12 V : 15A (Bussman ABC-15 or Littelfuse 314015)
Dc motor output
Maximum load current
25A locked rotor for 3 seconds typical
Environmental applicable condition
Operating Temperature: -40 to 85 °C
Storage Temperature: -50 to 105°C
Relative Humidity: 0 to 90 % (at non-condensing)
Vibration resistance: 15~55Hz double amplitude
4.10.3. Outline features
ACDM-200 12V for HQ-008/010 ACDM-200 24V for HQ-008/010 ACDM-200 24V for HQ-015/020/030
----- 17 rev1]
5. Wiring
5.1. Electrical Connections and Preliminary Test
WARNING:
[You must never do any welding work while the actuator is connected with electrical line. If an elec-
trical shock occurs on the actuator, it makes a cause of serious damage to the microprocessor of the
actuator.----- 17 Rev1]
When working in potentially explosive atmospheres, observe the European Standards EN 60079-14 “Elec-
trical Installation in Hazardous Areas” and EN 60079-17 “Inspection and Maintenance of Electrical Installa-
tions in Hazardous Areas”. Work on the electrical system or equipment must only be carried out by a
skilled electrician himself or by specially instructed personnel under the control and supervision of such an
electrician and in accordance with the applicable electrical engineering rules.
For cable gland or cable entries that are not used, user or installer shall close by Ex d IIC certified cable
gland or blanking element suitable for the type of protection, Ex d so that type of protection of the enclo-
sure is maintained.
Flameproof enclosure! Treat cover with care. Gap surfaces must not be damaged in any way. Do not jam
cover during fitting.
5.1.1. For testing purposes, loosen the bolts on the actuator cover and remove the cover.
5.1.2. Make sure that the power supply voltage is in accordance with the data on the nameplate of the
actuator.
5.1.3. Pass cables through the cable glands: NPT 3/4” for Ex “d”
5.1.4. Connect wires according to the enclosed wiring diagram.

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 14 / 21 Valve Automation Leader HKC
5.1.5. Manually move the valve to half-open position. Then electrically operate the actuator to fully open
position and check if the motor rotates in correct direction; standards units are counter-clockwise to
open.
5.1.6. Test the actuator and check whether the limit switches work correctly
5.1.7. After the testing, check that all cable glands are correctly tightened. Applicable cable glands should
be selected to meet the application’s condition. It is recommended to use the grade of IP67 cable
gland or higher in potentially explosive atmosphere.
5.1.8. Put carefully the cover on the body and tighten the bolts.
6. Maintenance
6.1. Maintenance
WARNING:
Turn off all power before attempting to perform maintenance on the actuator.
POTENTIALLY HIGH PRESSURE VESSEL. Before removing or disassembling your actuator, ensure that the
valve or other actuated device is isolated and not under pressure.
Under the normal conditions, maintenance should be carried out at six month intervals. But when the
conditions are more severe, more frequent inspections may be advisable.
6.1.1. Ensure that the actuator is properly aligned with the valve or other actuated device
6.1.2. Ensure that all wirings are insulated, connected and terminated properly
6.1.3. Ensure that all screws are present and tight
6.1.4. Ensure cleanness of internal electrical devices
6.1.5. Ensure that cable connections are properly installed and are dried
6.1.6. Check the internal devices for any condensation
6.1.7. Check the power to the internal heater
6.1.8. Check enclosure O-rings seals and verify that the O ring is not pinched between each joint.
6.1.9. Verify the declutch mechanism
6.1.10. Visually inspect the open/close cycle
6.1.11. Check whether the o-ring for Ex d enclosure is damaged or not
6.1.12. Inspect the identification labels for wear and replace it if necessary
WARNING:
Flameproof Enclosure! Before opening, ensure the absence of any gas and any electrical
power
Treat cover with care. Gap surfaces must not be damaged or dirtied in any way. Do not
jam the cover during fitting.
6.2. Tools
6.2.1. Metric Allen Key (Hex Wrench) × 1
6.2.2. Screw Driver × 1
6.2.3. Metric Spanner × 1
6.2.4. Wrench 200mm × 1
6.2.5. Wrench 300mm × 1
6.2.6. Wire Stripper Long Nose × 1
6.2.7. Multi-meter (ac, dc, Resistance) × 1
6.2.8. PCU Board Option: dc Signal Generator (4 – 20mA dc) × 1
6.2.9. PCU & CPT Board Option: 1 mA Meter (0~25mA) x 1
7. Trouble Shooting
The following instructions are listed the most common difficulties encountered during the installation and start-
up, and their countermeasures.
7.1. The actuator does not respond
7.1.1. Visually inspect the actuator to check no shipping or handling damage has occurred
7.1.2. Verify the line voltage supplied to the actuator; check that the line voltage matches with the rating
on the actuator’s nameplate
7.1.3. Check the internal wiring against the supplied wiring diagram of the actuator
7.1.4. Check the limit switch cams

