Honeywell Farenhyt IFP-2000 User manual

Document 151430-L8 Rev: P
12/07/2017 ECN: 17-0555
IFP-2000/IFP-2000ECS
/ RPS-2000
Analog/ Addressable Fire System
Emergency Communication System
Farenhyt™ Series

2
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notifica-
tion capability—can provide early warning of a developing fire. Such
a system, however, does not assure protection against property
damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an
automatic fire alarm system (as described above) and a life safety
communication system that may include an autonomous control
unit (ACU), local operating console (LOC), voice communication,
and other various interoperable communication methods—can
broadcast a mass notification message. Such a system, however,
does not assure protection against property damage or loss of life
resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors
be located throughout a protected premises following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of System
Smoke Detectors, which is made available at no charge to all
installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in as
many as 35% of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee warning or
protection against fire. A fire alarm system may not provide timely or
adequate warning, or simply may not function, for a variety of
reasons:
Smoke detectors may not sense fire where smoke cannot reach
the detectors such as in chimneys, in or behind walls, on roofs, or
on the other side of closed doors. Smoke detectors also may not
sense a fire on another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may
not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim-
neys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach the
ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air out-
lets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching
the detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels
of smoke density. If such density levels are not created by a devel-
oping fire at the location of detectors, the detectors will not go into
alarm.
Smoke detectors, even when working properly, have sensing limita-
tions. Detectors that have photoelectronic sensing chambers tend
to detect smoldering fires better than flaming fires, which have little
visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering fires.
Because fires develop in different ways and are often unpredictable
in their growth, neither type of detector is necessarily best and a
given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning
of fires caused by arson, children playing with matches (especially
in bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined rate
or reaches a predetermined level. Rate-of-rise heat detectors may
be subject to reduced sensitivity over time. For this reason, the rate-
of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors are
designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for the
connection of alarm transmission wiring, communications, signal-
ing, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, compromising its ability to report a
fire.
Audible warning devices such as bells, horns, strobes, speak-
ers and displays may not alert people if these devices are located
on the other side of closed or partly open doors or are located on
another floor of a building. Any warning device may fail to alert peo-
ple with a disability or those who have recently consumed drugs,
alcohol, or medication. Please note that:
• An emergency communication system may take priority over a
fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility
requirements as defined by NFPA, local codes, and Authorities
Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis-
seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a
fire alarm signal, do not respond to or comprehend the meaning
of the signal. Audible devices, such as horns and bells, can have
different tonal patterns and frequencies. It is the property
owner's responsibility to conduct fire drills and other training
exercises to make people aware of fire alarm signals and
instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only
for a specified time and only if the batteries have been properly
maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Telephone lines needed to transmit alarm signals from a premises
to a central monitoring station may be out of service or temporarily
disabled. For added protection against telephone line failure,
backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inad-
equate maintenance. To keep the entire life safety system in excel-
lent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards. At
a minimum, the requirements of NFPA 72 shall be followed. Envi-
ronments with large amounts of dust, dirt, or high air velocity require
more frequent maintenance. A maintenance agreement should be
arranged through the local manufacturer's representative. Mainte-
nance should be scheduled as required by National and/or local fire
codes and should be performed by authorized professional life
safety system installers only. Adequate written records of all inspec-
tions should be kept.
Limit-D2-2016

3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources of
power before servicing. Control unit and associated equipment may
be damaged by removing and/or inserting cards, modules, or inter-
connecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until manuals are read and
understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product must be
tested in accordance with NFPA 72 after any programming opera-
tion or change in site-specific software. Re-acceptance testing is
required after any change, addition or deletion of system compo-
nents, or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system operations, or
software functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not inadver-
tently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also
be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/
32-120º F and at a relative humidity 93% ± 2% RH (noncondens-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys-
tem's standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its peripherals
be installed in an environment with a normal room temperature of
15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from light-
ning transients and interference, proper grounding will reduce sus-
ceptibility. Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes. Con-
sult with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make all
cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or printed
circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tighten-
ing may damage threads, resulting in reduced terminal contact
pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any cir-
cuits so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies removed
from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual may cause interfer-
ence to radio communications. It has been tested and found
to comply with the limits for class A computing devices pur-
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such
interference when devices are operated in a commercial
environment. Operation of this equipment in a residential
area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own
expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for
radiation noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Depart-
ment of Communications.
Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
Farenhyt™ is a trademark; and eVance®, Honeywell®, Silent Knight® and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and
Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The
Mozilla Foundation.
©2017 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

4
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we
strongly recommend that you download the most current version of software for each product prior to commissioning any system.
Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.T[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.

