S-Quad Dual Optical Heat & Optical Heat sensor STATES
STATE Definition / Class Application in / Suitable for:
Sensitivity
a-high- to-j-none
STATE 3 High sensitivity optical,
Class A1 heat
Clean area or environment, where early detection
is required
a
STATE 4 Medium sensitivity with no
optical spike protection, Class
A1 heat
General area as STATE 0 with less immunity to
steam and dust for ease of testing using artificial
smoke in normal operating mode, when test /
commissioning mode is not active
b
STATE 0#Medium sensitivity optical,
Class A1 heat
General area c
STATE 8 Delayed medium sensitivity
optical, Class A1 heat
General application in area with transient steam,
dust or smoke present
d
STATE 7 Medium sensitivity optical,
Class A2S heat
General application in area with low dust, smoke
or steam present, for fixed temperature operation
that is totally unaffected by transient temperature
variation
e
STATE 5 Medium sensitivity optical,
Class B heat
Area having high ambient temperature with low
dust, smoke or steam present
f
STATE 2 Low sensitivity optical,
Class A1 heat
Areas with moderate dust, smoke or heat during
working hours when used with timing function
g
STATE 11 Low sensitivity optical,
Class B heat
Area having high ambient temperature, plus
where moderate dust, smoke or steam present
h
STATE 6 Low sensitivity optical,
Class BS heat
Area having high ambient temperature that
changes, plus moderate dust, smoke or steam
present
i
STATE 12 Class A1 heat only Area where smoke, dust or steam occurs at times j
STATE 15 No detection k
# - factory default settings
S-Quad Dual Optical, Heat & CO sensor STATES
STATE Definition / Class Application in / Suitable for:
Sensitivity
a-high- to-h-none
STATE 1 High sensitivity optical, Class A1
heat, high sensitivity gas
Clean area or environment where early detection
is required with false alarm reduction
a
STATE 4 Medium sensitivity optical with no
spike protection, Class A1 heat,
medium sensitivity gas
General area as STATE 0 with less immunity to
steam and dust for ease of testing using artificial
smoke in normal operating mode, when test /
commissioning mode is not active
b
STATE 0#Medium sensitivity optical, Class
A1 heat, medium sensitivity gas
General area where false alarm reduction is
required for comprehensive fire detection
c
STATE 7 Medium sensitivity optical,
Class A2S heat, medium
sensitivity gas
General area with moderate dust, smoke
(tobacco) or steam, operates at a fixed
temperature and is totally unaffected by transient
temperature variation
d
STATE 2 Medium sensitivity optical,
Class A1 heat, low sensitivity gas
Applications with moderate dust, smoke
(tobacco) or steam
e
STATE 9 Medium sensitivity gas,
Class A1 heat
Area where high levels of smoke, dust or steam
is often present
f
STATE 11 Medium sensitivity optical,
Class B heat
Area with high ambient temperature, plus low
levels of dust, smoke or steam present
g
STATE 12 Class A1 heat only Area where smoke, dust, steam or gas occurs at
times
h
STATE 15 No detection i
Description & Commissioning S-Quad
6 4188-779 issue 10_12/13_S-Quad _Part 2