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 15 / 21 Valve Automation Leader HKC
7.2. The actuator is supplied with power but does not operate
7.2.1. Verify the line voltage supplied to the actuator; check that the line voltage matches with the rating
on the actuator’s nameplate.
7.2.2. [Make sure that the actuator output torque is greater than the valve required torque -17 Rev0]
7.2.3. Check the limit switch cams
7.2.4. Check that the torque switches have not been tripped
7.2.5. Check the mechanical travel stop adjustment
7.2.6. Verify that the actuator operating direction against the rotation of the valve (standard units are
counter-clockwise rotation to open)
7.2.7. [Check internal wiring --- 17 rev0]
7.2.8. Check for any corrosion and condensation that any of the electrical or mechanical devices have not
been contaminated
7.2.9. Verify that coupler/bracket is correctly installed and is not causing any binding
7.3. Actuator runs erratically
7.3.1. Check the ambient temperature
7.3.2. Verify that the duty cycle has not been exceeded
7.3.3. Check the position of manual override lever
7.4. Optional Equipment(s)
7.4.1. [Potentiometer --- 17 Rev0]
① Check the resistance value
② Check potentiometer gear for jamming
③ Check ZERO and SPAN calibration, [and confirm input / output signal --- 17 Rev0]
④ Check the board for any damage
7.4.2. Current Position Transmitter
① Verify the input signal
② Check the configuration of the dip switches
③ Check the board for any damage
8. Installation and Maintenance Tips
WARNING:
When working in potentially explosive areas, be sure to comply with the standard EN 60079-14 “Elec-
trical Installations in Hazardous Areas”.
For cable entries that are not used, user or installer shall close by Ex db IIC certified blanking el-
ement suitable type of protection, Ex d so that type of protection of the enclosure is maintained.
Working on the actuator that is in open position and under voltage must only be performed if it is as-
sured that there is no danger of explosion for the duration of the work.
Flameproof Enclosure! Before opening, ensure the absence of any flammable gas and any electrical
power
When operation, maintenance, or installation shall be verified that O-rings are not damaged or
pinched between their parts.
CAUTION:
A regular inspection and maintenance should be performed by qualified and trained personnel
Treat cover with care. Gap surfaces must not be damaged or dirtied in any way. Do not jam the cover
during fitting.
Pay attention to national regulations
For any installation and maintenance work, the followings should be noted:
8.1. Check the quarter turn actuators visually. Ensure that no external damage or changes are visible. The
electrical cables must not be damaged and wired correctly.
8.2. Cable entries, cable glands, plugs, etc. have to be checked whether they are correctly tightened and
sealed.

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 16 / 21 Valve Automation Leader HKC
8.3. Check that the Ex-connections are correctly fastened.
8.4. Check for the possible discoloration of the terminals and wires as this may indicate an increased temper-
ature.
8.5. Check the flame path gaps of the flameproof enclosures for any dirt and corrosion. Since the dimensions
of all Ex gaps are strictly defined and inspected, no mechanical work shall be performed on them.
8.6. Ensure that all housing covers are handled carefully and that the seals are checked.
8.7. All cables and motor protection elements have to be checked.
8.8. During the maintenance if any defects are detected that may affect the safety, repair measures have to be
taken immediately.
8.9. Any kind of surface coating for the gap surface is not permitted.
8.10. When replacing parts, seals, etc., only original spare ones must be used.