Contents
Section 1
Introduction ..................................................................................................................................................1
1.1 Overview of Basic System ........................................................................................................... 1
1.1.1 Hardware Features ...............................................................................................................1
1.1.2 Network System Hardware Features ....................................................................................1
1.1.3 Software Features .................................................................................................................2
1.1.4 IFP-2000ECS Features ......................................................................................................... 2
1.2 About this Manual ........................................................................................................................2
1.2.1 Terms Used in this Manual ...................................................................................................3
1.3 Compatible Products ...................................................................................................................4
Section 2
Agency Listings, Approvals, and Requirements .......................................1
2.1 Federal Communications Commission (FCC) .............................................................................1
2.2 Underwriters Laboratories (UL) ...................................................................................................2
2.2.1 Requirements for All Installations .........................................................................................2
2.2.2 Requirements for Central Station Fire Alarm Systems .........................................................2
2.2.3 Requirements for Local Protected Fire Alarm Systems ........................................................2
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - (DACT) ........................3
Section 3
Before You Begin Installation ..............................................................................................1
3.1 What’s in the Box? ......................................................................................................................1
3.2 Environmental Specifications ......................................................................................................1
3.3 Electrical Specifications ...............................................................................................................1
3.4 Wiring Specifications ...................................................................................................................4
3.5 Board Assembly Diagram ............................................................................................................7
3.6 Calculating Current Draw and Standby Battery ...........................................................................8
3.6.1 Current Draw Worksheet Requirements ...............................................................................8
3.6.2 Current Draw Worksheet for IDP SLC Devices ....................................................................8
3.6.3 Current Draw Worksheet for SD SLC Devices ...................................................................12
3.6.4 Maximum Battery Standby Load .........................................................................................16
3.7 Installation Task Overview ........................................................................................................16
Section 4
Control Panel Installation ..........................................................................................................1
4.1 Mounting the Control Panel Cabinet ...........................................................................................1
4.1.1 Preventing Water Damage ....................................................................................................1
4.1.2 Removing the IFP-2000 Assembly from the Housing ...........................................................1
4.1.3 Ethernet Connection .............................................................................................................1

4.2 AC Connection ............................................................................................................................2
4.3 Battery Connection ......................................................................................................................3
4.3.1 Battery Accessory Cabinets ..................................................................................................3
4.3.1.1 Installing the RBB or AB-55 Accessory Cabinet and Batteries ...................................3
4.4 SBUS Wiring ...............................................................................................................................5
4.4.1 Calculating Wiring Distance for SBUS Modules ...................................................................5
4.4.2 Wiring Configurations ............................................................................................................8
4.5 RA-2000 Remote Annunciator Installation ..................................................................................9
4.5.1 Mounting the RA-2000 ..........................................................................................................9
4.5.1.1 Flush Mounting ............................................................................................................9
4.5.1.2 Surface Mounting ......................................................................................................11
4.5.2 RA-2000 Connection to the Panel .....................................................................................12
4.5.3 Temporary Programming Display .......................................................................................13
4.6 5815XL Installation ....................................................................................................................13
4.6.1 5815XL Connection to the Panel ........................................................................................14
4.7 5824 Serial/Parallel Interface Module Installation .....................................................................14
4.7.1 Selecting 5824 Options .......................................................................................................16
4.8 5880 LED I/O Module ................................................................................................................17
4.8.1 5880 Board Layout ..............................................................................................................17
4.8.2 FACP Connection ...............................................................................................................18
4.8.3 LED Wiring ..........................................................................................................................18
4.8.4 Dry Contact Wiring ..............................................................................................................19
4.9 5865-3 / 5865-4 LED Annunciator Installation ...........................................................................20
4.9.1 FACP Connection ...............................................................................................................20
4.9.2 5865 Mounting ....................................................................................................................21
4.10 Configuring SBUS Modules .......................................................................................................22
4.10.1 Assigning SBUS Module IDs .............................................................................................22
4.10.2 SBUS Bandwidth Considerations ......................................................................................22
4.11 Telephone Connection ..............................................................................................................23
4.12 Flexputs™I/O Circuits ...............................................................................................................23
4.12.1 Conventional Notification Appliance ..................................................................................23
4.12.1.1 Class B Notification Wiring ....................................................................................... 23
4.12.1.2 Class A Notification Wiring ......................................................................................24
4.12.2 Conventional Input Switch Circuits ....................................................................................25
4.12.2.1 Class B Inputs ..........................................................................................................25
4.12.2.2 Class A Inputs ..........................................................................................................26
4.12.3 Installing 2-Wire Smoke Detectors ....................................................................................27
4.12.3.1 Installing 2-Wire Class B Smoke Detectors .............................................................27
4.12.3.2 Installing 2-Wire Class A Smoke Detectors ............................................................ 28
4.12.4 Installing 4-Wire Smoke Detectors ....................................................................................28
4.12.4.1 Installing a Class B 4-Wire Smoke Detectors ..........................................................28
4.12.4.2 Installing 4-Wire Class A Smoke Detectors .............................................................29
4.12.5 Auxiliary Power Installation ................................................................................................30
4.12.5.1 Door Holder Power ...................................................................................................31
4.12.5.2 Constant Power ........................................................................................................31
4.12.5.3 Resettable Power .....................................................................................................31
4.12.5.4 Sounder Sync Power ...............................................................................................31
4.13 On-Board Relays (Conventional) ..............................................................................................32
4.13.1 Trouble Relay ....................................................................................................................32
4.13.2 Programmable Relays .......................................................................................................32
4.14 Remote Station Applications .....................................................................................................33
4.14.1 Keltron Model 3158 Installation .........................................................................................33
4.14.2 City Box Connection Using the 5220 Module ....................................................................34
4.14.3 Using the IDP-Relay Addressable Relay Module for City Box Connection .......................35

