HQ(XC) Series Quarter-turn Electric Actuator 
Installation Operation& Maintenance Manual 
 
 Doc No. : HumC-HQ-21 Rev1   Page  4 / 21  Valve Automation Leader HKC 
2.1.2. Applied Standard 
① IEC60079-0:2011(Ed.6 +IS01),    EN60079-0:2012+A11 
② IEC60079-1:2014-06 (Ed.7),    EN60079-1:2014 
③ IEC60079-31:2013(Ed.2),      EN60079-31:2014  
④ CAN/CSA C22.2 No. 139-13 / UL 429 seventh ed. ---- 17 Rev0] 
2.1.3. Certification 
① [IECEx: for HQ-008 ~ HQ-300 with LCU,   IECEx DEK 16.0042X 
Ex db IIB T4 Gb, Ta -20℃ to +60℃,   Ex tb IIIC 135℃ Db 
② ATEX: for HQ-008 ~ HQ-300 with LCU,  DEKRA 16ATEX0083 X, CE 0344 
II 2 G Ex db IIB T4 Gb, Ta -20℃ to +60℃,   II 2 D Ex tb IIIC 135℃ Db ----- 18 Rev0] 
③ [KCs Ex d IIB T4, -20℃ ~ +60℃:  
for HQ-008/010, 제 2020-BO-0016 호,  for HQ-015/020, 제 2020-BO-0017 호,    
for HQ-030~060, 제 2020-BO-0018 호,  for HQ-080~300, 제 2020-BO-0019 호    
KCs Ex tD A21 IP6X T135℃, -20℃ ~ +60℃:  
for HQ-008/010, 제 2020-BO-0012 호,  for HQ-015/020, 제 2020-BO-0013 호,    
for HQ-030~060, 제 2020-BO-0014 호,  for HQ-080~300, 제 2020-BO-0015 호 – 20 Rev0] 
④ CSA: for HQ-008 ~ HQ-300, 249581 (except HQ-060) Hazardous location 
Class I, Division 1, Group C, D, T4  Ex d IIB Gb T4 
Class I, Zone 1, AEx d IIB Gb T4 
[Ambient Temperature -20℃ to +60℃ --- 21 r0], Enclosure rating : Type 4, 4X, 6, IP66, IP67 
Cable entry : 2 x NPT 3/4” Female 
⑤ CSA: for HQ-008 ~ HQ-300, 249581 (except HQ-060) Ordinary location  
Note  : 
 Sealing devices must be used and shall be fitted directly at enclosure wall when using conduit. 
 Cable glands shall be suitable for the environment and shall be certified as flameproof if used in 
Zone 1 application. 
 Cable glands and conduit to be installed minimum 6 full threads and the length of thread is min-
imum 8mm.  
 Temperature of cable entry is maximum 90℃. Heat resistance wire is recommended when you in-
stall. 
 Ex d certified cable glands suitable for 90℃ must be used. 
 Users should confirm all information about dimensions of flamepath with the manufacturer 
 All information about the material and the allowance of LCU fasteners. [However LCU is not apply 
to CSA items. --- 17 rev1] 
 Fasteners with yield strength ≥ 210MPa (stainless steel) 
 Bolts type : M5*0.8, M6*1, M8*1.25, M10*1.5, M12*1.75 (Tolerance Fit 6g) 
 Cable connection : Refers to the Appendix Ⅱ (Wiring Diagram) 
 For  cable  entries  or  conduit  entries  that  are  not  used,  user  or  installer  shall  close  by  certified 
blanking elements (stopping plugs) so that the flameproof properties of the enclosure are main-
tained. 
 Always ground the enclosure in accordance with local electric codes. The most effective enclosure 
grounding method is a direct connection to earth ground with minimal impedance. Methods for 
grounding the enclosure include:  
 Internal ground connection: The internal ground is located in the terminal block #1. Refer to the 
enclosed wiring diagram.  
 External ground connection: The ground lug is located on the centre of cable entries.  
 For more information, refers to the Appendix Ⅲ (Grounding) 
 [Stainless steel name plate for the flame proof and dust ignition proof type shall be permanently 
attached by rivets or screw on the cover. ----- 20 Rev0] 
 
2.2. Initial inspection  
When the user receipts the actuator, inspect the condition of the product and ensure the name plate com-
paring with order sheet. 
2.2.1 Remove packing wrap  or  wooden box  carefully.  Inspect the  product  for any  physical  damage  that 
may have occurred during shipment. 
2.2.2 Check the product specification with product ordered. If a wrong product has been shipped, imme-
diately report to our coordinator.  
2.3. Storage