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 17 / 21 Valve Automation Leader HKC
APPENDIXⅠ. HQ(XE)-series Coding System
Note: Coding system was consolidated from each model’s
[Example : HQ – 030 a b c d e f g
Model Name Code (as below)
MODEL
a
b
c
d
e
f
g
HQ-XXX Enclosure Input Volt-
age
Option 1
Control Unit
Option 2
Software
Option 3
Additional
Switch
Option 4
Signal Lamp
Option 5
Fireproofing
XE-XXXXX
INITIAL
HQ
-
XE
-
Size
TORQUE
Size
TORQUE
Model
008
80 Nm
00690
690 In
-
Lbs
010
100 Nm
00860
860 In
-
Lbs
015
150 Nm
01350
1350 In
-
Lbs
020
200 Nm
01700
1700 In
-
Lbs
030
300 Nm
02640
2640 In
-
Lbs
050
500 Nm
04400
4400 In
-
Lbs
080
800 Nm
06900
6900 In
-
Lbs
120
1
1
00 Nm
10500
9600
In
-
Lbs
200
2000 Nm
17500
17500 In
-
Lbs
300
3000 Nm
25900
25900 In
-
Lbs
a
(Enclosure)
1
Weather proof(
NEMA type 4/4X/6,
IP67)
I
nclude CSA ordinary location item
2
Submersible(IP68)
*1
3
Flamep
roof
(CSA
, IECEx, ATEX, KCs
, EAC
)
4
Dust ignition p
roof
(IECEx
, ATEX
, KCs
)
*
1
b
(Input
Voltage)
1
110V ac, 1ph
2
220V ac, 1ph
3
220V ac, 3ph (Except
-
008,
-
010)
*1
4
[
380V ac, 3ph
*1
5
440V ac, 3ph
*1
6
460V ac, 3ph
*1
---
18 Rev0]
7
24V
d
c (Except HQ
-
0
5
0~HQ
-
300)
*
2
---
17 Rev0]
8
24V
ac/d
c (Except HQ
-
0
5
0~HQ
-
300)
*2
---
17 Rev0]
9
12V dc (Except HQ
-
015~HQ
-
300)
*2
A
12V ac/dc (Except HQ
-
015~HQ
-
300)
*2
---
17 Rev0]
The 12/24V AC and DC groups are not applied to IECEx / ATEX items
-----
16 Rev0]
c
(Option 1)
Control Unit *1
0
Without control unit
1
ICU (Intelligent Digital Control Unit :
LCU
-
C
+IMS+Auto Phase Discriminator)
2
SICU(Semi
-
Integral Control Unit :
LCU
-
B
+IMS+Phase Protect Indicator)
3
RBP (Rechargeable Battery Backup)
*1
,
*2
d
(Option 2)
Software
0
without PIU / CPT / PCU
1
PIU
(Potentiometer Unit : 0~1kΩ)
*1
2
CPT(Current
p
osition
t
ransmitter:
Out
4~20mA)
*1
3
PCU(Proportional
c
ontrol
u
nit :
I
n
/O
ut
0~10V, 4~20mA)
Modulating Controller Card (PCU)
e(Option 3)
Additional
switches
0
without
additional switches
1
2ALS (Additional Limit Switches)
2
2ATS (Additional Torque Switches)
f(Option 4)
Signal Lamp /
90° mounting
Plate
0
without LPA
1
SLU (Signal Lamp Unit)
*1
2
LPA (Lever Plate Actuator 90°)
*1
3
SLU + LPA
*1
g(Option 5)
Fire Proofing
Actuator
0
without FPA 1 / FPA 2
1
FPA 1 (Fire Proofing: 1,050
℃
/50min)
*1
2
FPA 2 (Fire Proofing: 250
℃
/150min)
*1
REMARK
*1: This option shall not be applied to CSA items. More details should be advised to the manufacturer. --- 16 Rev0]
*2: This option shall not be applied to IECEx/ATEX items. --- 17 Rev.0]

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 18 / 21 Valve Automation Leader HKC
Appendix II: Wiring Diagram
HQ-008/010 Standard 1Ph.
HQ-008/010 Standard DC
DANGER:
HAZARDOUS VOLTAGE. No electrical power should be connected until all wiring and limit
switch adjustments have been completed.

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 19 / 21 Valve Automation Leader HKC
HQ-015 ~ 300 Standard 1Ph.
HQ-015 ~ 300 Standard 1Ph. PCU --- 17 Rev1]
DANGER:
HAZARDOUS VOLTAGE. No electrical power should be connected until all wiring and limit
switch adjustments have been completed.

HQ(XC) Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumC-HQ-21 Rev1 Page 20 / 21 Valve Automation Leader HKC
HQ-015 ~ 030 Standard DC
HQ-015 ~ 030 Standard DC PCU --- 17 Rev1]
NOTE:
Each actuator is packed with individual box, and you can get the wiring diagram inside.
Other manuals for HQ Series
1
This manual suits for next models
21
Table of contents
Other HKC Controllers manuals

HKC
HKC HQ-005 RBP Instruction manual

HKC
HKC HQ-004 Instruction manual

HKC
HKC HP Series Instruction manual

HKC
HKC HL Series Instruction manual

HKC
HKC HQ-006 Instruction manual

HKC
HKC HM04 Manual

HKC
HKC HL Series User manual

HKC
HKC ET Series Instruction manual

HKC
HKC HQ Series Instruction manual

HKC
HKC HQ-005 User manual
Popular Controllers manuals by other brands

Broadcom
Broadcom HBA 9405W-16e Quick installation guide

Hayward
Hayward Aqua Plus® installation manual

Tyco
Tyco DSC PowerSeries HS2016 Reference manual

Generac Power Systems
Generac Power Systems PowerManager PM-GC manual

Honeywell
Honeywell ML7420A6025 installation instructions

mensor
mensor CPC8000 operating instructions