4.14.4 NFPA 72 Polarity Reversal ................................................................................................35
4.14.4.1 Using the 5220 Module ............................................................................................ 35
4.14.4.2 Using the 7644-L8* Module ......................................................................................36
4.14.5 Transmitter Activated by Dry Contacts ..............................................................................37
Section 5
Networking ....................................................................................................................................................1
5.1 Network System Hardware Features ..........................................................................................1
5.1.1 Networked Sites ....................................................................................................................1
5.1.2 Wiring Options to Connect Networked Panels ......................................................................1
5.2 Model RPS-2000 .........................................................................................................................1
5.3 Direct Connect Wiring Option ......................................................................................................1
5.3.1 Installing using Direct Connection within a Site: ...................................................................2
5.4 Repeater Wiring Options .............................................................................................................3
5.4.1 Network Repeater Types ......................................................................................................3
5.4.1.1 Accessory Mounting Kits .............................................................................................4
5.4.2 Network Repeater Installation ...............................................................................................4
5.4.2.1 Network Repeater Cable Requirements .....................................................................5
5.4.2.2 Unshielded Twisted Pair Wiring between Multiple Panels ..........................................5
5.4.2.3 Fiber Optic Repeater Wiring between Multiple Panels ................................................6
5.4.2.4 Fiber Optic and Twisted Pair Repeater Wiring between Multiple Panels .................... 6
5.5 Using Both Repeaters and Direct Connect
Wiring on a Networked System ...................................................................................................8
5.5.1 Setting the Network Terminators at Panel DIP Switches and Repeater Jumpers ................8
5.6 Setting the Network ID for each Panel ......................................................................................10
Section 6
Network Management .....................................................................................................................1
6.1 Network Diagnostics ....................................................................................................................1
6.1.1 Ping Panel .............................................................................................................................1
6.1.2 Network Status ......................................................................................................................1
6.1.3 Repeater Power .................................................................................................................... 1
6.2 Network Programming .................................................................................................................1
6.2.1 Learn Network ....................................................................................................................... 1
6.2.2 Edit Network Names .............................................................................................................2
6.2.3 Edit Panel ID .........................................................................................................................2
6.2.4 Computer Access ..................................................................................................................3
6.3 Access Codes .............................................................................................................................4
6.3.1 Edit Name .............................................................................................................................6
6.3.2 Edit Access Code ..................................................................................................................6
6.3.3 Panel Functions ....................................................................................................................6
6.4 Dialer ...........................................................................................................................................6
6.4.1 Dialer Assignments ............................................................................................................... 6
6.4.2 Dialer Miscellaneous .............................................................................................................6
6.4.3 Receiver Configuration .........................................................................................................6
6.4.4 Dialer Report Table ...............................................................................................................7
6.5 Voice Options ..............................................................................................................................7
6.5.1 Edit Timers ............................................................................................................................7
6.5.1.1 Control Lockout ...........................................................................................................7

6.5.1.2 Auto Reset ECS Custom Event/Auto Reset ECS Event .............................................7
6.5.2 Edit Voice Commands ..........................................................................................................8
6.6 Sync Network Options .................................................................................................................9
6.7 Network Management Quick Reference ................................................................................... 10
Section 7
IDP and SD SLC Device Installation ..........................................................................1
7.1 List of IDP SLC Devices ..............................................................................................................1
7.2 List of SD SLC Devices ............................................................................................................... 2
7.3 Maximum Number of SLC Devices .............................................................................................3
7.4 Wiring Requirements for SLC Devices ........................................................................................3
7.4.1 Wiring 5815XL in Style 4 (Class B) Configuration ................................................................3
7.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration ..........................................................5
7.5 Wiring IDP SLC Detectors ........................................................................................................... 6
7.6 Addressing IDP SLC Devices ......................................................................................................7
7.7 Wiring SD Detectors ....................................................................................................................8
7.8 Addressing SD Devices ...............................................................................................................9
7.8.1 SD505-PHOTO & SD505-HEAT ........................................................................................... 9
7.8.2 SLC Devices with DIP Switches .........................................................................................10
Section 8
Programming Overview ...............................................................................................................1
8.1 Security and Data Protection .......................................................................................................1
8.2 JumpStart AutoProgramming ......................................................................................................1
8.2.1 Input Points ...........................................................................................................................1
8.2.2 Output Points ........................................................................................................................2
8.2.3 Running JumpStart AutoProgramming ................................................................................. 2
8.3 Mapping Overview .......................................................................................................................4
8.3.1 Input Point Mapping ..............................................................................................................5
8.3.2 Output Circuit Mapping .........................................................................................................6
8.3.3 Event Mapping ..................................................................................................................... 7
8.3.4 Mapping LED Points ...........................................................................................................13
8.3.5 Mapping LED Points for a Networked System ....................................................................14
8.4 Programming Using the 5655 Silent Knight PC
Configuration Software ..............................................................................................................14
8.5 Programming Using an Annunciator .........................................................................................14
8.5.1 Entering & Exiting Panel Programming ...............................................................................15
8.5.1.1 Moving through the Menus ........................................................................................ 15
8.5.1.2 Selecting Options and Entering Data ........................................................................15
8.5.1.3 Editing Keys ..............................................................................................................16
8.6 Programming Menu Quick Reference .......................................................................................17
Section 9
Programming .............................................................................................................................................1
9.1 UL 864 / UL 2572 Programming Requirements ..........................................................................1
9.2 Modules .......................................................................................................................................1
9.2.1 Edit Modules ......................................................................................................................... 2

9.2.1.1 Editing Module ID ........................................................................................................2
9.2.1.2 Naming Modules .........................................................................................................2
9.2.1.3 Changing Module Options ...........................................................................................2
9.2.2 Adding a Module ...................................................................................................................3
9.2.3 Deleting a Module ................................................................................................................. 3
9.2.4 View Module List ...................................................................................................................3
9.3 Zone ............................................................................................................................................3
9.3.1 Edit Zone ...............................................................................................................................4
9.3.1.1 Edit Zone Name ..........................................................................................................4
9.3.1.2 Edit Zone Properties ...................................................................................................4
9.3.1.3 Zone Accessory Options ............................................................................................. 6
9.3.2 View Zone Points .................................................................................................................. 7
9.4 Group ..........................................................................................................................................7
9.4.1 Edit Group .............................................................................................................................7
9.4.1.1 Edit Group Name ........................................................................................................8
9.4.1.2 Edit Group Properties ..................................................................................................8
9.4.2 View Group Points ................................................................................................................9
9.4.3 Edit OPG Template ...............................................................................................................9
9.5 Point ..........................................................................................................................................10
9.5.1 Point Programming For 5815XL Module .............................................................................10
9.5.2 Point Programming For Internal or External Power Module (RPS-1000) ...........................14
9.5.3 Point Programming For 5880/5865 Modules ......................................................................16
9.5.4 Point Programming for 5496 ...............................................................................................17
9.5.5 Point Programming for ECS-AMP’s ....................................................................................17
9.5.6 Point Programming for ECS-VCM or ECS-RVM .................................................................18
9.6 System Options .........................................................................................................................20
9.6.1 Auto Test Time ....................................................................................................................20
9.6.2 Phone Lines ........................................................................................................................ 21
9.6.2.1 Dialing Prefix .............................................................................................................21
9.6.2.2 Number of Answer Rings ..........................................................................................21
9.6.2.3 Dial Option (TouchTone or Pulse, or TT/PL) .............................................................22
9.6.2.4 Rotary Format ...........................................................................................................22
9.6.2.5 Dial Tone Detection Disabled ....................................................................................22
9.6.2.6 Line Monitor .............................................................................................................. 22
9.6.2.7 Answering Machine Bypass ......................................................................................22
9.6.2.8 Phone Line Unused ...................................................................................................22
9.6.3 Daytime/Nighttime Sensitivity .............................................................................................23
9.6.4 Holiday Days .......................................................................................................................23
9.6.5 Time Options .......................................................................................................................24
9.6.5.1 Water Flow Delay ......................................................................................................24
9.6.5.2 Alarm Verification Time .............................................................................................24
9.6.5.3 Low AC Report Delay ................................................................................................24
9.6.5.4 Change AC Line Frequency ...................................................................................... 25
9.6.5.5 Clock Display Format (AM/PM or Military) ................................................................25
9.6.6 Miscellaneous Options ........................................................................................................25
9.6.6.1 Strobes Active when Silenced ................................................................................... 25
9.6.6.2 Auto Display Events ..................................................................................................25
9.6.6.3 IFP-RPT Repeater Installed ......................................................................................25
9.6.6.4 Both Ports Used ........................................................................................................26
9.6.7 Daylight Saving Options ......................................................................................................26
9.6.7.1 Automatic Daylight Saving Adjustment .....................................................................26
9.6.7.2 Daylight Saving Time Start and End .........................................................................26
9.6.8 Edit Banner .........................................................................................................................27
9.6.9 Edit SLC Family ..................................................................................................................27

9.6.10 Edit Ethernet ......................................................................................................................27
9.7 JumpStart AutoProgramming ....................................................................................................28
9.8 Restore Defaults ........................................................................................................................28
9.9 Voice Options ............................................................................................................................ 28
9.9.1 ECS-VCM Maintenance ......................................................................................................28
9.9.2 Edit Voice Settings ..............................................................................................................29
9.9.2.1 Enable Dual Channel System ...................................................................................29
Section 10
System Operation ................................................................................................................................1
10.1 User and Installer Default Codes ................................................................................................1
10.2 Annunciator Description ..............................................................................................................1
10.2.1 LCD Display .........................................................................................................................1
10.2.2 Banner .................................................................................................................................2
10.3 Menu System ..............................................................................................................................2
10.3.1 Main Menu Overview ...........................................................................................................2
10.3.2 Using the Menus ..................................................................................................................3
10.4 Basic Operation ...........................................................................................................................3
10.4.1 Setting Time and Date .........................................................................................................3
10.4.2 Disable / Enable a Point ......................................................................................................3
10.4.2.1 Disable / Enable NACs by Template ..........................................................................3
10.4.2.2 Disable / Enable NACs by Group ...............................................................................3
10.4.2.3 Disable / Enable Zone Points .....................................................................................3
10.4.2.4 Disable / Enable Point ................................................................................................3
10.4.2.5 Inhibit Output Group ...................................................................................................4
10.4.3 View Event History ..............................................................................................................4
10.4.3.1 To clear the event history ...........................................................................................4
10.4.4 Conduct a Fire Drill ..............................................................................................................4
10.4.5 Conduct an Indicator Test ...................................................................................................4
10.4.6 Conduct a Walk Test ...........................................................................................................5
10.4.7 Conduct a Dialer Test ..........................................................................................................5
10.4.8 Silence Alarms or Troubles .................................................................................................5
10.4.9 Reset Alarms ......................................................................................................................5
10.4.10 Check Detector Sensitivity Through Point Status .............................................................6
10.4.11 View Status of a Point ......................................................................................................6
10.4.12 View Alarms or Troubles ..................................................................................................7
10.4.13 System Information ...........................................................................................................7
10.4.14 Communicating with a Remote Computer ........................................................................7
10.5 Event Priority ...............................................................................................................................8
10.5.1 System Control ....................................................................................................................8
10.5.2 System Override ..................................................................................................................8
10.5.3 Event Priority .......................................................................................................................8
10.5.4 Priority Rules .......................................................................................................................9
10.5.5 Other Priority Considerations ..............................................................................................9
10.6 Operation Mode Behavior .........................................................................................................10
10.7 Releasing Operations ................................................................................................................15
10.7.1 Single Interlock Zone Releasing ........................................................................................17
10.7.2 Double Interlock Zone Releasing ......................................................................................18
10.8 Smoke Alarm Verification ..........................................................................................................19
10.9 Function Keys ........................................................................................................................... 19
10.9.1 Recording an F-Key Macro ................................................................................................19

10.9.2 Aborting an F-Key Macro Recording Session ...................................................................19
10.9.3 Erasing an F-Key Macro ....................................................................................................20
10.9.4 Using a Recorded F-Key Macro ........................................................................................20
10.9.5 F-Key Status Event ............................................................................................................20
10.9.6 F-Key Map Inhibit ..............................................................................................................20
Section 11
Emergency Communication System Operation ..........................................1
11.1 Overview .....................................................................................................................................1
11.2 LOC Functionality ........................................................................................................................1
11.2.1 Keys and LEDs .................................................................................................................... 1
11.2.1.1 ECS Control Key ........................................................................................................1
11.2.1.2 ECS Control LED .......................................................................................................1
11.2.1.3 ECS Message Keys ...................................................................................................2
11.2.1.4 ECS Message LEDs ..................................................................................................2
11.2.1.5 Select Keys ................................................................................................................2
11.2.1.6 Select Key LEDs ........................................................................................................2
11.2.2 Gaining ECS Control ...........................................................................................................3
11.2.2.1 LOC Priority ................................................................................................................3
11.2.2.2 LOC Lockout ..............................................................................................................3
11.2.2.3 User Profile Access Control ....................................................................................... 4
11.2.3 Manual ECS ........................................................................................................................4
11.2.3.1 Switching between Microphone Mode and Message Mode .......................................4
11.2.3.2 Activating Output Groups Dynamically .......................................................................4
11.2.4 Microphone Mode ................................................................................................................4
11.2.5 Message Mode ....................................................................................................................5
11.2.6 Custom ECS Event ..............................................................................................................5
11.2.7 Passing ECS Control ...........................................................................................................5
11.2.8 Exit ECS Control Menu ........................................................................................................6
11.2.9 Relinquish ECS Control .......................................................................................................6
11.2.10 ECS Reset ........................................................................................................................6
11.3 ECS Super User ..........................................................................................................................6
11.4 ECS Point Functionality ...............................................................................................................7
11.4.1 ECS Point Activations ..........................................................................................................7
11.4.2 ECS-VCM Points .................................................................................................................7
11.5 Amplifier Programming ................................................................................................................7
11.5.1 Adding an Amplifier .............................................................................................................7
11.5.2 Editing an Amplifier ..............................................................................................................8
11.6 LOC Programming ......................................................................................................................8
11.6.1 Adding an LOC ....................................................................................................................8
11.6.2 Editing an LOC ....................................................................................................................8
11.6.2.1 LOC Priority ................................................................................................................9
11.6.2.2 LOC Association ........................................................................................................9
11.7 Using the Microphone .................................................................................................................9
11.7.1 Microphone Functionality .....................................................................................................9
11.7.2 Custom ECS Event ..............................................................................................................9
11.7.3 Fire Page .............................................................................................................................9
11.7.4 Emergency Page ................................................................................................................. 9
11.7.4.1 Paging ......................................................................................................................10
11.8 Recording Custom Messages ...................................................................................................10
11.8.1 Recording Messages 1-15 Using Aux Audio Input ............................................................ 11

11.8.2 Recording Messages 1-15 Using the Microphone .............................................................13
11.8.3 Erasing User Message ......................................................................................................15
11.8.4 Using Farenhyt ECS Message Manager Software Tool ....................................................15
Section 12
Reporting .........................................................................................................................................................1
12.1 Receivers Compatible with the Control Panel .............................................................................1
12.2 Reporting Formats Table .............................................................................................................1
12.3 SIA - IntelliKnight / IFP-2000 Panels PI Modifier Reporting: .....................................................13
12.4 SIA – IFP-2000 Panel Dialer: ....................................................................................................14
Section 13
Testing and Troubleshooting ...............................................................................................1
13.1 Troubleshooting ...........................................................................................................................1
13.2 Common Problems ......................................................................................................................1
13.3 Periodic Testing and Maintenance ..............................................................................................2
13.4 Event History ...............................................................................................................................2
13.5 Built-in Troubleshooting and Testing Tools .................................................................................3
13.5.1 SLC Device Locator .............................................................................................................3
13.5.2 SLC Multiple Device Locator ...............................................................................................3
13.5.3 I/O Point Control .................................................................................................................. 4
13.5.4 Earth Fault Resistance ........................................................................................................4
Section 14
Installation Records ..........................................................................................................................1
14.1 Detector and Module Point Record .............................................................................................1
14.2 Conventional Output Point Record ..............................................................................................5

Appendix A
Compatible Devices ..........................................................................................................................1
Appendix B
Editing Text Using the Built-In Programmer ....................................................1
Appendix C
Cadence Patterns .................................................................................................................................1
Honeywell Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
Model IFP-2000 Basic Operating Instructions
Model IFP-2000ECS / ECS-RCU2000 Basic Operating
Instructions

Model IFP-2000/ECS Installation Manual 151430-L8
1-1
Section 1
Introduction
The IFP-2000 Fire Alarm Control/Communicator is an analog addressable fire control system that meets the
requirements of UL 864. The RPS-2000 is used in a networked system where there is at least one IFP-2000 in the
system. The RPS-2000 is the same as the IFP-2000 without the display. When using the RPS-2000 as a stand
alone local unit, one RA-2000 must be connected, and the RA-2000 must be wired in conduit within 20’ of the
RPS-2000.
The IFP-2000ECS Fire Alarm Control/Communicator is an analog addressable fire control system combined
with an Emergency Communication System that meets the requirements of UL standard 2572.
1.1 Overview of Basic System
The IFP-2000 base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum
housing.
1.1.1 Hardware Features
• The basic IFP-2000 panel contains one built in signaling line circuit (SLC), which supports up to 159 IDP
sensors and 159 IDP modules or 127 SD SLC devices. Additional SLC loops can be added using the model
5815XL SLC expander to increase overall point capacity to a maximum of 636 points. The SLC(s) supports
both the SD Protocol and Intelligent Device Protocol (IDP).
• Each SLC supports 159 IDP sensors and 159 IDP modules or 127 SD devices to a maximum of 636 points
per IFP-2000 control panel.
• 9.0A of output power is available through 8 sets of terminals for notification and auxiliary applications.
Each circuit is power limited per UL 864 and can source up to 3.0A (total output power must not exceed
9.0A). The constant auxiliary power load must not exceed 6.0A for normal standby.
• Built-in dual phone line, digital alarm communicator/transmitter (DACT).
• Reports events to central station by point or by zone.
• UL Listed for pre-action and deluge releasing systems.
• Dedicated Form C trouble relay and two general purpose Form C programmable relays.
• Can be used with Model RA-2000 remote annunciators (sold separately).
• Supports the 5865-3, 5865-4, and 5880 LED annunciators. See sections 4.8 and 4.9 for additional
information on these models (sold separately).
• Printing of event log available through the Model 5824 serial/parallel printer interface module (sold
separately).
• Supports conventional 2-wire & 4-wire detectors using the 8 Flexput™ circuits or SLC zone modules.
• 999 software zones, 999 output groups.
• Add four notification/auxiliary power circuits with each 5496 Intelligent Power Module.
• Add six Flexput™ circuits with each RPS-1000 Remote Power Supply.
• Interconnection capability for up to eight panels.
1.1.2 Network System Hardware Features
• The default network setup can contain up to eight IFP-2000 / RPS-2000 panels connected within a
networked system providing a maximum addressable point capacity of 5,088.
• The networked system can be configured to emulate a large virtual system or can be segmented into separate

151430-L8 Introduction
1-2
sites for multiple building applications.
• Each building is referred to as a “site”. All panels in a site operate as a single panel.
• Panels can be interconnected using a BUS or CLASS A (style 7) topology.
• Panels can be connected cost effectively via shielded twisted pair copper wire within conduit when the
panels are located no more than 20 feet apart and within the same room.
• Panels separated by more than 20 feet or located in multiple buildings use IFP-RPT network repeater
hardware to provide up to 3000 ft. of separation with twisted pair copper wire or up to 8dB loss of signal
separation for fiber optic cable. Both methods of panel connectivity can be used within the same networked
system.
• The network architecture provides true peer to peer capability allowing network survivability for all
hardware that remains operational in the event of partial system failure.
1.1.3 Software Features
• Advanced analog smoke detector features:
Three sensitivity settings (high, medium, low)
Automatic drift compensation
Maintenance alert region
Point status meets calibrated smoke test requirements for NFPA 72
Automatic day/night sensitivity adjustment
• “JumpStart AutoProgramming” feature for easy programming
• Non-volatile event history stores 1000 events per panel
• A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal
• Built-in synchronization appliance support for AMSECO, Gentex®, System Sensor®, and Wheelock®
1.1.4 IFP-2000ECS Features
• 15 Recordable one minute messages that can be mapped to eight ECS buttons.
• ECS messages can be selected as priority over fire.
• Support of up to 15 ECS-RCU2000’s. The ECS-RCU2000 meets the requirements for an LOC.
• Programmable trigger inputs from an external source, such as a Monaco system, to either the ECS-VCM,
ECS-RVM or 5880. Up to eight inputs available on the 5880 module.
• Support for up to 16 SBUS addressable amplifiers using a combination of ECS-50W, ECS-125W, ECS-
INT50W or ECS-DUAL50W for a maximum of 2000 watts per system and up to 128 mappable speaker
circuits.
• Support for dual channel and backup audio using the ECS-DUAL50W amplifier and ECS-50WBU back-up
amplifier.
• Single enclosure for both Fire and Emergency Control System components.
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the IFP-2000, IFP-
2000ECS*, IFP-2000HV, IFP-2000ECSHV**, RPS-2000, and RPS-2000HV.
Please let us know if the manual does not meet your needs in any way. We value your feedback!
* All references to IFP-2000 within this manual are applicable to the IFP-2000ECS.
** All references to IFP-2000HV within this manual are applicable to the IFP-2000ECSHV.

Model IFP-2000/ECS Installation Manual 151430-L8
1-3
1.2.1 Terms Used in this Manual
The following terminology is used with the above mentioned control panels:
Term Description
SLC Signaling line circuit
Module The term module is used for all hardware devices except for SLC addressable devices
and notification appliances. This includes the IFP-2000/RPS-2000 panels itself and the
built-in power supply. It also refers to any (optional) 5815XL SLC expansion module.
Input Point An addressable sensing device, such as a smoke, heat detector or a contact monitor
device
Input Zone A protected area made up of input points
Output Point
(or “Output Circuit”)
A notification point or circuit for notification appliances. Relay circuits and auxiliary power
circuits are also considered output points
Group (or “Output Group” or
OPG)
A group of output points. Operating characteristics are common to all output points in a
group
Mapping Mapping is the process of specifying which outputs are activated when certain events
occur in the system. Section 8.3 explains mapping in detail
Networking Up to 8 panels can be networked to sites that act like one panel
ECS Emergency Communication System

151430-L8 Introduction
1-4
1.3 Compatible Products
Table 1-1 lists the products available from Silent Knight for use with the IFP-2000.
Table 1-1: IFP-2000 Compatible Products
Type of Device Model Description
IDP Addressable
SLC Devices
See Section 7.1 for a list of compatible devices
SD Addressable
SLC Devices
See Section 7.2 for a list of compatible devices
Other Modules
5815XL SLC Expander Each 5815XL allows up to 159 IDP sensors and 159 IDP modules or up to 127
SD devices to be added to the system. The number of 5815XLs that can be
added to the system is limited only by the maximum number of SBUS devices.
However the maximum point count is limited to 636 per panel. This allows the
installer to distribute the 636 points on more than two SLC loops and also allows
all 636 points to be all sensors or all modules or any combination of sensors and
modules.
RPS-2000 Addressable
Power Supply w/no
display
Same operation as IFP-2000 without display
5824 Serial/Parallel
Printer Interface Module
Allows a printer to be attached for the on-site event logging. Maximum of two
5824s per control panel.
RPS-1000 Intelligent
Power Module
Provides additional power, six Flexput™ circuits, and two Form C relays. See
Model RPS-1000 Installation Instructions P/N 151024.
5496 Intelligent Power
Module
Provides four additional Notification Appliance Circuits/Auxiliary power
RA-2000 Remote Fire
Alarm Annunciator
Same operation, similar appearance as on-board annunciator
5865-3 and 5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has
key switches for silence and reset, and a system trouble LED.
5880 LED I/O Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In
addition, the 5880 has eight generic switch input points.
5883 General Purpose
Relay Module
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s
can be used with each 5880 module.
VIP-50* 50 watt audio amplifier
VIP-125** 125 wall audio amplifier
ECS-VCM Voice Control Module used with the IFP-2000ECS
Refer to the ECS-Series
installation manual PN
151455 for more info on
these accessories.
ECS-SW24 24 Switch expander
ECS-50W 50 watt audio amplifier
ECS-125W 125 watt audio amplifier
ECS-INT50W 50 watt Internal amplifier
ECS-CE4 Provides 4 additional audio circuits for the
ECS-50W or the ECS-125W
ECS-RVM Remote Voice Microphone used with the
IFP-2000ECS
ECS-DUAL50W Dual Channel amplifier
ECS-50WBU Backup daughter card
IFP-2000ECS Contains IFP-2000 and ECS-VCM in single cabinet.
Other Modules
(cont.)
IFP-RCU2000ECS Contains RA-2000 and ECS-RVM in single cabinet.

Model IFP-2000/ECS Installation Manual 151430-L8
1-5
The following modems have been tested by Silent Knight for compatibility with the Silent Knight Software Suite
software packages:
Misc.
7860 Telephone Cord RJ31X cord for connecting phone line to the IFP-2000.
Silent Knight 5655
Software Suite (SKSS-2)
For communication and panel programming with a Windows-based computer
and modem (not sold by Silent Knight, see Table 1-2 for compatible modems).
Enables remote viewing of detector status and event history.
RBB Remote Battery Box for mounting backup batteries up to 35AH that are too large
to fit into the main control panel cabinet.
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
AB-55 Remote Battery Box for mounting backup batteries up to 55AH that are too large
to fit into the main control panel cabinet.
Dimensions: 20" W x 12" H x 7.5" D (50.8 cm W x 30.48 cm H x 19.05 cm D)
Note: *All references to ECS-50W within this manual will be applicable to VIP-50.
Note: ** All references to ECS-125W within this manual will be applicable to VIP-125
Table 1-2: Compatible Modems
Manufacturer Model
US Robotics 28.8
Motorola
LifeStyle
28.8, 3400 series
Premier 33.6
MultiTech MT19321ZDX
Table 1-1: IFP-2000 Compatible Products
Type of Device Model Description

Model IFP-2000/ECS Installation Manual 151430-L8
2-1
Section 2
Agency Listings, Approvals, and Requirements
2.1 Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the IFP-2000 can be con-
nected to the phone lines:
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside
cover of this equipment is a label that contains, among other information, a product identifier. If requested, this
information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with
the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not
provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that
is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of
devices that may be connected to the public switched telephone network. This number must not exceed 5.0.
Since this product has an REN of 0.8, the number of devices is limited. The REN number is embedded in the
FCC registration number as 11B.
If the IFP-2000 / IFP-2000HV / IFP-2000ECS / IFP-2000ECSHV causes harm to the telephone network, the
telephone company will notify you in advance that the temporarily discontinuance of service may be required.
But if advance notice is not practical, the telephone company will notify the customer as soon as possible. Also,
you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect
the operation of the equipment. If this happens the telephone company will provide advance notice in order for
you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the IFP-2000 / IFP-2000HV / IFP-2000ECS / IFP-2000ECSHV, for repair or
warranty information, please contact Silent Knight at 1-800-328-0103 or www.silentknight.com. If the
equipment is causing harm to the telephone network, the telephone company may request that you disconnect the
IFP-2000 / IFP-2000HV / IFP-2000ECS / IFP-2000ECSHV until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state
tariffs. You may contact the state public utility commission, public service commission or corporation
commission for information.
Since the IFP-2000, IFP-2000HV, IFP-2000ECS, or IFP-2000ECSHV is a commercial fire alarm panel, it must
be connected upstream of all other equipment utilizing the phone lines. If you have questions about the
A Manufacturer: Silent Knight by Honeywell
B Model Number: IFP-2000 / IFP-2000ECS
C FCC registration number: AC6AL11B6820
Ringer equivalence: 0.8B
D Type of jack: RJ31X
E Facility Interface Codes: Loop Start: 02LS2
F Service Order Code: 9.0F

151430-L8 Agency Listings, Approvals, and Requirements
2-2
installation, contact your telephone company or a qualified installer.
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements. The following subsections list specific requirements for each
type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and
so on). See Section 10.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 7.1 (IDP devices) or Section 7.2 (SD devices) of
this manual and/or conventional detectors listed in the compatibility chart in Appendix A.
3. Use UL listed notification appliances compatible with the IFP-2000 from those specified in Appendix A of
this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
• The loss of AC signal is defaulted to 3 hours, but the system still allows settings from 0 - 30 hours. For UL
certified installations, this number must be set from 1 to 3 hours.
• The system allows the use of non-latching, spot type smoke detectors. This feature may not be used in
commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding
applications, and hotel/motel room applications.
• The system allows the Alarm Verification confirmation time to be set from 1 to 250 seconds. For UL
certified installations the setting must be a minimum of 60 seconds.
• Call forwarding shall not be used.
• When two count is used: detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.
• P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
• No ECS initiating devices on SLC loops.
2.2.2 Requirements for Central Station Fire Alarm Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the IFP-2000 sends an automatic daily test to the
central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1)
This device may not cause radio interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
This manual suits for next models
2
Table of contents
Other Honeywell Conference System manuals

Honeywell
Honeywell Mark III Installation guide

Honeywell
Honeywell ECS Series Operating instructions

Honeywell
Honeywell Farenhyt ECS Series User manual

Honeywell
Honeywell ASPIRE-200 Operating instructions

Honeywell
Honeywell JetWave User manual

Honeywell
Honeywell TA3840 User manual

Honeywell
Honeywell AlarmNet IGSMV Assembly instructions

Honeywell
Honeywell THALES MCS-4200 Manual

Honeywell
Honeywell ASPIRE-400 Operating and installation instructions

Honeywell
Honeywell QUIETPRO QP100Ex User manual